Carrier T--298 service manual Line Voltage -- 10%

Page 33

3.5.8Capacitor Troubleshooting

WARNING

Disconnect power to the AirV unit before checking the capacitor.

To test capacitor to determine if good, open or shorted, an ohm meter can be used. To determine a capacitor’s capacitance, a capacitor meter is required.

Capacitors showing signs of leaks or bulging should be replaced immediately.

3.5.9Capacitor Testing and Replacement Capacitors must be discharged properly before testing.

a. Place a 20,000 ohm, 2 watt resistor across the termi- nals of the capacitor for approximately 30 seconds (See Figure 3-25 for a suggested tool).

WARNING

Do not touch the metal of the screwdriver when discharging the capacitor. You could receive a shock.

b. After the capacitor has been discharged and all wires removed from the capacitor terminals, use an ohm-- meter to test its resistance.

c. Set the scale to R x 1K or 10K ohm and place the ohmmeter leads across the capacitor terminals.

d.If the ohmmeter first reads 0, then rises toward infinity or some higher resistance, the capacitor is good.

e.If the ohmmeter goes to 0 or a low resistance and stays there, the capacitor is shorted and needs to be replaced.

f.If the ohmmeter reads infinity (OL) the capacitor is open and needs to be replaced.

INSULATED SCREWDRIVER

 

 

20,000 -- OHM

 

2 -- WATT RESISTOR

 

ATTACH TO CLEAN UNPAINTED

 

METAL PART OF UNIT FRAME

CLIP TO

TOUCH TO CAPACITOR TERMINALS

SCREWDRIVER

 

TO DISCHARGE CAPACITOR

Figure 3-25 Set--Up For Discharging a Capacitor

3.5.10Positive Temperature Coefficient Thermister (PTC) (Start Thermistor) Troubleshooting

a. Disconnect power from the AirV unit. b. Disconnect the wires to the PTC.

c. Using an ohm meter, check for continuity across the PTC.

If the PTC does not have continuity, it must be replaced. If continuity exists, reconnect the wires to the PTC. d. Reconnect power to the AirV unit.

e. Turn on the AirV unit to start.

f.Use a clamp--on amp probe to monitor the amp draw of the compressor during its start--up.

When the compressor starts, an amp draw will be indicated for almost a second.

If no amp draw is indicated or if the amp draw occurs for much longer than a second, the PTC is defective and must be replaced.

3.5.11 Line Voltage -- 10%

Line voltage should be checked during peak electrical load periods.

With the AirV unit on and the compressor operating, use a voltmeter to check the voltage being supplied to the AirV unit. The voltage must be within 10% of the units required voltage. A voltage drop greater than 10% will cause a premature compressor failure and needs to be corrected immediately.

3-9

T--298

Image 33
Contents Model AirV AirV General Safety Notices Safety SummaryOperating Precautions Maintenance PrecautionsSpecific Warnings and Cautions Specific Warning and Caution StatementsSafety 298 Table of Contents Table of Contents Figure Number List of FiguresTable Number List of TablesIntroduction Section DescriptionSerial Number Identification Design Change DescriptionsCeiling Unit Upper Unit RoofAdditional Support Manuals MANUAL--FORM no Equipment Covered Type of ManualFor Part no Ceiling Unit Component Identification Free--Blow Component Identification -- Low Profile -- Upper Unit Component Listing--Ceiling Unit For Ducted Systems Return AIR Supply AIRFree Blow Type Cations START--UPRefrigerant CYCLE--STANDARD System Refrigerant Cycle -- Heat Pump Refrigerant Flow Schematic -- Heat Pump -- Cool Mode CoolingPage Section Troubleshooting Insufficient COOLING, Cooling AIR not Adequate Heater Cycles on Limit Switch HEAT/ Cool Version onlyCondenser AIR not Adequate Insufficient CoolingInadequate Heat HEAT--PUMP Clearing Diagnostic AlarmsPriority Malfunction Section Service and Maintenance Preventative MaintenanceService -- General Ceiling Grill -- Free Blow 3.3.3 Ceiling Panel Removal Indoor Thermostat 3.3.7 Air Sweep Removal Indoor Thermostat RemovalControl Box Assembly Removal Ceiling Unit -- Ducted SystemsFilter Removal Service -- Upper Unit -- STANDARD, HC & HP PCB Display RemovalFuse Removal 15 Control Box Compressor Replacement19 Motor Assembly Upper Scroll Assembly Removal23 Blower Wheel Air Handling System RemovalLine Voltage -- 10% 27 Upper Scroll Assembly Locking Tabs b. & Screw Locations c 30 Condenser Fan Assembly Retaining Ring 34 Evaporator Motor Locking Tabs Condenser Motor RemovalChange from Fahrenheit to Celsius will Capacitor RemovalBe permanent. It cannot be changed back to Fahrenheit38 Remote Control Components LCD Display SET Thermostat ConfigurationCheck Thermostat Operation Powerbox Assembly Upper UnitThermostat Ac to ry Wiri ng Fie ld Wiri ng Thermostat Powerbox AssemblyUpper Unit Schematic -- Standard & HC Section Wiring SchematicsCeiling Unit Schematic -- Cooling Only Heat Pump -- Ceiling Unit -- Free Blow Heat Pump -- Upper Unit -- Ducted Wall Mounted Thermostats 10 Ceiling Unit -- Wall Thermostat -- Ducted & Free BlowCeiling Unit -- Ducted Systems Ceiling Unit -- Free Blow Index