APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont)

SCREEN NAME

POINT NAME

 

PASSWORD

EDITABLE

RANGE

DEFAULT

NOTES

 

LEVEL

 

 

 

 

 

 

 

 

 

 

Occupied Heating

 

 

X

40 - 90 ° F

72 ° F

Defines the Occupied

 

 

 

 

Heating Set Point

 

 

 

 

 

 

 

 

 

 

Occupied Cooling

 

 

X

55 - 99 ° F

76 ° F

Defines the Occupied

 

 

 

 

Cooling Set Point

 

 

 

 

 

 

 

 

 

 

Unoccupied Heating

 

 

X

40 - 90 ° F

55 ° F

Defines the Unoccupied

 

 

 

 

Heating Set Point

 

 

 

 

 

 

 

 

 

 

Unoccupied Cooling

 

 

X

55 - 99 ° F

90 ° F

Defines the Unoccupied

 

 

 

 

Cooling Set Point

 

 

 

 

 

 

 

 

 

 

Effective Heating

 

 

X

0 - 10 ° F

 

Takes into effect bias (maximum

 

 

Set Point

 

 

 

allowable set point deviation)

 

 

 

 

 

 

 

 

 

Effective Cooling

 

 

X

0 - 10 ° F

 

Takes into effect bias (maximum

 

 

Set Point

 

 

 

allowable set point deviation)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Uses historical data to calculate

 

 

Optimal Start

 

 

 

 

 

ramp up time so as to be at set point

Configuration

 

 

 

 

 

 

at occupied/unoccupied time

 

 

User/Admin

 

 

 

Defines the control set point used

 

 

 

 

 

 

 

 

Occupied RH

 

 

 

 

during occupied periods (Viewable

 

 

Password level

 

 

 

 

 

X

0 - 100%

65%

only if Humidity Sensor = Installed/

 

 

Set Point

 

access

 

 

 

Determines when to start

Set Points

 

 

 

 

 

 

 

 

 

 

 

 

Dehumidification when occupied)

 

 

 

 

 

 

 

 

Defines the control set point used

 

 

Unoccupied RH

 

 

 

 

 

during unoccupied periods

 

 

 

 

X

0 - 100%

90%

(Viewable only if Humidity Sensor =

 

 

Set Point

 

 

 

 

 

 

 

 

 

Installed/Determines when to start

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dehumidification when unoccupied)

 

 

 

 

 

 

 

 

Defines the control set point used to

 

 

DCV CTRL Start

 

 

X

0 - 9999 ppm

500 ppm

start increasing ventilation during

 

 

Set Point

 

 

occupied periods (Viewable only if

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ventilation DMP Type = DCV)

 

 

 

 

 

 

 

 

Defines the control set point

 

 

 

 

 

 

 

 

used to define where the ventilation

 

 

DCV Max CTRL

 

 

 

 

 

will reach its maximum limit during

 

 

 

 

X

0 - 9999 ppm

1050 ppm

occupied periods (Viewable only if

 

 

Set Point

 

 

 

 

 

 

 

 

 

Ventilation DMP Type = DCV/Used

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

to determine DCV ending control

 

 

 

 

 

 

 

 

point)

 

 

Start Time

 

 

X

00:00 - 23:59

06:00

Defines the start time for an

 

 

 

 

occupied period

 

 

 

 

 

 

 

 

 

 

End Time

 

 

X

00:00 - 24:00

18:00

Defines the ending time of an

 

 

 

 

occupied period

 

 

 

 

 

 

 

 

Configuration

Mon

 

 

X

No/Yes

Yes

Determines if this day is included

 

 

in this schedule

 

Tue

 

 

X

No/Yes

Yes

Determines if this day is included

 

 

User/Admin

in this schedule

Schedule

 

 

 

 

 

Determines if this day is included

Wed

 

Password level

X

No/Yes

Yes

 

in this schedule

 

 

 

 

access

 

 

 

 

Thur

 

X

No/Yes

Yes

Determines if this day is included

 

 

 

 

 

 

 

 

 

 

 

in this schedule

Weekly Schedule

Fri

 

 

X

No/Yes

Yes

Determines if this day is included

 

 

 

 

in this schedule

 

 

 

 

 

 

 

 

 

 

Sat

 

 

X

No/Yes

No

Determines if this day is included

 

 

 

 

in this schedule

 

 

 

 

 

 

 

 

 

 

Sun

 

 

X

No/Yes

No

Determines if this day is included

 

 

 

 

in this schedule

 

 

 

 

 

 

 

 

 

 

Start Month

 

 

X

0 - 12

0

Defines the start month of this

Configuration

 

 

hoilday schedule

 

 

 

 

 

 

Start Day

 

 

X

0 - 31

0

Defines the start day of this holiday

 

 

 

 

 

 

 

schedule

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Start Time

 

User/Admin

X

00:00 - 23:59

0:00

Determines the start time for this

Schedule

 

schedule

 

 

Password level

 

 

 

 

 

 

 

 

 

 

Defines the month to end this

 

End Month

 

access

X

0 - 12

0

 

 

hoilday schedule

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Exception

End Day

 

 

X

0 - 31

0

Defines the day to end this holiday

 

 

schedule

 

 

 

 

 

 

Schedules 1 - 12

 

 

 

 

 

 

 

End Time

 

 

X

00:00 - 24:00

0:00

Determines the time to end this

 

 

 

 

 

 

 

 

schedule

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

BAS — Building Automation System

 

 

 

 

 

DCV

Demand Controlled Ventilation

 

 

 

 

 

IAQ

Indoor Air Quality

 

 

 

 

 

OAT

Outdoor Air Temperature

 

 

 

 

 

RH

Relative Humidity

 

 

 

 

 

SAT — Supply Air Temperature

 

 

 

 

 

SPT

Space Temperature

 

 

 

 

 

TPI

Third Party Integration

 

 

 

 

 

45

Image 45
Contents Safety Considerations ContentsGeneral Installation50PCH,PCV Unit Physical Data 203 218209 224 Connections 50PCH 8412Opening Unit IPTTypical Installation 50PCH Units A50-8413 Typical Vertical Installation 50PCV Units Install Condensate Drain Mount the UnitA50-8489 A50-6261tf Metal Hose Minimum Bend RadiiSlope to drain Fitting Wire Field Power SupplyBMC LOCMves NECTXV RVSPower Block High-Pressure Water SwitchHpws Clippable Field Selection JumperMotorized Valve End Switch Temperature Switch Loss of Charge Pressure Switch Condensate PanA50-8493 LONA50-8440 National Electrical Code Temperature SwitchA50-8355 8354 A508356 LWT Wshp Open Control A50-8162 50PCH,PCV Unit Electrical DataMCA FLA HacrWire Field Controls A50-8441A50-8442 Rnet Wiring Rnet Wiring SpecificationsField-Supplied Sensors for Wshp Open Controller SPT SensorsBlower Speed Selection PRE-START-UP50PCV Blower Performance with Wet Coil 50PCV Blower Performance with Hot Water Reheat HWR Option50PCH,PCV Blower Performance Standard Unit 50PCH,PCV Blower Performance High-Static UnitComplete C Control Jumper Settings Refer to Deluxe D Control Jumper Settings Refer to , 15,Field Selectable Inputs DIP Switch Block S2 Accessory 2 Relay Options DIP Switch Block S2 Accessory 1 Relay OptionsSTART-UP Operating LimitsUnit Start-Up Cooling Mode Water Temperature Change Through Heat ExchangerOperating Limits 50PCH,PCV Units 50PC024 Typical Unit Operating Pressures and Temperatures 50PC030 Typical Unit Operating Pressures and Temperatures50PC036 Typical Unit Operating Pressures and Temperatures 50PC048 Typical Unit Operating Pressures and Temperatures 50PC042 Typical Unit Operating Pressures and Temperatures50PC060 Typical Unit Operating Pressures and Temperatures Temp GPM/ton Pressure HeatUnit Start-Up with Wshp Open Controls Unit Start-Up Heating Mode50PC Pressure DROP, psi kPa Coaxial Water Pressure DropGpm 30 F 50 F 70 F 90 F SizeAntifreeze Percentages by Volume Approximate Fluid Volume gal Per 100 Ft of PipeOperation Units with Aquazone Complete C ControlUnits with Wshp Open Multiple Protocol Auxiliary Modulating Hot Water/Steam Heating Reheat Page Complete C Control LED Code Fault Descriptions Complete C and Deluxe D Board System TestAquazone Deluxe D Control LED Indica Service Description Status LED Test LEDESD Refrigerant Charging Air Coil Fan Motor Removal’ to 4’ Troubleshooting Replacing the Wshp Open Controller’s BatA50-8163 Air temperature out of range TroubleshootingCooling mode FP1125 F or Reduced or no airflow in heatReduced airflow in cooling Reduced or no water flowAlarm Status Appendix a Wshp Open Screen ConfigurationStatus SensorMaintenance Appendix a Wshp Open Screen ConfigurationSystem Settings ConfigurationSchedule Appendix a Wshp Screen Open Configuration ServiceTest Configuration Service Point Name Password Editable Range Default LevelScreen Name Alarm Page Copyright 2009 Carrier Corporation II. START-UP 50PCH,PCV START-UP ChecklistCooling Cycle Analysis Heating Cycle AnalysisA50-8445 A50-8446

PCV015-060 specifications

The Carrier PCV015-060 is a cutting-edge packaged cooling and heating unit designed for commercial applications that demand high efficiency, reliability, and adaptability. This model is particularly renowned for its robust performance, making it an ideal choice for businesses seeking optimal indoor climate control.

One of the standout features of the PCV015-060 is its impressive energy efficiency. Equipped with advanced scroll compressors, this unit operates with a higher energy efficiency ratio (EER), translating to lower operational costs and reduced environmental impact. The incorporation of eco-friendly refrigerants further bolsters its sustainability credentials, ensuring compliance with modern environmental regulations.

The PCV015-060 showcases superior airflow design, which minimizes noise levels while maximizing thermal comfort. Its high-efficiency evaporator and condenser coils facilitate enhanced heat transfer, ensuring effective cooling and heating performance even in extreme weather conditions. This model is also designed with multiple fan speed options, allowing users to customize air distribution according to specific requirements.

Built with user-friendly controls, the Carrier PCV015-060 supports advanced digital thermostat interfaces, enabling precise temperature management. Optional integration with building management systems allows for remote monitoring and control, enhancing operational efficiency and simplifying maintenance tasks.

Durability is another hallmark of the PCV015-060. The unit is constructed using high-quality materials designed to withstand varying environmental conditions, which enhances the lifespan of the system. Additionally, its modular design simplifies installation and service access, reducing downtime for businesses.

The versatility of the PCV015-060 is underscored by its capability to function effectively in numerous configurations, including rooftop installations and ground-mounted setups. It can efficiently handle diverse applications, from offices to retail spaces, making it an adaptable choice for many commercial needs.

In summary, the Carrier PCV015-060 offers a blend of energy efficiency, advanced technology, and durable construction, making it a formidable solution for businesses seeking reliable climate control. Its commitment to sustainability, user-friendly features, and versatile configurations solidify its standing as a premier choice for commercial heating and cooling needs. With the PCV015-060, businesses can ensure a comfortable environment for both employees and customers while maintaining operational efficiency.