Carrier PCV015-060 specifications Refrigerant Charging, Air Coil Fan Motor Removal, ’ to 4’

Page 39

of dishwasher detergent and water is recommended for cleaning both sides of the coil, followed by a thorough water rinse. Clean coil with a stiff brush, vacuum cleaner, or com- pressed air. Use a fin comb of the correct tooth spacing when straightening mashed or bent coil fins.

Condenser Cleaning — Water-cooled condensers may require cleaning of scale (water deposits) due to improperly maintained closed-loop water systems. Sludge build-up may need to be cleaned in an open water tower system due to induced contaminants.

Local water conditions may cause excessive fouling or pitting of tubes. Condenser tubes should therefore be cleaned at least once a year, or more often if the water is contaminated.

Proper water treatment can minimize tube fouling and pitting. If such conditions are anticipated, water treatment analysis is recommended. Refer to the Carrier System Design Manual, Part 5, for general water conditioning information.

CAUTION

Follow all safety codes. Wear safety glasses and rubber gloves when using inhibited hydrochloric acid solution. Observe and follow acid manufacturer’s instructions.

Clean condensers with an inhibited hydrochloric acid solution. The acid can stain hands and clothing, damage concrete, and, without inhibitor, damage steel. Cover sur- roundings to guard against splashing. Vapors from vent pipe are not harmful, but take care to prevent liquid from being carried over by the gases.

Warm solution acts faster, but cold solution is just as effec- tive if applied for a longer period.

GRAVITY FLOW METHOD — Do not add solution faster than vent can exhaust the generated gases.

When condenser is full, allow solution to remain overnight, then drain condenser and flush with clean water. Follow acid manufacturer’s instructions. See Fig. 32.

FILL CONDENSER WITH

 

CLEANING SOLUTION. DO

PAIL

NOT ADD SOLUTION

 

MORE RAPIDLY THAN

 

VENT CAN EXHAUST

 

GASES CAUSED BY

FUNNEL

CHEMICAL ACTION.

 

1”

 

PIPE

VENT

 

PIPE

5’ APPROX

 

3’ TO 4’

CONDENSER

PAIL

Fig. 32 — Gravity Flow Method

FORCED CIRCULATION METHOD — Fully open vent pipe when filling condenser. The vent may be closed when condenser is full and pump is operating. See Fig. 33.

Regulate flow to condenser with a supply line valve. If pump is a nonoverloading type, the valve may be fully closed while pump is running.

For average scale deposit, allow solution to remain in condenser overnight. For heavy scale deposit, allow 24 hours. Drain condenser and flush with clean water. Follow acid manu- facturer’s instructions.

PUMP

PRIMING

GAS VENT

 

CONN.

GLOBE

 

 

 

 

VALVES

SUCTION

 

 

PUMP

 

SUPPLY

 

 

SUPPORT

 

 

 

 

1” PIPE

 

 

CONDENSER

TANK

 

REMOVE WATER

 

 

 

 

REGULATING VALVE

FINE MESH

 

RETURN

SCREEN

 

 

Fig. 33 — Forced Circulation Method

Checking System Charge — Units are shipped with full operating charge. If recharging is necessary:

1.Insert thermometer bulb in insulating rubber sleeve on liquid line near filter drier. Use a digital thermometer for all temperature measurements. DO NOT use a mercury or dial-type thermometer.

2.Connect pressure gage to discharge line near compressor.

3.After unit conditions have stabilized, read head pressure on discharge line gage.

NOTE: Operate unit a minimum of 15 minutes before checking charge.

4.From standard field-supplied Pressure-Temperature chart for R-410A, find equivalent saturated condens- ing temperature.

5.Read liquid line temperature on thermometer; then subtract from saturated condensing temperature. The dif- ference equals subcooling temperature.

6.Compare the subcooling temperature with the normal temperature listed in Tables 16-22. If the measured liquid line temperature does not agree with the required liquid line temperature, ADD refrigerant to raise the tempera- ture or REMOVE refrigerant (using standard practices) to lower the temperature (allow a tolerance of ± 3° F).

Refrigerant Charging

WARNING

To prevent personal injury, wear safety glasses and gloves when handling refrigerant. Do not overcharge system — this can cause compressor flooding.

NOTE: Do not vent or depressurize unit refrigerant to atmosphere. Remove and recover refrigerant following accepted practices.

Air Coil Fan Motor Removal

CAUTION

Before attempting to remove fan motors or motor mounts, place a piece of plywood over evaporator coils to prevent coil damage.

Disconnect motor power wires from motor terminals before motor is removed from unit.

39

Image 39
Contents Safety Considerations ContentsGeneral Installation50PCH,PCV Unit Physical Data 203 218209 224 IPT 8412Connections 50PCH Opening UnitTypical Installation 50PCH Units A50-8413 Typical Vertical Installation 50PCV Units Install Condensate Drain Mount the UnitA50-8489 A50-6261tf Metal Hose Minimum Bend RadiiSlope to drain Fitting Wire Field Power SupplyNEC LOCBMC MvesTXV RVSClippable Field Selection Jumper High-Pressure Water SwitchPower Block HpwsLON Loss of Charge Pressure Switch Condensate PanMotorized Valve End Switch Temperature Switch A50-8493A50-8440 National Electrical Code Temperature SwitchA50-8355 8354 A508356 LWT Wshp Open Control FLA Hacr 50PCH,PCV Unit Electrical DataA50-8162 MCAWire Field Controls A50-8441A50-8442 SPT Sensors Rnet Wiring SpecificationsRnet Wiring Field-Supplied Sensors for Wshp Open ControllerBlower Speed Selection PRE-START-UP50PCH,PCV Blower Performance High-Static Unit 50PCV Blower Performance with Hot Water Reheat HWR Option50PCV Blower Performance with Wet Coil 50PCH,PCV Blower Performance Standard UnitComplete C Control Jumper Settings Refer to Deluxe D Control Jumper Settings Refer to , 15,Field Selectable Inputs Operating Limits DIP Switch Block S2 Accessory 1 Relay OptionsDIP Switch Block S2 Accessory 2 Relay Options START-UPUnit Start-Up Cooling Mode Water Temperature Change Through Heat ExchangerOperating Limits 50PCH,PCV Units 50PC024 Typical Unit Operating Pressures and Temperatures 50PC030 Typical Unit Operating Pressures and Temperatures50PC036 Typical Unit Operating Pressures and Temperatures Temp GPM/ton Pressure Heat 50PC042 Typical Unit Operating Pressures and Temperatures50PC048 Typical Unit Operating Pressures and Temperatures 50PC060 Typical Unit Operating Pressures and TemperaturesUnit Start-Up with Wshp Open Controls Unit Start-Up Heating ModeSize Coaxial Water Pressure Drop50PC Pressure DROP, psi kPa Gpm 30 F 50 F 70 F 90 FUnits with Aquazone Complete C Control Approximate Fluid Volume gal Per 100 Ft of PipeAntifreeze Percentages by Volume OperationUnits with Wshp Open Multiple Protocol Auxiliary Modulating Hot Water/Steam Heating Reheat Page Complete C Control LED Code Fault Descriptions Complete C and Deluxe D Board System TestAquazone Deluxe D Control LED Indica Service Description Status LED Test LEDESD Refrigerant Charging Air Coil Fan Motor Removal’ to 4’ Troubleshooting Replacing the Wshp Open Controller’s BatA50-8163 Reduced or no airflow in heat TroubleshootingAir temperature out of range Cooling mode FP1125 F orReduced airflow in cooling Reduced or no water flowSensor Appendix a Wshp Open Screen ConfigurationAlarm Status StatusConfiguration Appendix a Wshp Open Screen ConfigurationMaintenance System SettingsSchedule Appendix a Wshp Screen Open Configuration ServiceTest Configuration Service Point Name Password Editable Range Default LevelScreen Name Alarm Page Copyright 2009 Carrier Corporation II. START-UP 50PCH,PCV START-UP ChecklistA50-8446 Heating Cycle AnalysisCooling Cycle Analysis A50-8445

PCV015-060 specifications

The Carrier PCV015-060 is a cutting-edge packaged cooling and heating unit designed for commercial applications that demand high efficiency, reliability, and adaptability. This model is particularly renowned for its robust performance, making it an ideal choice for businesses seeking optimal indoor climate control.

One of the standout features of the PCV015-060 is its impressive energy efficiency. Equipped with advanced scroll compressors, this unit operates with a higher energy efficiency ratio (EER), translating to lower operational costs and reduced environmental impact. The incorporation of eco-friendly refrigerants further bolsters its sustainability credentials, ensuring compliance with modern environmental regulations.

The PCV015-060 showcases superior airflow design, which minimizes noise levels while maximizing thermal comfort. Its high-efficiency evaporator and condenser coils facilitate enhanced heat transfer, ensuring effective cooling and heating performance even in extreme weather conditions. This model is also designed with multiple fan speed options, allowing users to customize air distribution according to specific requirements.

Built with user-friendly controls, the Carrier PCV015-060 supports advanced digital thermostat interfaces, enabling precise temperature management. Optional integration with building management systems allows for remote monitoring and control, enhancing operational efficiency and simplifying maintenance tasks.

Durability is another hallmark of the PCV015-060. The unit is constructed using high-quality materials designed to withstand varying environmental conditions, which enhances the lifespan of the system. Additionally, its modular design simplifies installation and service access, reducing downtime for businesses.

The versatility of the PCV015-060 is underscored by its capability to function effectively in numerous configurations, including rooftop installations and ground-mounted setups. It can efficiently handle diverse applications, from offices to retail spaces, making it an adaptable choice for many commercial needs.

In summary, the Carrier PCV015-060 offers a blend of energy efficiency, advanced technology, and durable construction, making it a formidable solution for businesses seeking reliable climate control. Its commitment to sustainability, user-friendly features, and versatile configurations solidify its standing as a premier choice for commercial heating and cooling needs. With the PCV015-060, businesses can ensure a comfortable environment for both employees and customers while maintaining operational efficiency.