Carrier P, 52C manual Operating Controls, UNIT-MOUNTED Controls

Page 20

52C,P

SERIES

OPERATING CONTROLS

UNIT-MOUNTED CONTROLS

The controls and components used in the 52C,P cool- ing only or heat/cool units are as follows: the selec- tor switch, the indoor thermostat, the dual capacitor, the temperature limiter, the vent lever, and the fan cycle switch. See Figure 37.

The selector switch is used to determine the mode of operation: heat, cool, fan, or off. The indoor thermostat controls the room ambient temperature and cycles the heater or the compressor based on the selector switch setting. The dual capacitor aids in the start-up of the compressor and the fan motor. The temperature limiter is integrated into the control box top cover located under front panel. It is a mechanical device that restricts the amount of rotation of the thermostat. The temperature limiter device may be adjusted by moving the plastic temperature selector tabs to another temper- ature location on the control box. The vent lever is located on the front left side of the chassis. It is a slide mechanism that opens and closes the vent door. The vent control may be accessed by removing the front panel of the unit. The fan cycle switch is used to provide 2 options of fan control. The first option, CON, causes the fan to run continuously. The second option, CYC, causes the fan to cycle on with the compressor or elec- tric heater and off when the thermostat is satisfied.

INDOOR

 

SELECT0R

 

SWITCH

THERMOSTAT

 

 

75

 

80

70

 

 

8565

90 60

TEMPERATURE

 

LIMITER

 

 

CON

FAN CYCLE

CYC

 

SWITCH

 

The 52C,P heat pump unit contains all the compo- nents of the heat/cool and cooling only unit, and the following additional ones: the outdoor frost thermostat and the reversing valve. The outdoor frost thermostat prevents operation of the unit in the heat pump mode when the outdoor coil temperature drops below 20 F, or at about 35 F outdoor ambient temperature. The unit automatically engages the electric heat strip and disables the compressor under these conditions.

The outdoor frost thermostat has a manual override to place the unit in electric heat mode operation only. The override switch is located behind the front panel on the front side of the unit control box door.

IMPORTANT: Placing the override switch to elec- tric heat mode operation will disable the compres- sor for ALL heating or cooling operations (for all units except RC units). Placing the override switch to electric heat mode operation on RC units will only disable the compressor in heating mode.

The reversing valve allows for operation in reverse cycle heat pump mode. The valve is located in the piping sys- tem and is controlled by the reversing valve solenoid coil. The coil is energized only during the heating mode.

OUTDOOR FROST THERMOSTAT (HEAT PUMP UNITS ONLY)

FIGURE 37 — 52C,P OPERATING CONTROLS

20

Image 20
Contents Service Technician Guide ContentsIntroduction Summary of DANGERS, WARNINGS, and CautionsUnit Disassembly Disconnect Power for CORD-CONNECTED UnitDisconnect Power for Permanently Connected Hardwired Units Tools NeededOpen the Control BOX Remove the Unit from the Wall SleeveAccessing Unit Components Accessing INDOOR-AIR Section ComponentsAccessing OUTDOOR-AIR Section Components Remove the Discharge Deck AssemblyPtac Unit with Lateral Duct Accessory Installed Remove the AIR Discharge GrilleGusset Removal Reinstall Front Panel Location of Screws on Discharge GrilleComponent Cleaning Schedule General CleaningCleaning and Safety Monthly Cleaning Cleaning the Outdoor AIR Vent FilterAccess and Clean Indoor FAN and FAN Scroll Seasonal CleaningCleaning the Indoor and Outdoor Coils Ptac Exterior Surfaces Compressor Rotary Compressor ComponentsBasic Hermetic Compressor Electrical Measurements Compressor TroubleshootingDisconnect ALL Power to the Unit Compressor Replacement Basic Compressor Troubleshooting GuideSHORTED/OPEN Windings Test Strainer Capillary Tube Location Heater Removal HeatersCommon Causes Heater Failure Disconnect ALL Power to Unit Acceptable Heater Resistance ValuesOperating Controls UNIT-MOUNTED ControlsRemote Thermostat Troubleshooting WALL-MOUNTED Thermostat ControlsDo not daisy chain R 24 VAC Description of Selector Switch Settings Figure NON-USER Adjustable ControlsTools Needed Component Operation and TroubleshootingSequence of Operation Indoor Thermostat IT CONTACTS, ALL 52CE, PE Models Indoor Thermostat IT CONTACTS, ALL 52CQ, PQ Models Electrical Components Removal and Replacement Capacitor TestComponent Locations Open Control BOX Basic FAN Motor Electrical Tests FAN Motor TroubleshootingFAN Motor FAN Motor Troubleshooting Chart Typical 208/230 Volt Motors Typical 265 Volt MotorsFAN Motor Replacement Location of Wiring Schematic On Front Panel of Control BOXField Temperature Charts 100 110 120 130 52P 12,000 BTU Unit Field Temperature Chart High Cool 50% RH Indoor Series Indoor 52C,P Series Page 000 Btu 52P-12,000 Btu 52C-12,000 Btu 15,000 Btu Wiring Diagrams Refer to Figures 68-72 for Typical Wiring SchematicsComponent Legend CAP Component Connection Marked Fan Motor Page Most Frequent Ptac Service Questions Accessories Accessory Form Number Part Number Description52C Performance and Physical Data Amps52P Performance and Physical Data 52PE-512---3Page Page Copyright 2002 Carrier Corporation