Page 74

Table 13 Ð Keyboard Directory (cont)

SERVICE CONFIGURATIONS

Keyboard Entry

Display

Description

 

AIRQUAL1

Con®guration of indoor air quality

 

and AQ sensor no. 1

 

 

 

MPG X

Master proportional gain

 

MIG X

Master integral gain

 

XDP X

Maximum damper position

 

Q1LV X

Air quality sensor 1 low voltage

 

point

 

 

 

Q1HV X

Air quality sensor 1 high voltage

 

point

 

 

 

Q1LR X

Air quality sensor 1 low voltage

 

reference

 

 

 

Q1HR X

Air quality sensor 1 high voltage

 

reference

 

 

 

MDP X

Minimum damper position

 

 

 

 

AIRQUAL2

Con®guration of indoor air quality

 

and AQ sensor no. 2

 

 

 

MPG X

Master proportional gain

 

MIG X

Master integral gain

 

XDP X

Maximum damper position

 

Q2LV X

Air quality sensor 2 low voltage point

 

Q2HV X

Air quality sensor 2 high voltage point

 

Q2LR X

Air quality sensor 2 low voltage reference

 

Q2HR X

Air quality sensor 2 high voltage reference

 

MDP X

Minimum damper position

 

 

 

 

AOSS X

Con®guration of optimal start/stop

 

BLDF X

Building factor

 

UOCF X

24 hour occupied factor

 

SETB X

Set point bias

 

OSMT X

Maximum allowable stop time

 

 

 

 

SPRESET

Con®guration of space temperature reset

 

RTIO X

Reset ratio X

 

LIMT X

Reset limit X

 

 

 

 

LOADSHED

Con®guration of loadshed

 

LSGP X

Loadshed group number (1-16)

 

 

 

 

FANTRACK

Con®guration of fan tracking

 

SVUL X

Supply velocity upper limit

 

RVUL X

Return velocity upper limit

 

SDAR X

Supply duct area

 

RDAR X

Return duct area

 

MPG X

Master proportional gain

 

MIG X

Master integral gain

 

MDG X

Master derivative gain

 

SMG X

Submaster gain

 

SCV X

Submaster center value

 

SMR X

Submaster reference value

 

SMR X

Submaster reference value forced

 

 

 

SERVICE CONFIGURATIONS

Keyboard Entry

Display

Description

 

HUMIDITY

Con®guration of humidity

 

MPG X

Master proportional gain

 

MIG X

Master integral gain

 

MDG X

Master derivative gain

 

SMG X

Submaster gain

 

SCV X

Submaster center value

 

SMR X

Submaster reference value

 

SMR X

Submaster reference value forced

 

 

 

 

ALRMLIMT

Con®guration of alarm limits

 

SPLO X

Space temperature low alarm limit/

 

occupied

 

 

 

SPHO X

Space temperature high alarm limit/

 

occupied

 

 

 

SPLU X

Space temperature low alarm limit/

 

unoccupied

 

 

 

SPHU X

Space temperature high alarm limit/

 

unoccupied

 

 

 

SALO X

Supply air temperature low alarm limit/

 

occupied

 

 

 

SAHO X

Supply air temperature high alarm limit/

 

occupied

 

 

 

SALU X

Supply air temperature low alarm limit/

 

unoccupied

 

 

 

SAHU X

Supply air temperature high alarm limit/

 

unoccupied

 

 

 

RALO X

Return air temperature low alarm limit/

 

occupied

 

 

 

RAHO X

Return air temperature high alarm limit/

 

occupied

 

 

 

RALU X

Return air temperature low alarm limit/

 

unoccupied

 

 

 

RAHU X

Return air temperature high alarm limit/

 

unoccupied

 

 

 

TLO X

Temperature input low alarm limit/

 

occupied

 

 

 

THO X

Temperature input high alarm limit/

 

occupied

 

 

 

TLU X

Temperature input low alarm limit/

 

unoccupied

 

 

 

THU X

Temperature input high alarm limit/

 

unoccupied

 

 

 

OATL X

Outside air temperature low alarm limit

 

OATH X

Outside air temperature high alarm limit

 

MATL X

Mixed air temperature low alarm limit

 

MATH X

Mixed air temperature high alarm limit

 

RHL X

Relative humidity low alarm limit

 

RHH X

Relative humidity high alarm limit

 

ORHL X

Outside air relative humidity low alarm

 

limit

 

 

 

ORHH X

Outside air relative humidity high alarm

 

limit

 

 

 

SPL X

Static pressure low alarm limit

 

SPH X

Static pressure high alarm limit

 

SVPL X

Supply velocity pressure low alarm limit

 

SVPH X

Supply velocity pressure high alarm limit

 

RVPL X

Return velocity pressure low alarm limit

 

RVPH X

Return velocity pressure high alarm limit

 

CFML X

Delta CFM x 100 low alarm limit

 

CFMH X

Delta CFM x 100 high alarm limit

 

Q1H X

Air quality sensor 1 high alarm limit

Q2H X

Air quality sensor 2 high alarm limit

74

Image 74
Contents Installation, Operation, Start-Up Instructions ContentsGeneral Safety ConsiderationsInstallation Page PIC ABXIGV VAVMXB Ð Mixing Box Direct ExpansionFMB Ð Filter Mixing Box Normally ClosedControl Box for Remote Mounting AQ1 AFSAotc AQ2PIC Section Control Box Component Arrangements, 39L PIC Section Control Box Component Arrangement, 39NX Sizes PIC Section Control Box Component Arrangement, 39NX Sizes Page Input and Output Points AddressUnit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Page Page Page Page Page Page Junction Box Connections for Optional Remote Control Box Terminal SignalValve Assembly Typical Hot Water Valve Wiring Chilled Water Valve Wiring Duct Static Pressure ProbeNema Ð National Electrical Manufacturers Association Resistance Temperature OhmsMixed-Air Temperature Sensor HH79NZ021 Installation Enthalpy Control Settings Supply/Return Air Temperature Sensor HH79NZ019COI L Comno Wall-Mounted Relative Humidity Sensor Fig Duct-Mounted Relative Humidity Sensor Locations Air¯ow Switch P/N HK06WC030 CGCDXSEN003A00 CO2 Sensor AccessoriesCGCDXSEN002A00 CGCDXGAS001A00Air Quality CO2 Sensor Wall Mount Version Shown CO2 Concentration PPMOAC Pressure Transducers Processor Recommended Sensor Device WiringManufacturer Part Number Sensor Module PIN noField Wiring of Sensors Recommended Actuators StrokeField-Supplied Mixing Box Actuator Signal Wiring Evacuation Supply Fan Contactor HAND/OFF/AUTO Switch Tran Ð TransformerHigh-Pressure Switch Remove Jumper Fire Shut Down Terminal BlockPres Single-Pole, Double-Throw Spdt Relay Wiring of Device Under Discrete Output Temperature Control Wiring of Two-Stage Humidication Control Relays Duct Mounted Relative Humidity Transmitter Wiring Air Quality and Oavp Sensor Wiring Wiring of Return Fan Volume Control With IGVs Pulse-Type Meter Wiring Control SystemCCN Communication Wiring Relay Module AHUAir Handling Unit Outdoor Air ThermostatOperative USE Keys Local Interface Device Key UsageFunction USE Keys SUB Function Number Status History Schedule Service Set Point TestFunctions and Subfunctions OavpControl Operation Operation Keyboard Display Description EntryKeyboard Directory StatusInputs VAV Direct Expansion Oavp Ð Outside Air Velocity Pressure AIRQUAL1 SET Point Quick Test History Keyboard Display Comments Entry Response Example 1 Ð Reading Alarm CodesExample 2 Ð Reading Current Operating Modes Force States AlarmsDisplay Codes Display DescriptionExample 4 Ð Forcing An Output Value State of Items ControlledExample 3 Ð Forcing An Input Value Relay StagesKeyboard Display Comments Entry Response To LOG on Example 5 Ð Using Quick TestExample 6 Ð Logging On and Logging Off Service Function To LOG OFFService Conguration Ranges and Defaults Analog Output Temperature Control Example 9 Ð User Congurations Example 7 Ð Reading and Changing Factory CongurationsExample 8 Ð Conguration of Measurements Example 12 Ð Conguration of Loadshed Example 11 Ð Conguration of Space Temperature ResetExample 10 Ð Conguration of Heating Coil Example 13 Ð Conguration of Fan Tracking Example 14 Ð Conguration of Alarm LimitsExample 15 Ð Conguration of Analog Temperature Control Example 18 Ð Service/Maintenance Alarm Conguration Example 16 Ð Conguration of Discrete Temperature ControlExample 17 Ð Service History Conguration Set Point Ranges and DefaultsExample 20 Ð Reading and Changing System Set Points Example 21 Ð Setting of Time and DateExample 22 Ð Setting Daylight Savings Time Example 23 Ð Setting of Holidays Schedule I Sample Time SchedulePeriod 1 Dene schedule period Example 24 Ð Using the Schedule FunctionKeyboard Display Comment Entry Response Programming Period For this example, Period 6 is used for holiday only Constant Volume and Variable Air Volume Units Control Operating SequencePage Page IAQ MAT Ð Mixed-Air TemperatureOAT Ð Outdoor-Air Temperature Indoor-Air QualityConstant Volume Units Only CCV Ð Cooling Coil Valve RAT Ð Return-AirDX Submaster Gain Control Operation Variable Air Volume Units Only Page Constant Outside Air Outside AirOAC Oavp Ð Outside Air Velocity Pressure102 START-UP Initial CheckTest of Input Signals Keyboard Display COMMENTS/ACTION Entry ResponseKeyboard Display COMMENTS/ACTION Entry Response FSD NRM FollowingTest of Output Signals For Variable Air Volume UnitsTest of Output Options Using Option Module Electric Heater TestDigital DC Volt Meter vs DC Milliamp Meter Control Loop CheckoutDirect Expansion DX Cooling Test DC Milliamps DC VoltageValve Troubleshooting Recommended Gain Starting ValvesIGV % Typical LinkagesExample 25 Ð Forcing An Output HCV 10/FORCEDExit Test Control Module TroubleshootingExample 26 Ð Heating Coil Valve Test Way Normally Open Dsio Unit Troubleshooting Problem Possible Cause Corrective ActionHCV, CCV, IGV Malfunctioning IAQ featuresOAC malfunctioning Metric Conversion Chart

39L specifications

The Carrier 39L is a cutting-edge air conditioning unit designed for both residential and commercial applications, providing exceptional cooling and heating performance. Equipped with advanced technologies, this system ensures optimal climate control while maintaining energy efficiency.

One of the standout features of the Carrier 39L is its inverter technology. This innovation allows the system to adjust its compressor speed based on the ambient temperature, which results in a significant reduction in energy consumption. By operating at varying capacities rather than a fixed output, the 39L can maintain a consistent temperature, enhancing comfort while lowering electricity bills.

The Carrier 39L also includes a high-efficiency air filtration system, designed to capture dust, allergens, and other airborne particles. This not only improves indoor air quality but also promotes a healthier living environment. The filtration system is complemented by anti-bacterial treatment, ensuring that the air circulated within your space is both clean and refreshing.

In terms of design, the Carrier 39L boasts a sleek and compact form factor, making it easy to integrate into various settings, from homes to offices. Its quiet operation is another notable feature, as it minimizes noise levels, allowing occupants to enjoy a serene atmosphere without disruptive sound.

Further enhancing convenience, the Carrier 39L comes equipped with smart connectivity options. Users can control the unit remotely via a smartphone app, making it easy to adjust settings, program schedules, and monitor energy usage from anywhere. This feature not only improves user experience but also supports energy-saving practices.

Durability is also a key characteristic of the Carrier 39L. Constructed with high-quality materials and coated with corrosion-resistant treatments, the unit is built to withstand various environmental conditions. This ensures long-lasting performance and reduces the need for frequent maintenance.

Overall, the Carrier 39L is a versatile, efficient, and user-friendly air conditioning solution. Its blend of advanced technologies, energy-saving capabilities, and robust design makes it an ideal choice for those seeking reliable climate control in their spaces. Whether for residential comfort or commercial necessity, the Carrier 39L stands out as a leader in modern air conditioning.