Carrier 52C manual SHORTED/OPEN Windings Test

Page 16

52C,P

SERIES

FIGURE 30 — SHORTED/OPEN WINDINGS TEST

FIGURE 31 — GROUNDED WINDINGS TEST

For compressors that are known to be dam- aged: Remove refrigerant prior to disconnecting compressor wires. Damaged hermetic compressor terminals may become loose and eject from the com- pressor. Wear safety glasses and keep your face away from the area above the terminals when removing compressor wires.

TOOLS NEEDED — The following list includes the recommended tools and devices for removing and replacing the compressor.

1/2-in. and 3/8-in. Tube Benders

1/2-in. Nut Driver

5/16-in. Nut Driver

Flat Head Screwdriver

Piercing Valve

2Parker Access Valves (Part No. AVUSE-5) Pinch Off Tool

Filter Drier — All Units (Part No. P504-80845) Carrier TOTALTEST Kit (Part No. TT1-001) Totalclaim System

Charging Cylinder or an Electronic Scale Refrigerant-22

Tubing Cutter Torch

Nitrogen Cylinder with Regulator Strainers

Capillary Tubes

REMOVING THE COMPRESSOR — Follow the steps below to remove the compressor:

1.Disconnect all power to unit.

2.Remove unit from wall sleeve as detailed in the UNIT DISASSEMBLY section. The unit weighs up to 150 pounds. Seek assistance or use a lifting device when removing unit from wall sleeve.

3.If the unit is a heat pump: Disconnect the wire plug on the reversing valve solenoid and carefully remove the outdoor thermostat capillary from the outdoor coil. See Figure 32.

4.Attach the piercing valve to the suction side pro- cess tube below the crimps. Attach Carrier TOTALTEST® kit (Part No. TT1-001), to the piercing valve to verify acidity of the system. After verifying the system acidity, remove the refriger- ant using a certified refrigerant recovery system.

5.When all the refrigerant has been recovered, remove the terminal cover from the compressor with a nut driver. Disconnect the 3 wires from the compressor and label the location of each. Once the wires are labeled, replace the terminal cover to protect the compressor terminals.

6.Remove the air system components by following the procedure detailed in the ACCESSING UNIT COMPONENTS section.

7.Remove the piercing valve and cut the crimped portion of both process tubes off with a small tub- ing cutter. Braze an access valve on each process tube. Using a torch, disconnect the suction and discharge tubes from the compressor connections.

8.Remove the compressor mounting bolts, and remove the compressor.

The compressor may still be hot from the brazing process.

IMPORTANT: Any time the compressor is replaced, the strainer and capillary tubes must be removed and replaced also.

9.For all units: Remove and replace the strainer and capillary tubes from the system. See Figure 32 for strainer and capillary tube location.

10.For Heat/Cool Units: Use an in-line filter drier (P/N P504-80845). The filter drier can be installed in any location in suction line. See Figure 33A for general installation location.

For Heat Pump Units: Use an in-line filter drier (P/N P504-80845) and install between the reversing valve and the compressor accumu- lator. There are several suction tube configura- tions and the in-line filter drier will be field piped and brazed into the suction tube for your unit. See Figure 33B for a general installation location.

11.Remove the grommets from the existing compres- sor and install them onto the new compressor.

16

Image 16
Contents Service Technician Guide ContentsIntroduction Summary of DANGERS, WARNINGS, and CautionsUnit Disassembly Disconnect Power for CORD-CONNECTED UnitDisconnect Power for Permanently Connected Hardwired Units Tools NeededOpen the Control BOX Remove the Unit from the Wall SleeveAccessing Unit Components Accessing INDOOR-AIR Section ComponentsAccessing OUTDOOR-AIR Section Components Remove the Discharge Deck AssemblyPtac Unit with Lateral Duct Accessory Installed Remove the AIR Discharge GrilleGusset Removal Reinstall Front Panel Location of Screws on Discharge GrilleCleaning and Safety General CleaningComponent Cleaning Schedule Monthly Cleaning Cleaning the Outdoor AIR Vent FilterCleaning the Indoor and Outdoor Coils Seasonal CleaningAccess and Clean Indoor FAN and FAN Scroll Ptac Exterior Surfaces Compressor Rotary Compressor ComponentsDisconnect ALL Power to the Unit Compressor TroubleshootingBasic Hermetic Compressor Electrical Measurements Compressor Replacement Basic Compressor Troubleshooting GuideSHORTED/OPEN Windings Test Strainer Capillary Tube Location Common Causes Heater Failure HeatersHeater Removal Disconnect ALL Power to Unit Acceptable Heater Resistance ValuesOperating Controls UNIT-MOUNTED ControlsRemote Thermostat Troubleshooting WALL-MOUNTED Thermostat ControlsDo not daisy chain R 24 VAC Description of Selector Switch Settings Figure NON-USER Adjustable ControlsSequence of Operation Component Operation and TroubleshootingTools Needed Indoor Thermostat IT CONTACTS, ALL 52CE, PE Models Indoor Thermostat IT CONTACTS, ALL 52CQ, PQ Models Electrical Components Removal and Replacement Capacitor TestComponent Locations Open Control BOX FAN Motor FAN Motor TroubleshootingBasic FAN Motor Electrical Tests FAN Motor Troubleshooting Chart Typical 208/230 Volt Motors Typical 265 Volt MotorsFAN Motor Replacement Location of Wiring Schematic On Front Panel of Control BOXField Temperature Charts 100 110 120 130 52P 12,000 BTU Unit Field Temperature Chart High Cool 50% RH Indoor Series Indoor 52C,P Series Page 000 Btu 52P-12,000 Btu 52C-12,000 Btu 15,000 Btu Wiring Diagrams Refer to Figures 68-72 for Typical Wiring SchematicsComponent Legend CAP Component Connection Marked Fan Motor Page Most Frequent Ptac Service Questions Accessories Accessory Form Number Part Number Description52C Performance and Physical Data Amps52P Performance and Physical Data 52PE-512---3Page Page Copyright 2002 Carrier Corporation