Carrier PCV015-060 specifications Units with Wshp Open Multiple Protocol

Page 34

Speed relays are turned off after a 60-second delay. The control reverts to Standby mode.

Output EH1, EH2, Fan Enable, and Fan Speed will be ON if the G input is not active during Emergency Heat mode.

COOLING STAGE 1 — In Cooling Stage 1 mode, the Fan Enable, compressor and RV relays are turned on immediately. If configured as stage 2 (DIP switch set to OFF) then the com- pressor and fan will not turn on until there is a stage 2 demand. The fan Enable and compressor relays are turned off immedi- ately when the Cooling Stage 1 demand is removed. The control reverts to Standby mode. The RV relay remains on until there is a heating demand. If there is a master/slave or dual compressor application, all compressor relays and related func- tions will track with their associated DIP switch 2 on S1.

COOLING STAGE 2 — In Cooling Stage 2 mode, the Fan Enable, compressor and RV relays remain on. The Fan Speed relay is turned on immediately and turned off immediately once the Cooling Stage 2 demand is removed. The control re- verts to Cooling Stage 1 mode. If there is a master/slave or dual compressor application, all compressor relays and related func- tions will track with their associated DIP switch 2 on S1.

NIGHT LOW LIMIT (NLL) STAGED HEATING — In NLL staged Heating mode, the override (OVR) input becomes active and is recognized as a call for heating and the control will immediately go into a Heating Stage 1 mode. With an additional 30 minutes of NLL demand, the control will go into Heating Stage 2 mode. With another additional 30 minutes of NLL demand, the control will go into Heating Stage 3 mode.

Units with WSHP Open Multiple Protocol —

The WSHP Open multi-protocol controller will control me- chanical cooling, heating and waterside economizer outputs based on its own space temperature input and set points. An optional CO2 IAQ (indoor air quality) sensor mounted in the space can maximize the occupant comfort. The WSHP Open controller has its own hardware clock that is automatically set when the heat pump software is downloaded to the board. Oc- cupancy types are described in the scheduling section below. The following sections describe the functionality of the WSHP Open multi-protocol controller. All point objects referred to in this sequence of operation will be referenced to the objects as viewed in the BACview6 handheld user interface.

SCHEDULING — Scheduling is used to start/stop the unit based on a time period to control the space temperature to spec- ified occupied heating and cooling set points. The controller is defaulted to control by occupied set points all the time, until ei- ther a time schedule is configured with BACview6, Field Assis- tant, i-Vu®Open, or a third party control system to enable/dis- able the BAS (Building Automation System) on/off point. The local time and date must be set for these functions to operate properly. The occupancy source can be changed to one of the following:

Occupancy Schedules — The controller will be occupied 24/7 until a time schedule has been configured using either Field Assistant, i-Vu Open, BACview6 or a third party control system to enable/disable the BAS on/off point. The BAS point can be disabled by going to Config, then Unit, then Occupancy Sched- ules and changing the point from enable to disable then click- ing OK.

NOTE: This point must be enabled in order for the i-Vu Open, Field Assistant, or BACview6 control system to assign a time schedule to the controller.

Schedule_schedule — The unit will operate according to the schedule configured and stored in the unit. The schedule is accessible via the BACview6 Handheld tool, i-Vu Open, or Field Assistant control system. The daily schedule consists of a start/stop time (standard or 24-hour mode) and seven days of the week, starting with Monday and ending on Sunday. To enter a daily schedule, navigate to Config, then Sched, then enter BACview6 Admin Password (1111), then go to

schedule_schedule. From here, enter either a Weekly or Excep- tion schedule for the unit.

Occupancy Input Contact — The WSHP Open controller has the capability to use an external dry contact closure to deter- mine the occupancy status of the unit. The Occupancy Sched- ules will need to be disabled in order to utilize the occupancy contact input.

NOTE: Scheduling can only be controlled from one source.

BAS (Building Automation System) On/Off — A BAS system that supports network scheduling can control the unit through a network communication and the BAS scheduling function once the Occupancy Schedules have been disabled.

NOTE: Scheduling can either be controlled via the unit or the BAS, but not both.

INDOOR FAN — The indoor fan will operate in any one of three modes depending on the user configuration selected.

Fan mode can be selected as Auto, Continuous, or Always On. In Auto mode, the fan is in intermittent operation during both occupied and unoccupied periods. Continuous fan mode is intermittent during unoccupied periods and continuous dur- ing occupied periods. Always On mode operates the fan con- tinuously during both occupied and unoccupied periods. In the default mode, Continuous, the fan will be turned on whenever any one of the following is true:

The unit is in occupied mode as determined by its occu- pancy status.

There is a demand for cooling or heating in the unoccu- pied mode.

There is a call for dehumidification (optional).

When power is reapplied after a power outage, there will be a configured time delay of 5 to 600 seconds before starting the fan. There are also configured fan delays for Fan On and Fan Off. The Fan On delay defines the delay time (0 to 30 seconds; default 10) before the fan begins to operate after heating or cooling is started while the Fan Off delay defines the delay time (0 to 180 seconds; default 45) the fan will continue to op- erate after heating or cooling is stopped. The fan will continue to run as long as the compressors, heating stages, or the dehu- midification relays are on. If the SPT failure alarm or conden- sate overflow alarm is active; the fan will be shut down imme- diately regardless of occupancy state or demand.

Fan Speed Control (During Heating) — Whenever heat is re- quired and active, the control continuously monitors the sup- ply-air temperature to verify it does not rise above the config- ured maximum heating SAT limit (110 F default). As the SAT approaches this value, the control will increase the fan speed as required to ensure the SAT will remain within the limit. This feature provides the most quiet and efficient operation by oper- ating the fan at the lowest speed possible.

Fan Speed Control (During Cooling) — Whenever mechani- cal cooling is required and active, the control continuously monitors the supply-air temperature to verify it does not fall be- low the configured minimum cooling SAT limit (50 F default). As the SAT approaches this value, the control will increase the fan speed as required to ensure the SAT will remain within the limit. The fan will operate at lowest speed to maximize latent capacity during cooling.

COOLING — The WSHP Open controller will operate one or two stages of compression to maintain the desired cooling set point. The compressor outputs are controlled by the PI (propor- tional-integral) cooling loop and cooling stages capacity algo- rithm. They will be used to calculate the desired number of stages needed to satisfy the space by comparing the space tem- perature (SPT) to the appropriate cooling set point. The water side economizer, if applicable, will be used for first stage cool- ing in addition to the compressor(s). The following conditions must be true in order for the cooling algorithm to run:

• Cooling is set to Enable.

34

Image 34
Contents Contents Safety ConsiderationsInstallation General203 218 50PCH,PCV Unit Physical Data209 224 Opening Unit 8412Connections 50PCH IPTTypical Installation 50PCH Units A50-8413 Typical Vertical Installation 50PCV Units Mount the Unit Install Condensate DrainA50-8489 Metal Hose Minimum Bend Radii A50-6261tfSlope to drain Wire Field Power Supply FittingMves LOCBMC NECRVS TXVHpws High-Pressure Water SwitchPower Block Clippable Field Selection JumperA50-8493 Loss of Charge Pressure Switch Condensate PanMotorized Valve End Switch Temperature Switch LONNational Electrical Code Temperature Switch A50-8440A50-8355 A50 83548356 LWT Wshp Open Control MCA 50PCH,PCV Unit Electrical DataA50-8162 FLA HacrA50-8441 Wire Field ControlsA50-8442 Field-Supplied Sensors for Wshp Open Controller Rnet Wiring SpecificationsRnet Wiring SPT SensorsPRE-START-UP Blower Speed Selection50PCH,PCV Blower Performance Standard Unit 50PCV Blower Performance with Hot Water Reheat HWR Option50PCV Blower Performance with Wet Coil 50PCH,PCV Blower Performance High-Static UnitDeluxe D Control Jumper Settings Refer to , 15, Complete C Control Jumper Settings Refer toField Selectable Inputs START-UP DIP Switch Block S2 Accessory 1 Relay OptionsDIP Switch Block S2 Accessory 2 Relay Options Operating LimitsWater Temperature Change Through Heat Exchanger Unit Start-Up Cooling ModeOperating Limits 50PCH,PCV Units 50PC030 Typical Unit Operating Pressures and Temperatures 50PC024 Typical Unit Operating Pressures and Temperatures50PC036 Typical Unit Operating Pressures and Temperatures 50PC060 Typical Unit Operating Pressures and Temperatures 50PC042 Typical Unit Operating Pressures and Temperatures50PC048 Typical Unit Operating Pressures and Temperatures Temp GPM/ton Pressure HeatUnit Start-Up Heating Mode Unit Start-Up with Wshp Open ControlsGpm 30 F 50 F 70 F 90 F Coaxial Water Pressure Drop50PC Pressure DROP, psi kPa SizeOperation Approximate Fluid Volume gal Per 100 Ft of PipeAntifreeze Percentages by Volume Units with Aquazone Complete C ControlUnits with Wshp Open Multiple Protocol Auxiliary Modulating Hot Water/Steam Heating Reheat Page Complete C and Deluxe D Board System Test Complete C Control LED Code Fault DescriptionsAquazone Deluxe D Control LED Indica Description Status LED Test LED ServiceESD Air Coil Fan Motor Removal Refrigerant Charging’ to 4’ Replacing the Wshp Open Controller’s Bat TroubleshootingA50-8163 Cooling mode FP1125 F or TroubleshootingAir temperature out of range Reduced or no airflow in heatReduced or no water flow Reduced airflow in coolingStatus Appendix a Wshp Open Screen ConfigurationAlarm Status SensorSystem Settings Appendix a Wshp Open Screen ConfigurationMaintenance ConfigurationSchedule Service Appendix a Wshp Screen Open ConfigurationTest Point Name Password Editable Range Default Level Configuration ServiceScreen Name Alarm Page Copyright 2009 Carrier Corporation 50PCH,PCV START-UP Checklist II. START-UPA50-8445 Heating Cycle AnalysisCooling Cycle Analysis A50-8446

PCV015-060 specifications

The Carrier PCV015-060 is a cutting-edge packaged cooling and heating unit designed for commercial applications that demand high efficiency, reliability, and adaptability. This model is particularly renowned for its robust performance, making it an ideal choice for businesses seeking optimal indoor climate control.

One of the standout features of the PCV015-060 is its impressive energy efficiency. Equipped with advanced scroll compressors, this unit operates with a higher energy efficiency ratio (EER), translating to lower operational costs and reduced environmental impact. The incorporation of eco-friendly refrigerants further bolsters its sustainability credentials, ensuring compliance with modern environmental regulations.

The PCV015-060 showcases superior airflow design, which minimizes noise levels while maximizing thermal comfort. Its high-efficiency evaporator and condenser coils facilitate enhanced heat transfer, ensuring effective cooling and heating performance even in extreme weather conditions. This model is also designed with multiple fan speed options, allowing users to customize air distribution according to specific requirements.

Built with user-friendly controls, the Carrier PCV015-060 supports advanced digital thermostat interfaces, enabling precise temperature management. Optional integration with building management systems allows for remote monitoring and control, enhancing operational efficiency and simplifying maintenance tasks.

Durability is another hallmark of the PCV015-060. The unit is constructed using high-quality materials designed to withstand varying environmental conditions, which enhances the lifespan of the system. Additionally, its modular design simplifies installation and service access, reducing downtime for businesses.

The versatility of the PCV015-060 is underscored by its capability to function effectively in numerous configurations, including rooftop installations and ground-mounted setups. It can efficiently handle diverse applications, from offices to retail spaces, making it an adaptable choice for many commercial needs.

In summary, the Carrier PCV015-060 offers a blend of energy efficiency, advanced technology, and durable construction, making it a formidable solution for businesses seeking reliable climate control. Its commitment to sustainability, user-friendly features, and versatile configurations solidify its standing as a premier choice for commercial heating and cooling needs. With the PCV015-060, businesses can ensure a comfortable environment for both employees and customers while maintaining operational efficiency.