APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)

SCREEN NAME

POINT NAME

 

PASSWORD

EDITABLE

RANGE

DEFAULT

NOTES

 

LEVEL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Defines the hysteresis applied above

 

 

SPT Occupied Alarm

 

 

X

2 - 20 ° F

5 ° F

the cooling and below the heating set

 

 

Hysteresis

 

 

points before an alarm condition will

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

occur

 

 

 

 

 

 

 

 

Used to calculate the delay time before

 

 

SPT Alarm Delay

 

 

X

0 - 30 min per degree

10 min

an alarm is generated after the alarm

 

 

 

 

 

 

 

 

condition occurs

 

 

SPT Unoccupied Low

 

 

X

35 - 90 ° F

45 ° F

Defines the fixed unoccupied

 

 

Alarm Temperature

 

 

ow SPT alarm limit

 

 

 

 

 

 

 

 

 

SPT Unoccupied High

 

 

X

45 - 100 ° F

95 ° F

Defines the fixed unoccupied

 

 

Alarm Temperature

 

 

high SPT alarm limit

 

 

 

 

 

 

 

 

 

SAT Low SAT

 

 

X

15 - 90 ° F

45 ° F

Defines the fixed minimum

 

 

Alarm Limit

 

 

SAT alarm limit

 

 

 

 

 

 

 

 

 

SAT High SAT

 

 

X

90 - 175 ° F

120 ° F

Defines the fixed maximum

 

 

Alarm Limit

 

 

SAT alarm limit

 

 

 

 

 

 

 

 

 

Condensate Overflow

 

 

 

 

 

Defines the delay time before an alarm

 

 

 

 

X

5 - 600 sec

10 sec

is generated after the alarm condition

 

 

Alarm Delay

 

 

 

 

 

 

 

 

 

occurs

 

 

 

 

 

 

 

 

 

 

Space Humidity Occupied

 

 

X

45% - 100%

100%

Defines the fixed occupied

 

 

High Alarm Limit

 

 

high space RH alarm limit

 

 

 

 

 

 

 

 

 

Space Humidity Alarm

 

 

 

 

 

Used to calculate the delay time before

Configuration

 

 

X

0 - 30 min per % RH

5 min

an alarm is generated after the alarm

Delay

 

 

 

 

 

 

 

 

 

condition occurs

 

 

 

 

 

 

 

 

 

Space Humidity Unoccu-

 

Admin Password

X

45% - 100%

100%

Defines the fixed unnoccupied

 

 

pied High Alarm Limit

 

level access only

high space RH alarm limit

 

 

 

 

 

 

 

Alarm

IAQ/Ventilation Occupied

 

 

X

0 - 9999 ppm

1100 ppm

Defines the fixed occupied high

Configuration

High Alarm Limit

 

 

space IAQ/Ventilation alarm limit

 

 

 

 

 

 

 

IAQ/Ventilation

 

 

 

 

 

Used to calculate the delay time before

 

 

 

 

X

0.1 - 1.0 min per ppm

0.25 min

an alarm is generated after the alarm

 

 

Alarm Delay

 

 

 

 

 

 

 

 

 

condition occurs

 

 

 

 

 

 

 

 

 

 

Rnet Sensor SPT Alarm

 

 

X

Ignore/Display

Ignore

Determines if the SPT alarm is

 

 

 

 

displayed on the local Rnet sensor

 

 

 

 

 

 

 

 

 

 

Rnet Sensor SAT Alarm

 

 

X

Ignore/Display

Ignore

Determines if the SAT alarm is

 

 

 

 

displayed on the local Rnet sensor

 

 

 

 

 

 

 

 

 

 

Rnet Sensor Compressor

 

 

 

 

 

Determines if the Compressor Lockout

 

 

 

 

X

Ignore/Display

Display

alarm is displayed on the local Rnet

 

 

Lockout Alarm

 

 

 

 

 

 

 

 

 

sensor

 

 

 

 

 

 

 

 

 

 

Rnet Sensor Condenser

 

 

 

 

 

Determines if the Condenser Water

 

 

 

 

X

Ignore/Display

Display

Temperature alarm is displayed on the

 

 

Water Temperature Alarm

 

 

 

 

 

 

 

 

 

local Rnet sensor

 

 

 

 

 

 

 

 

 

 

Rnet Sensor Condensate

 

 

 

 

 

Determines if the Condensate

 

 

 

 

X

Ignore/Display

Display

Overflow alarm is displayed on the

 

 

Overflow Alarm

 

 

 

 

 

 

 

 

 

local Rnet sensor

 

 

 

 

 

 

 

 

 

 

Rnet Sensor Dirty

 

 

X

Ignore/Display

Display

Determines if the Dirty Filter alarm is

 

 

Filter Alarm

 

 

displayed on the local Rnet sensor

 

 

 

 

 

 

 

 

 

Rnet Sensor Space

 

 

 

 

 

Determines if the High Space

 

 

 

 

X

Ignore/Display

Ignore

RH alarm is displayed on the

 

 

High Humidity Alarm

 

 

 

 

 

 

 

 

 

local Rnet sensor

 

 

 

 

 

 

 

 

Configuration

Loop Control Network

 

 

 

 

 

See TPI

Number

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Loop Control Network

 

 

 

 

 

See TPI

 

Address

 

 

 

 

 

 

 

 

 

 

 

 

 

Linkage

Number of Linked Heat

 

 

 

 

 

See TPI

Pumps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

BAS — Building Automation System

 

 

 

 

 

DCV

Demand Controlled Ventilation

 

 

 

 

 

IAQ

Indoor Air Quality

 

 

 

 

 

OAT

Outdoor Air Temperature

 

 

 

 

 

RH

Relative Humidity

 

 

 

 

 

SAT — Supply Air Temperature

 

 

 

 

 

SPT

Space Temperature

 

 

 

 

 

TPI

Third Party Integration

 

 

 

 

 

48

Image 48
Contents Contents Safety ConsiderationsInstallation General50PCH,PCV Unit Physical Data 203 218209 224 8412 Connections 50PCHOpening Unit IPTTypical Installation 50PCH Units A50-8413 Typical Vertical Installation 50PCV Units Install Condensate Drain Mount the UnitA50-8489 A50-6261tf Metal Hose Minimum Bend RadiiSlope to drain Wire Field Power Supply FittingLOC BMCMves NECRVS TXVHigh-Pressure Water Switch Power BlockHpws Clippable Field Selection JumperLoss of Charge Pressure Switch Condensate Pan Motorized Valve End Switch Temperature SwitchA50-8493 LONNational Electrical Code Temperature Switch A50-8440A50-8355 A50 83548356 LWT Wshp Open Control 50PCH,PCV Unit Electrical Data A50-8162MCA FLA HacrWire Field Controls A50-8441A50-8442 Rnet Wiring Specifications Rnet WiringField-Supplied Sensors for Wshp Open Controller SPT SensorsPRE-START-UP Blower Speed Selection50PCV Blower Performance with Hot Water Reheat HWR Option 50PCV Blower Performance with Wet Coil50PCH,PCV Blower Performance Standard Unit 50PCH,PCV Blower Performance High-Static UnitComplete C Control Jumper Settings Refer to Deluxe D Control Jumper Settings Refer to , 15,Field Selectable Inputs DIP Switch Block S2 Accessory 1 Relay Options DIP Switch Block S2 Accessory 2 Relay OptionsSTART-UP Operating LimitsUnit Start-Up Cooling Mode Water Temperature Change Through Heat ExchangerOperating Limits 50PCH,PCV Units 50PC024 Typical Unit Operating Pressures and Temperatures 50PC030 Typical Unit Operating Pressures and Temperatures50PC036 Typical Unit Operating Pressures and Temperatures 50PC042 Typical Unit Operating Pressures and Temperatures 50PC048 Typical Unit Operating Pressures and Temperatures50PC060 Typical Unit Operating Pressures and Temperatures Temp GPM/ton Pressure HeatUnit Start-Up Heating Mode Unit Start-Up with Wshp Open ControlsCoaxial Water Pressure Drop 50PC Pressure DROP, psi kPaGpm 30 F 50 F 70 F 90 F SizeApproximate Fluid Volume gal Per 100 Ft of Pipe Antifreeze Percentages by VolumeOperation Units with Aquazone Complete C ControlUnits with Wshp Open Multiple Protocol Auxiliary Modulating Hot Water/Steam Heating Reheat Page Complete C Control LED Code Fault Descriptions Complete C and Deluxe D Board System TestAquazone Deluxe D Control LED Indica Service Description Status LED Test LEDESD Refrigerant Charging Air Coil Fan Motor Removal’ to 4’ Troubleshooting Replacing the Wshp Open Controller’s BatA50-8163 Troubleshooting Air temperature out of rangeCooling mode FP1125 F or Reduced or no airflow in heatReduced or no water flow Reduced airflow in coolingAppendix a Wshp Open Screen Configuration Alarm StatusStatus SensorAppendix a Wshp Open Screen Configuration MaintenanceSystem Settings ConfigurationSchedule Appendix a Wshp Screen Open Configuration ServiceTest Configuration Service Point Name Password Editable Range Default LevelScreen Name Alarm Page Copyright 2009 Carrier Corporation 50PCH,PCV START-UP Checklist II. START-UPHeating Cycle Analysis Cooling Cycle AnalysisA50-8445 A50-8446

PCV015-060 specifications

The Carrier PCV015-060 is a cutting-edge packaged cooling and heating unit designed for commercial applications that demand high efficiency, reliability, and adaptability. This model is particularly renowned for its robust performance, making it an ideal choice for businesses seeking optimal indoor climate control.

One of the standout features of the PCV015-060 is its impressive energy efficiency. Equipped with advanced scroll compressors, this unit operates with a higher energy efficiency ratio (EER), translating to lower operational costs and reduced environmental impact. The incorporation of eco-friendly refrigerants further bolsters its sustainability credentials, ensuring compliance with modern environmental regulations.

The PCV015-060 showcases superior airflow design, which minimizes noise levels while maximizing thermal comfort. Its high-efficiency evaporator and condenser coils facilitate enhanced heat transfer, ensuring effective cooling and heating performance even in extreme weather conditions. This model is also designed with multiple fan speed options, allowing users to customize air distribution according to specific requirements.

Built with user-friendly controls, the Carrier PCV015-060 supports advanced digital thermostat interfaces, enabling precise temperature management. Optional integration with building management systems allows for remote monitoring and control, enhancing operational efficiency and simplifying maintenance tasks.

Durability is another hallmark of the PCV015-060. The unit is constructed using high-quality materials designed to withstand varying environmental conditions, which enhances the lifespan of the system. Additionally, its modular design simplifies installation and service access, reducing downtime for businesses.

The versatility of the PCV015-060 is underscored by its capability to function effectively in numerous configurations, including rooftop installations and ground-mounted setups. It can efficiently handle diverse applications, from offices to retail spaces, making it an adaptable choice for many commercial needs.

In summary, the Carrier PCV015-060 offers a blend of energy efficiency, advanced technology, and durable construction, making it a formidable solution for businesses seeking reliable climate control. Its commitment to sustainability, user-friendly features, and versatile configurations solidify its standing as a premier choice for commercial heating and cooling needs. With the PCV015-060, businesses can ensure a comfortable environment for both employees and customers while maintaining operational efficiency.