Carrier P FAN Motor Troubleshooting Chart Typical 208/230 Volt Motors, Typical 265 Volt Motors

Page 30

52C,P

SERIES

 

 

 

SYMPTOM

 

 

POSSIBLE CAUSE

Motor Hums

Makes No Noise

Starts But

Starts

Runs On

But Does

and Does Not

Stops After

But Runs

One Speed,

 

 

Not Start

Start

Short Time

Slow

Not On Others

DEFECTIVE BEARING

X

 

X

X

 

CAPACITOR DEFECTIVE

X

 

X

 

 

SWITCH DEFECTIVE

 

X

 

 

X

LOW LINE VOLTAGE

X

 

X

X

 

SHORTED MOTOR WINDING

X

X

 

 

X

NO POWER TO UNIT

 

X

 

 

 

INTERNAL THERMOSTAT OPEN

 

X

 

 

 

MISWIRED

X

X

X

 

X

FAN STUCK

X

 

 

 

 

BROKEN MOTOR WIRE

X

X

X

 

X

MOTOR WINDING GROUNDED

X

X

 

 

 

OPEN MOTOR WINDING

X

X

X

 

X

FIGURE 56 — FAN MOTOR TROUBLESHOOTING CHART

TYPICAL 208/230 VOLT MOTORS

UNIT 52C,P (BTUH)

7,000/9,000

12,000/15,000

CARRIER MOTOR PART NUMBER

HC37GE237

HC37GE238

MANUFACTURER’S

5KCP29ECA299A

5KCP29ECA301

PART NUMBER

 

 

MOTOR VOLTAGE

208/230

208/230

MOTOR HORSEPOWER

.075

.125

MOTOR SPEEDS

2

2

RESISTANCE (OHMS)

101.4

90

BLACK TO WHITE WIRE

 

 

RESISTANCE (OHMS)

45.8

71

BLACK TO BROWN WIRE

 

 

RESISTANCE (OHMS)

38.8

32.9

BLACK TO RED WIRE

 

 

NOTE: Resistance values are approximate.

 

 

TYPICAL 265 VOLT MOTORS

UNIT 52C,P (BTUH)

7,000/9,000

12,000/15,000

CARRIER MOTOR PART NUMBER

HC29GE236

HC33GE239

MANUFACTURER’S

5KCP29FCA315

5KCP29FCA316

PART NUMBER

 

 

MOTOR VOLTAGE

265

265

MOTOR HORSEPOWER

.075

.125

MOTOR SPEEDS

2

2

RESISTANCE (OHMS)

144.0

83.7

BLACK TO WHITE WIRE

 

 

RESISTANCE (OHMS)

29.3

39.1

BLACK TO BROWN WIRE

 

 

RESISTANCE (OHMS)

82.1

45.2

BLACK TO RED WIRE

 

 

NOTE: Resistance values are approximate.

 

 

FIGURE 57 — TYPICAL 52C,P FAN MOTORS

30

Image 30
Contents Service Technician Guide ContentsIntroduction Summary of DANGERS, WARNINGS, and CautionsDisconnect Power for Permanently Connected Hardwired Units Unit DisassemblyDisconnect Power for CORD-CONNECTED Unit Tools NeededOpen the Control BOX Remove the Unit from the Wall SleeveAccessing OUTDOOR-AIR Section Components Accessing Unit ComponentsAccessing INDOOR-AIR Section Components Remove the Discharge Deck AssemblyPtac Unit with Lateral Duct Accessory Installed Remove the AIR Discharge GrilleGusset Removal Reinstall Front Panel Location of Screws on Discharge GrilleGeneral Cleaning Cleaning and SafetyComponent Cleaning Schedule Monthly Cleaning Cleaning the Outdoor AIR Vent FilterSeasonal Cleaning Cleaning the Indoor and Outdoor CoilsAccess and Clean Indoor FAN and FAN Scroll Ptac Exterior Surfaces Compressor Rotary Compressor ComponentsCompressor Troubleshooting Disconnect ALL Power to the UnitBasic Hermetic Compressor Electrical Measurements Compressor Replacement Basic Compressor Troubleshooting GuideSHORTED/OPEN Windings Test Strainer Capillary Tube Location Heaters Common Causes Heater FailureHeater Removal Disconnect ALL Power to Unit Acceptable Heater Resistance ValuesOperating Controls UNIT-MOUNTED ControlsRemote Thermostat Troubleshooting WALL-MOUNTED Thermostat ControlsDo not daisy chain R 24 VAC Description of Selector Switch Settings Figure NON-USER Adjustable ControlsComponent Operation and Troubleshooting Sequence of OperationTools Needed Indoor Thermostat IT CONTACTS, ALL 52CE, PE Models Indoor Thermostat IT CONTACTS, ALL 52CQ, PQ Models Electrical Components Removal and Replacement Capacitor TestComponent Locations Open Control BOX FAN Motor Troubleshooting FAN MotorBasic FAN Motor Electrical Tests FAN Motor Troubleshooting Chart Typical 208/230 Volt Motors Typical 265 Volt MotorsFAN Motor Replacement Location of Wiring Schematic On Front Panel of Control BOXField Temperature Charts 100 110 120 130 52P 12,000 BTU Unit Field Temperature Chart High Cool 50% RH Indoor Series Indoor 52C,P Series Page 000 Btu 52P-12,000 Btu 52C-12,000 Btu 15,000 Btu Wiring Diagrams Refer to Figures 68-72 for Typical Wiring SchematicsComponent Legend CAP Component Connection Marked Fan Motor Page Most Frequent Ptac Service Questions Accessories Accessory Form Number Part Number Description52C Performance and Physical Data Amps52P Performance and Physical Data 52PE-512---3Page Page Copyright 2002 Carrier Corporation