Carrier 39L specifications Test of Output Options Using Option Module, Electric Heater Test

Page 107

 

 

Table 20 Ð Test of Output Options Using Option Module

 

 

 

 

KEYBOARD

DISPLAY

COMMENTS/ACTION

ENTRY

RESPONSE

 

 

 

RFVC X

 

 

 

RFVCTEST

Verify that the return fan IGVs stroke to their fully open position.

 

HUM1 %

The return fan IGVs should close.

 

HUM1TEST

Verify that the return fan IGVs, if so equipped, return to their fully closed position. If equipped with single- stage

 

 

analog humidi®cation control, verify that the modulating valve goes to its fully open position. If equipped with

 

 

two stages of humidi®cation, use an ohmmeter to verify that the reading across the 1st stage normally-open

 

 

relay contacts is less than 10 ohms.

 

HUM2 %

Verify that the reading across the 1st stage normally-open relay contacts is greater than 1000 ohms.

 

HUM2TEST

If equipped with two stages of humidi®cation, use an ohmmeter to verify that the reading across the 2nd stage

 

normally open relay contacts is less than 10 ohms.

 

 

 

AOTC %

If equipped with two stages of humidi®cation, verify that the reading across the 2nd stage humidi®cation nor-

 

mally open relay contacts is greater than 100 ohms.

 

 

 

AOTCTEST

Verify that the analog device connected to this output strokes to its 100% position.

 

DOTC X

Verify that the analog device connected to this output strokes to its 0% position.

 

DOTCTEST

Using an ohmmeter, verify that the reading across the DOTC (Discrete Output Temperature Control) normally

 

open relay contacts is less than 10 ohms.

 

 

 

DTCC X

Using an ohmmeter, verify that the reading across the DOTC normally open relay contacts is greater than 1000

 

ohms.

 

 

 

DTCCTEST

Using an ohmmeter, verify that the reading across the DTCC (Discrete Timeclock Control) normally open relay

 

 

contacts is less than 10 ohms. Proceed with the testing of electric heat stages (Table 21). If the unit is not

 

 

equipped with electric heat, exit the Quick Test mode as described below:

 

EXIT TST

 

 

 

TST CMPL

Test is now completed. The unit is back under normal automatic control.

 

 

 

 

 

 

Table 21 Ð Electric Heater Test

 

 

 

KEYBOARD

DISPLAY

COMMENTS/ACTION

ENTRY

RESPONSE

 

 

 

NOTE: Only the con®gured number of stages are tested and appear on the display.

 

ELE HEAT

Entering ®eld test of electric heater. (Set the HOA switch to AUTO.)

 

EHS1 X

 

 

STG1 TST

The fan starts. If equipped, the IGVs open to 30%. After an 11-second delay, the 1st stage of heat is

 

turned ON.

 

 

 

EHS2 X

The 1st stage of heat is turned OFF.

 

STG2 TST

After a 2-second delay, the 2nd stage of heat is turned ON.

 

EHS3 X

The 2nd-stage of heat is turned OFF.

 

STG3 TST

After a 2-second delay, the 3rd stage of heat is turned ON.

 

EHS4 X

The 3rd stage of heat is turned OFF.

 

STG4 TST

After a 2-second delay, the 4th stage of heat is turned ON.

 

EHS5 X

The 4th stage of heat is turned OFF.

 

STG5 TST

After a 2-second delay, the 5th stage of heat is turned ON.

 

EHS6 X

The 5th stage of heat is turned OFF.

 

STG6 TST

After a 2-second delay, the 6th stage of heat is turned ON.

 

EHS7 X

The 6th stage of heat is turned OFF.

 

STG7 TST

After a 2-second delay, the 7th stage of heat is turned ON.

 

EHS8 X

The 7th stage of heat is turned OFF.

 

STG8 TST

After a 2-second delay, the 8th stage of heat is turned ON.

 

EXIT TST

The fan and preceding stage of heat shut OFF.

 

TST CMPL

Test is complete. The unit is back under automatic control.

 

 

 

107

Image 107
Contents Contents Installation, Operation, Start-Up InstructionsGeneral Safety ConsiderationsInstallation Page VAV ABXIGV PICNormally Closed Direct ExpansionFMB Ð Filter Mixing Box MXB Ð Mixing BoxControl Box for Remote Mounting AQ2 AFSAotc AQ1PIC Section Control Box Component Arrangements, 39L PIC Section Control Box Component Arrangement, 39NX Sizes PIC Section Control Box Component Arrangement, 39NX Sizes Page Address Input and Output PointsUnit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Page Page Page Page Page Page Terminal Signal Junction Box Connections for Optional Remote Control BoxValve Assembly Typical Hot Water Valve Wiring Duct Static Pressure Probe Chilled Water Valve WiringNema Ð National Electrical Manufacturers Association Ohms Resistance TemperatureMixed-Air Temperature Sensor HH79NZ021 Installation Supply/Return Air Temperature Sensor HH79NZ019 Enthalpy Control SettingsCOI L Comno Wall-Mounted Relative Humidity Sensor Fig Duct-Mounted Relative Humidity Sensor Locations Air¯ow Switch P/N HK06WC030 CGCDXGAS001A00 CO2 Sensor AccessoriesCGCDXSEN002A00 CGCDXSEN003A00CO2 Concentration PPM Air Quality CO2 Sensor Wall Mount Version ShownOAC Pressure Transducers Sensor Module PIN no Recommended Sensor Device WiringManufacturer Part Number ProcessorField Wiring of Sensors Stroke Recommended ActuatorsField-Supplied Mixing Box Actuator Signal Wiring Fire Shut Down Terminal Block HAND/OFF/AUTO Switch Tran Ð TransformerHigh-Pressure Switch Remove Jumper Evacuation Supply Fan ContactorPres Single-Pole, Double-Throw Spdt Relay Wiring of Device Under Discrete Output Temperature Control Wiring of Two-Stage Humidication Control Relays Duct Mounted Relative Humidity Transmitter Wiring Air Quality and Oavp Sensor Wiring Wiring of Return Fan Volume Control With IGVs Control System Pulse-Type Meter WiringCCN Communication Wiring Outdoor Air Thermostat AHUAir Handling Unit Relay ModuleOperative USE Keys Local Interface Device Key UsageFunction USE Keys Oavp Status History Schedule Service Set Point TestFunctions and Subfunctions SUB Function NumberOperation Keyboard Display Description Entry Control OperationStatus Keyboard DirectoryInputs VAV Direct Expansion Oavp Ð Outside Air Velocity Pressure AIRQUAL1 SET Point Quick Test History Keyboard Display Comments Entry Response Example 1 Ð Reading Alarm CodesExample 2 Ð Reading Current Operating Modes Display Description AlarmsDisplay Codes Force StatesRelay Stages State of Items ControlledExample 3 Ð Forcing An Input Value Example 4 Ð Forcing An Output ValueTo LOG OFF Example 5 Ð Using Quick TestExample 6 Ð Logging On and Logging Off Service Function Keyboard Display Comments Entry Response To LOG onService Conguration Ranges and Defaults Analog Output Temperature Control Example 9 Ð User Congurations Example 7 Ð Reading and Changing Factory CongurationsExample 8 Ð Conguration of Measurements Example 12 Ð Conguration of Loadshed Example 11 Ð Conguration of Space Temperature ResetExample 10 Ð Conguration of Heating Coil Example 13 Ð Conguration of Fan Tracking Example 14 Ð Conguration of Alarm LimitsExample 15 Ð Conguration of Analog Temperature Control Set Point Ranges and Defaults Example 16 Ð Conguration of Discrete Temperature ControlExample 17 Ð Service History Conguration Example 18 Ð Service/Maintenance Alarm CongurationExample 20 Ð Reading and Changing System Set Points Example 21 Ð Setting of Time and DateExample 22 Ð Setting Daylight Savings Time Schedule I Sample Time Schedule Example 23 Ð Setting of HolidaysPeriod 1 Dene schedule period Example 24 Ð Using the Schedule FunctionKeyboard Display Comment Entry Response Programming Period For this example, Period 6 is used for holiday only Control Operating Sequence Constant Volume and Variable Air Volume UnitsPage Page Indoor-Air Quality MAT Ð Mixed-Air TemperatureOAT Ð Outdoor-Air Temperature IAQConstant Volume Units Only RAT Ð Return-Air CCV Ð Cooling Coil ValveDX Submaster Gain Control Operation Variable Air Volume Units Only Page Oavp Ð Outside Air Velocity Pressure Outside AirOAC Constant Outside Air102 Initial Check START-UPKeyboard Display COMMENTS/ACTION Entry Response Test of Input SignalsFollowing Keyboard Display COMMENTS/ACTION Entry Response FSD NRMFor Variable Air Volume Units Test of Output SignalsElectric Heater Test Test of Output Options Using Option ModuleDC Milliamps DC Voltage Control Loop CheckoutDirect Expansion DX Cooling Test Digital DC Volt Meter vs DC Milliamp MeterRecommended Gain Starting Valves Valve TroubleshootingHCV 10/FORCED Typical LinkagesExample 25 Ð Forcing An Output IGV %Exit Test Control Module TroubleshootingExample 26 Ð Heating Coil Valve Test Way Normally Open Dsio Problem Possible Cause Corrective Action Unit TroubleshootingHCV, CCV, IGV Malfunctioning IAQ featuresOAC malfunctioning Metric Conversion Chart

39L specifications

The Carrier 39L is a cutting-edge air conditioning unit designed for both residential and commercial applications, providing exceptional cooling and heating performance. Equipped with advanced technologies, this system ensures optimal climate control while maintaining energy efficiency.

One of the standout features of the Carrier 39L is its inverter technology. This innovation allows the system to adjust its compressor speed based on the ambient temperature, which results in a significant reduction in energy consumption. By operating at varying capacities rather than a fixed output, the 39L can maintain a consistent temperature, enhancing comfort while lowering electricity bills.

The Carrier 39L also includes a high-efficiency air filtration system, designed to capture dust, allergens, and other airborne particles. This not only improves indoor air quality but also promotes a healthier living environment. The filtration system is complemented by anti-bacterial treatment, ensuring that the air circulated within your space is both clean and refreshing.

In terms of design, the Carrier 39L boasts a sleek and compact form factor, making it easy to integrate into various settings, from homes to offices. Its quiet operation is another notable feature, as it minimizes noise levels, allowing occupants to enjoy a serene atmosphere without disruptive sound.

Further enhancing convenience, the Carrier 39L comes equipped with smart connectivity options. Users can control the unit remotely via a smartphone app, making it easy to adjust settings, program schedules, and monitor energy usage from anywhere. This feature not only improves user experience but also supports energy-saving practices.

Durability is also a key characteristic of the Carrier 39L. Constructed with high-quality materials and coated with corrosion-resistant treatments, the unit is built to withstand various environmental conditions. This ensures long-lasting performance and reduces the need for frequent maintenance.

Overall, the Carrier 39L is a versatile, efficient, and user-friendly air conditioning solution. Its blend of advanced technologies, energy-saving capabilities, and robust design makes it an ideal choice for those seeking reliable climate control in their spaces. Whether for residential comfort or commercial necessity, the Carrier 39L stands out as a leader in modern air conditioning.