Carrier T--298 service manual Section Troubleshooting

Page 21

SECTION 2

TROUBLESHOOTING

For ducted units, the green operation indicator LED (SeeFigure 3-9) will flash if there is a problem. Refer to Table 2--1 for diagnostic information.

 

SYMPTOM AND PROBABLE CAUSE

 

PROBABLE REMEDY

2.1 NO POWER TO UNIT

 

 

 

 

 

 

1.

Master switch off

1.

Reset master switch

2.

Open circuit breaker

2.

Reset circuit breaker

3.

Defective wiring

3.

Replace wiring

4.

Loose electrical connections

4.

Tighten connections

5.

Faulty switches, thermostat, or fan

5.

Replace defective components

6.

12 VDC not connected (Ducted System)

6.

Connect to 12 VDC power source

7.

12 VDC in--line fuse open (Ducted)

7.

Replace fuse

 

 

 

2.2 DUCTED UNIT WILL NOT OPERATE

 

 

 

 

 

 

1.

Display not illuminated

1.

Check 12 Volt DC in--line fuse

2.

Display illuminated

2.

Check 115 Volt AC Connections

 

 

 

2.3 DUCTED UNIT WILL NOT COOL

 

 

 

 

 

 

1.

Green LED light flashes 5 times

1.

Check 115 volt AC power source

 

 

 

Momentarily disconnect 12 VDC power source

 

 

 

Disable compressor malfunction test switch.

 

 

 

Check AMP draw.

 

 

 

Check T

2.

Unit cools for a few moments then stops cooling

2.

Remove grill, verify evaporator coil probe is

 

 

 

inserted into coil.

 

 

 

Check AMP draw.

 

 

 

Check T

 

 

 

Replace unit

 

 

 

2.4 COMPRESSOR POWER SUPPLY OPEN

 

 

 

 

 

 

1.

Loose leads at compressor terminals

1.

Tighten leads

2.

Defective motor overload switch

2.

Replace switch

3.

Defective capacitor

3.

Replace capacitor -- Refer to Paragraph 3.5.8

4.

Open compressor windings

4.

Replace compressor

5.

Seized compressor

5.

Replace compressor

6.

Capacitor incorrectly wired

6.

Verify capacitor wiring (Refer to wiring diagram)

 

 

2.5 COMPRESSOR RUNS BUT CYCLES, FAN OPERATING ERRATICALLY

 

 

 

1.

Loose lead at fan motor

1. Tighten lead.

2.

Defective or burned out motor

2.

Replace motor.

3.

Outdoor air restricted or recirculating

3.

Check for dirty condenser coil, proper clearance

 

 

 

around unit, remove any obstructions.

4.

Overcharge or noncondensables in system

4.

Check AMP draw

5.

Restricted discharge line

5.

Check for obstruction in line.

 

 

 

Check T.

 

 

 

Replace unit.

6.

Defective motor overload switch

6.

Replace switch.

2-1

T--298

Image 21
Contents Model AirV AirV General Safety Notices Safety SummaryOperating Precautions Maintenance PrecautionsSpecific Warnings and Cautions Specific Warning and Caution StatementsSafety 298 Table of Contents Table of Contents Figure Number List of FiguresTable Number List of TablesIntroduction Section DescriptionSerial Number Identification Design Change DescriptionsCeiling Unit Upper Unit RoofAdditional Support Manuals MANUAL--FORM no Equipment Covered Type of ManualFor Part no Ceiling Unit Component Identification Free--Blow Component Identification -- Low Profile -- Upper Unit Component Listing--Ceiling Unit For Ducted Systems Return AIR Supply AIRFree Blow Type Cations START--UPRefrigerant CYCLE--STANDARD System Refrigerant Cycle -- Heat Pump Refrigerant Flow Schematic -- Heat Pump -- Cool Mode CoolingPage Section Troubleshooting Insufficient COOLING, Cooling AIR not Adequate Heater Cycles on Limit Switch HEAT/ Cool Version onlyCondenser AIR not Adequate Insufficient CoolingInadequate Heat HEAT--PUMP Clearing Diagnostic AlarmsPriority Malfunction Section Service and Maintenance Preventative MaintenanceService -- General Ceiling Grill -- Free Blow 3.3.3 Ceiling Panel Removal Indoor Thermostat 3.3.7 Air Sweep Removal Indoor Thermostat RemovalControl Box Assembly Removal Ceiling Unit -- Ducted SystemsFilter Removal Service -- Upper Unit -- STANDARD, HC & HP PCB Display RemovalFuse Removal 15 Control Box Compressor Replacement19 Motor Assembly Upper Scroll Assembly Removal23 Blower Wheel Air Handling System RemovalLine Voltage -- 10% 27 Upper Scroll Assembly Locking Tabs b. & Screw Locations c 30 Condenser Fan Assembly Retaining Ring 34 Evaporator Motor Locking Tabs Condenser Motor RemovalChange from Fahrenheit to Celsius will Capacitor RemovalBe permanent. It cannot be changed back to Fahrenheit38 Remote Control Components LCD Display SET Thermostat ConfigurationCheck Thermostat Operation Powerbox Assembly Upper UnitThermostat Ac to ry Wiri ng Fie ld Wiri ng Thermostat Powerbox AssemblyUpper Unit Schematic -- Standard & HC Section Wiring SchematicsCeiling Unit Schematic -- Cooling Only Heat Pump -- Ceiling Unit -- Free Blow Heat Pump -- Upper Unit -- Ducted Wall Mounted Thermostats 10 Ceiling Unit -- Wall Thermostat -- Ducted & Free BlowCeiling Unit -- Ducted Systems Ceiling Unit -- Free Blow Index