Carrier 39L Junction Box Connections for Optional Remote Control Box, Terminal Signal

Page 37

Table 2 Ð Junction Box Connections for Optional Remote Control Box

REMOTE

CONTROL

FAN SECTION

JUNCTION

CONTROL BOX

BOX

JUNCTION BOX

BOX

LOCATION

TERMINAL

SIGNAL

TERMINAL

MPSIO

2

SAT Ð BLK

1

MPSIO

3

SAT Ð RED

2

MPSIO

8

MAT Ð BLK

3

MPSIO

9

MAT Ð RED

4

TB3

10

FLTS Ð BLK

5

MPSIO

28

FLTS Ð RED

6

TB3

10

LTT Ð K3

7

MPSIO

13

LTT Ð K1

8

TB2

19

OAD Ð BLK

9

TB2

20

OAD Ð WHT

10

TB2

6

OAD Ð GRN

11

MPSIO

40

OAD Ð RED

12

TB2

21

RAD Ð BLK

13

TB2

22

RAD Ð WHT

14

TB2

7

RAD Ð GRN

15

TB2

6

RAD Ð RED

16

TB2

27

EXD Ð BLK

17

TB2

28

EXD Ð WHT

18

TB2

8

EXD Ð GRN

19

TB2

7

EXD Ð RED

20

TB2

15

SFAN1 Ð BLK

21

TB2

16

SFAN1 Ð WHT

22

MPSIO

38

SFAN1 Ð GRN

23

MPSIO

37

SFAN1 Ð RED

24

TB2

17

SFAN2 Ð BLK

25

TB2

18

SFAN2 Ð WHT

26

TB2

23

RFAN1 Ð BLK

27

TB2

24

RFAN1 Ð WHT

28

SPSIO

38

RFAN1 Ð GRN

29

SPSIO

37

RFAN1 Ð RED

30

TB2

25

RFAN2 Ð BLK

31

TB2

26

RFAN2 Ð WHT

32

SPSIO

12

PH Ð BLK

33

SPSIO

11

PH Ð RED

34

NOTES:

1.Pneumatic tubing to connect the air¯ow sensor in the fan to the remote control box is bundled with the internal PIC wiring to the junction box, but does not enter the box. Route tube directly to remote control box along with conduit containing wiring from junction box to remote control box.

2.See Legend on page 7.

37

Image 37
Contents Contents Installation, Operation, Start-Up InstructionsInstallation Safety ConsiderationsGeneral Page IGV ABXPIC VAVFMB Ð Filter Mixing Box Direct ExpansionMXB Ð Mixing Box Normally ClosedControl Box for Remote Mounting Aotc AFSAQ1 AQ2PIC Section Control Box Component Arrangements, 39L PIC Section Control Box Component Arrangement, 39NX Sizes PIC Section Control Box Component Arrangement, 39NX Sizes Page Address Input and Output PointsUnit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Page Page Page Page Page Page Terminal Signal Junction Box Connections for Optional Remote Control BoxValve Assembly Typical Hot Water Valve Wiring Duct Static Pressure Probe Chilled Water Valve WiringNema Ð National Electrical Manufacturers Association Ohms Resistance TemperatureMixed-Air Temperature Sensor HH79NZ021 Installation Supply/Return Air Temperature Sensor HH79NZ019 Enthalpy Control SettingsCOI L Comno Wall-Mounted Relative Humidity Sensor Fig Duct-Mounted Relative Humidity Sensor Locations Air¯ow Switch P/N HK06WC030 CGCDXSEN002A00 CO2 Sensor AccessoriesCGCDXSEN003A00 CGCDXGAS001A00CO2 Concentration PPM Air Quality CO2 Sensor Wall Mount Version ShownOAC Pressure Transducers Manufacturer Part Number Recommended Sensor Device WiringProcessor Sensor Module PIN noField Wiring of Sensors Stroke Recommended ActuatorsField-Supplied Mixing Box Actuator Signal Wiring High-Pressure Switch Remove Jumper HAND/OFF/AUTO Switch Tran Ð TransformerEvacuation Supply Fan Contactor Fire Shut Down Terminal BlockPres Single-Pole, Double-Throw Spdt Relay Wiring of Device Under Discrete Output Temperature Control Wiring of Two-Stage Humidication Control Relays Duct Mounted Relative Humidity Transmitter Wiring Air Quality and Oavp Sensor Wiring Wiring of Return Fan Volume Control With IGVs Control System Pulse-Type Meter WiringCCN Communication Wiring Air Handling Unit AHURelay Module Outdoor Air ThermostatFunction USE Keys Local Interface Device Key UsageOperative USE Keys Functions and Subfunctions Status History Schedule Service Set Point TestSUB Function Number OavpOperation Keyboard Display Description Entry Control OperationStatus Keyboard DirectoryInputs VAV Direct Expansion Oavp Ð Outside Air Velocity Pressure AIRQUAL1 SET Point Quick Test History Example 2 Ð Reading Current Operating Modes Example 1 Ð Reading Alarm CodesKeyboard Display Comments Entry Response Display Codes AlarmsForce States Display DescriptionExample 3 Ð Forcing An Input Value State of Items ControlledExample 4 Ð Forcing An Output Value Relay StagesExample 6 Ð Logging On and Logging Off Service Function Example 5 Ð Using Quick TestKeyboard Display Comments Entry Response To LOG on To LOG OFFService Conguration Ranges and Defaults Analog Output Temperature Control Example 8 Ð Conguration of Measurements Example 7 Ð Reading and Changing Factory CongurationsExample 9 Ð User Congurations Example 10 Ð Conguration of Heating Coil Example 11 Ð Conguration of Space Temperature ResetExample 12 Ð Conguration of Loadshed Example 15 Ð Conguration of Analog Temperature Control Example 14 Ð Conguration of Alarm LimitsExample 13 Ð Conguration of Fan Tracking Example 17 Ð Service History Conguration Example 16 Ð Conguration of Discrete Temperature ControlExample 18 Ð Service/Maintenance Alarm Conguration Set Point Ranges and DefaultsExample 22 Ð Setting Daylight Savings Time Example 21 Ð Setting of Time and DateExample 20 Ð Reading and Changing System Set Points Schedule I Sample Time Schedule Example 23 Ð Setting of HolidaysKeyboard Display Comment Entry Response Programming Period Example 24 Ð Using the Schedule FunctionPeriod 1 Dene schedule period For this example, Period 6 is used for holiday only Control Operating Sequence Constant Volume and Variable Air Volume UnitsPage Page OAT Ð Outdoor-Air Temperature MAT Ð Mixed-Air TemperatureIAQ Indoor-Air QualityConstant Volume Units Only RAT Ð Return-Air CCV Ð Cooling Coil ValveDX Submaster Gain Control Operation Variable Air Volume Units Only Page OAC Outside AirConstant Outside Air Oavp Ð Outside Air Velocity Pressure102 Initial Check START-UPKeyboard Display COMMENTS/ACTION Entry Response Test of Input SignalsFollowing Keyboard Display COMMENTS/ACTION Entry Response FSD NRMFor Variable Air Volume Units Test of Output SignalsElectric Heater Test Test of Output Options Using Option ModuleDirect Expansion DX Cooling Test Control Loop CheckoutDigital DC Volt Meter vs DC Milliamp Meter DC Milliamps DC VoltageRecommended Gain Starting Valves Valve TroubleshootingExample 25 Ð Forcing An Output Typical LinkagesIGV % HCV 10/FORCEDExample 26 Ð Heating Coil Valve Test Way Normally Open Control Module TroubleshootingExit Test Dsio Problem Possible Cause Corrective Action Unit TroubleshootingHCV, CCV, IGV OAC malfunctioning IAQ featuresMalfunctioning Metric Conversion Chart

39L specifications

The Carrier 39L is a cutting-edge air conditioning unit designed for both residential and commercial applications, providing exceptional cooling and heating performance. Equipped with advanced technologies, this system ensures optimal climate control while maintaining energy efficiency.

One of the standout features of the Carrier 39L is its inverter technology. This innovation allows the system to adjust its compressor speed based on the ambient temperature, which results in a significant reduction in energy consumption. By operating at varying capacities rather than a fixed output, the 39L can maintain a consistent temperature, enhancing comfort while lowering electricity bills.

The Carrier 39L also includes a high-efficiency air filtration system, designed to capture dust, allergens, and other airborne particles. This not only improves indoor air quality but also promotes a healthier living environment. The filtration system is complemented by anti-bacterial treatment, ensuring that the air circulated within your space is both clean and refreshing.

In terms of design, the Carrier 39L boasts a sleek and compact form factor, making it easy to integrate into various settings, from homes to offices. Its quiet operation is another notable feature, as it minimizes noise levels, allowing occupants to enjoy a serene atmosphere without disruptive sound.

Further enhancing convenience, the Carrier 39L comes equipped with smart connectivity options. Users can control the unit remotely via a smartphone app, making it easy to adjust settings, program schedules, and monitor energy usage from anywhere. This feature not only improves user experience but also supports energy-saving practices.

Durability is also a key characteristic of the Carrier 39L. Constructed with high-quality materials and coated with corrosion-resistant treatments, the unit is built to withstand various environmental conditions. This ensures long-lasting performance and reduces the need for frequent maintenance.

Overall, the Carrier 39L is a versatile, efficient, and user-friendly air conditioning solution. Its blend of advanced technologies, energy-saving capabilities, and robust design makes it an ideal choice for those seeking reliable climate control in their spaces. Whether for residential comfort or commercial necessity, the Carrier 39L stands out as a leader in modern air conditioning.