Carrier manual Indoor Thermostat IT CONTACTS, ALL 52CE, PE Models

Page 25

The Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Consider the following safety issues:

Prior to performing any service or maintenance on electrical equipment you must Disconnect All

Power.

New and unfamiliar tasks should be performed under the supervision of an experienced service technician.

Personal protective equipment, such as safety glasses and work gloves, should be worn.

The floor around the work area should be clean and free of debris.

Make sure tools are the correct tools for job, and that they are working properly and in good condition.

The 52C,P unit may weigh up to 150 pounds. Use a lifting device or ask for assistance if the unit must be moved.

INDOOR THERMOSTAT (Heat/Cool and Cool Only Units) (Figure 48) — The thermostat maintains the selected temperature by cycling the compressor on and off during cooling operation and the electric heater during heating operation. The thermostat DOES

NOT switch from heating to cooling, or cooling to heating. If the switch is in the CYCLE position, then the fan will be cycled off when the thermostat satisfies.

To verify the operation of the thermostat switch, a con- tinuity test may be performed as follows:

1.Turn off unit power as described in UNIT DISASSEMBLY section.

2.Remove wire leads from thermostat. Note their locations to ease re-assembly.

FIGURE 48 — INDOOR THERMOSTAT (IT)

CONTACTS, ALL 52CE, PE MODELS

LEGEND (Figures 48-50)

COMP — Compressor

HTR

Heater

IT

Indoor Thermostat

OFT

Outdoor Frost Thermostat

OL

Overload

PLS

Primary Limit Switch

SLS

Secondary Limit Switch

3.Place one of the leads of the continuity tester on the terminal marked 2, and the other lead on either the terminal marked 1 or the terminal marked 3.

4.Adjust the thermostat up or down to verify the contacts of the switch open and close. When veri- fying continuity of a closed switch, the ohm read- ing should be 0 ohms. An open switch will show OL on the meter.

5.When testing is complete, reconnect the leads.

INDOOR THERMOSTAT (Heat Pump Units) (Figure 49) — The heat pump indoor thermostat uses a two-stage switch for the heating mode. The first stage engages the compressor and reversing valve, and the unit operates in normal heat pump mode. The indoor thermostat maintains the selected temperature by cycling the compressor on and off in cooling mode. In the heating mode, the indoor thermostat will cycle the compressor or the heater, depending on the difference between the actual room temperature and the thermo- stat temperature setting.

When the room temperature is more than 4 F cooler than the indoor thermostat setting, the second heating stage of the indoor thermostat engages the electric heat strip. This design feature allows the user to rap- idly warm the room with the electric heat strip by turning the thermostat to its highest setting. When room temperatures approach the desired temperature, the user may adjust the thermostat to a personal comfort setting, which allows for normal heat pump operation.

NOTE: For outdoor coil temperatures below approxi- mately 20 F, the outdoor frost thermostat prevents heat pump mode operation and immediately engages the electric heat strip upon a call for heating. The elec- tric heat strip is NEVER energized at the same time as the compressor.

To verify operation of the heat pump indoor thermo- stat switch, a continuity test may be performed as follows:

1.Turn off unit power as described in UNIT DISASSEMBLY section.

2.Remove wire leads from thermostat. Note their locations to ease re-assembly.

3.To test stage A, place one lead of the continuity tester on the terminal marked 2, and the other lead on either the terminal marked 1 or the termi- nal marked 3.

4.Adjust the thermostat up or down to verify the contacts of the switch open and close. When veri- fying continuity of the closed switch, the reading on the meter should be 0 ohms. An open switch will show OL on the meter.

5.To test stage B contacts, place one lead of the con- tinuity tester on contact 5 and the other lead on either contact 4 or contact 6.

6.Adjust the thermostat up or down to verify the contacts of the switch open and close as in Step 4.

7.When testing is complete, reconnect the leads.

25

Image 25
Contents Contents Service Technician GuideSummary of DANGERS, WARNINGS, and Cautions IntroductionDisconnect Power for CORD-CONNECTED Unit Unit DisassemblyDisconnect Power for Permanently Connected Hardwired Units Tools NeededRemove the Unit from the Wall Sleeve Open the Control BOXAccessing INDOOR-AIR Section Components Accessing Unit ComponentsAccessing OUTDOOR-AIR Section Components Remove the Discharge Deck AssemblyRemove the AIR Discharge Grille Ptac Unit with Lateral Duct Accessory InstalledGusset Removal Location of Screws on Discharge Grille Reinstall Front PanelCleaning and Safety General CleaningComponent Cleaning Schedule Cleaning the Outdoor AIR Vent Filter Monthly CleaningCleaning the Indoor and Outdoor Coils Seasonal CleaningAccess and Clean Indoor FAN and FAN Scroll Ptac Exterior Surfaces Rotary Compressor Components CompressorDisconnect ALL Power to the Unit Compressor TroubleshootingBasic Hermetic Compressor Electrical Measurements Basic Compressor Troubleshooting Guide Compressor ReplacementSHORTED/OPEN Windings Test Strainer Capillary Tube Location Common Causes Heater Failure HeatersHeater Removal Acceptable Heater Resistance Values Disconnect ALL Power to UnitUNIT-MOUNTED Controls Operating ControlsWALL-MOUNTED Thermostat Controls Remote Thermostat TroubleshootingDo not daisy chain R 24 VAC NON-USER Adjustable Controls Description of Selector Switch Settings FigureSequence of Operation Component Operation and TroubleshootingTools Needed Indoor Thermostat IT CONTACTS, ALL 52CE, PE Models Indoor Thermostat IT CONTACTS, ALL 52CQ, PQ Models Capacitor Test Electrical Components Removal and ReplacementComponent Locations Open Control BOX FAN Motor FAN Motor TroubleshootingBasic FAN Motor Electrical Tests Typical 265 Volt Motors FAN Motor Troubleshooting Chart Typical 208/230 Volt MotorsLocation of Wiring Schematic On Front Panel of Control BOX FAN Motor ReplacementField Temperature Charts 100 110 120 130 52P 12,000 BTU Unit Field Temperature Chart High Cool 50% RH Indoor Series Indoor 52C,P Series Page 000 Btu 52P-12,000 Btu 52C-12,000 Btu 15,000 Btu Refer to Figures 68-72 for Typical Wiring Schematics Wiring DiagramsComponent Legend CAP Component Connection Marked Fan Motor Page Most Frequent Ptac Service Questions Accessory Form Number Part Number Description AccessoriesAmps 52C Performance and Physical Data52PE-512---3 52P Performance and Physical DataPage Page Copyright 2002 Carrier Corporation