| SERVICE SUBFUNCTION |   | CONFIGURATION VALUE | RANGE | FACTORY DEFAULT | 
|   | NUMBER |   | VALUE | 
|   |   |   |   | 
|   | 13 |   | Night Purge Duration (minutes) | 5 to 240 | 15 | 
|   |   | Night Purge Low Temperature Damper Position (% output) | 0 to 100 | 10 | 
|   |   |   | Night Purge High Temperature Damper Position (% output) | 0 to 100 | 35 | 
|   |   |   | Constant Outside Air Master Proportional Gain | 0.0 to 5.0 | 0.3 | 
|   |   |   | Constant Outside Air Master Integral Gain | 0.0 to 5.0 | 1.0 | 
|   |   |   | Constant Outside Air Master Derivative Gain | 0.0 to 5.0 | 0.0 | 
|   | 14 |   | Constant Outside Air Submaster Gain | 60 to 600 | * | 
|   |   | OAVP Sensor Low Voltage Point | 0 to 2 | 2 | 
|   |   |   | OAVP Sensor High Voltage Point | 5 to 10 | 10 | 
|   |   |   | OAVP Sensor Low Voltage Reference | 0.0 to 2.0 | 0.0 | 
|   |   |   | OAVP Sensor High Voltage Reference | 0.01 to 5.00 | 0.05 | 
|   |   |   | OAVP Sensor Probe Multiplier Factor | 0.100 to 9.999 | 1.564 | 
|   |   |   | Air Quality Sensor 1 Master Proportional Gain | 0.01 to 1.00 | 0.10 | 
|   |   |   | Air Quality Sensor 1 Master Integral Gain | 0.01 to 1.00 | 0.03 | 
|   | 15 |   | Air Quality Sensor 1 Maximum Damper Position (%) | 0 to 100 | 50 | 
|   |   | Air Quality Sensor 1 Low Voltage Point | 0 to 2 | 2 | 
|   |   |   | Air Quality Sensor 1 High Voltage Point | 5 to 10 | 10 | 
|   |   |   | Air Quality Sensor 1 Low Voltage Reference | 0 to 2000 | 0 | 
|   |   |   | Air Quality Sensor 1 High Voltage Reference | 0 to 2000 | 2000 | 
|   |   |   | Air Quality Sensor 2 Master Proportional Gain | 0.01 to 1.00 | 0.10 | 
|   |   |   | Air Quality Sensor 2 Master Integral Gain | 0.01 to 1.00 | 0.03 | 
|   | 16 |   | Air Quality Sensor 2 Maximum Damper Position (%) | 0 to 100 | 50 | 
|   |   | Air Quality Sensor 2 Low Voltage Point | 0 to 2 | 2 | 
|   |   |   | Air Quality Sensor 2 High Voltage Point | 5 to 10 | 10 | 
|   |   |   | Air Quality Sensor 2 Low Voltage Reference | 0 to 2000 | 0 | 
|   |   |   | Air Quality Sensor 2 High Voltage Reference | 0 to 2000 | 2000 | 
|   |   |   | Building Factor (%) | 1 to 100 | 10 | 
|   | 17 |   | 24 hour Unoccupied Factor | 0 to 99 | 15 | 
|   |   | Set Point Bias (F) | 0 to 10 | 2 | 
|   |   |   | 
|   |   |   | Maximum Allowable Stop Time | 0 to 120 | 60 | 
|   |   |   |   |   |   | 
|   | 18 |   | Reset Ratio | 0 to 10 | 3 | 
|   |   | Reset Limit | 0 to 20 | 10 | 
|   |   |   | 
|   |   |   | Supply Velocity Upper Limit (in. wg) | 0 to 3.0 | 2.0 | 
|   |   |   | Return Velocity Upper Limit (in. wg) | 0 to 3.0 | 2.0 | 
|   |   |   | Supply Duct Area | 0 to 50 | 0 | 
|   | 20 |   | Return Duct Area | 0 to 50 | 0 | 
|   |   | Fan Tracking Master Proportional Gain | 0.0 to 2.0 | 0.5 | 
|   |   |   | Fan Tracking Master Integral Gain | 0.0 to 2.0 | 0.5 | 
|   |   |   | Fan Tracking Master Derivative Gain | 0.0 to 5.0 | 0.0 | 
|   |   |   | Fan Tracking Submaster Gain | −20.0 to 20.0 | 10.0 | 
|   |   |   | Fan Tracking Submaster Center Value (%) | 0 to 100 | 50 | 
|   |   |   | Humidity Master Proportional Gain | 0.0 to 10.0 | 2.0 | 
|   | 21 |   | Humidity Master Integral Gain | 0.0 to 2.0 | 0.3 | 
|   |   | Humidity Master Derivative Gain | 0.0 to 10.0 | 0.0 | 
|   |   |   | Humidity Submaster Gain | −20.0 to 20.0 | 7.5 | 
|   |   |   | Humidity Submaster Center Value (%) | 0 to 100 | 50 | 
|   |   |   | Space Temperature Low Alarm Limit Ð Occupied (F) | −10 to 245 | 65 | 
|   |   |   | Space Temperature High Alarm Limit Ð Occupied (F) | −10 to 245 | 80 | 
|   |   |   | Space Temperature Low Alarm Limit Ð Unoccupied (F) | −10 to 245 | 45 | 
|   |   |   | Space Temperature High Alarm Limit Ð Unoccupied (F) | −10 to 245 | 100 | 
|   |   |   | Supply Air Temperature Low Alarm Limit Ð Occupied (F) | −10 to 245 | 45 | 
|   |   |   | Supply Air Temperature High Alarm Limit Ð Occupied (F) | −10 to 245 | 120 | 
|   |   |   | Supply Air Temperature Low Alarm Limit Ð Unoccupied (F) | −10 to 245 | 35 | 
|   |   |   | Supply Air Temperature High Alarm Limit Ð Unoccupied (F) | −10 to 245 | 180 | 
|   |   |   | Return Air Temperature Low Alarm Limit Ð Occupied (F) | −10 to 245 | 60 | 
|   |   |   | Return Air Temperature High Alarm Limit Ð Occupied (F) | −10 to 245 | 90 | 
|   |   |   | Return Air Temperature Low Alarm Limit Ð Unoccupied (F) | −10 to 245 | 35 | 
|   |   |   | Return Air Temperature High Alarm Limit Ð Unoccupied (F) | −10 to 245 | 120 | 
|   |   |   | Temperature Input Low Alarm Limit Ð Occupied (F) | −10 to 245 | −10 | 
|   |   |   | Temperature Input High Alarm Limit Ð Occupied (F) | −10 to 245 | 245 | 
|   |   |   | Temperature Input Low Alarm Limit Ð Unoccupied (F) | −10 to 245 | −10 | 
|   |   |   | Temperature Input High Alarm Limit Ð Unoccupied (F) | −10 to 245 | 245 | 
|   | 22 |   | Outside Air Temperature Low Alarm Limit (F) | −40 to 245 | −40 | 
|   |   | Outside Air Temperature High Alarm Limit (F) | −40 to 245 | 120 | 
|   |   |   | 
|   |   |   | Mixed Air Temperature Low Alarm Limit (F) | 0 to 250 | 0 | 
|   |   |   | Mixed Air Temperature High Alarm Limit (F) | 0 to 250 | 250 | 
|   |   |   | Relative Humidity Low Alarm Limit (%) | 0 to 100 | 0 | 
|   |   |   | Relative Humidity High Alarm Limit (%) | 0 to 100 | 100 | 
|   |   |   | Outside Air Relative Humidity Low Alarm Limit (%) | 0 to 100 | 0 | 
|   |   |   | Outside Air Relative Humidity High Alarm Limit (%) | 0 to 100 | 100 | 
|   |   |   | Static Pressure Low Alarm Limit (in. wg) | 0 to 5.0 | 1.0 | 
|   |   |   | Static Pressure High Alarm Limit (in. wg) | 0 to 5.0 | 2.5 | 
|   |   |   | Supply Velocity Low Alarm Limit (in. wg) | 0 to 3.0 | 0.0 | 
|   |   |   | Supply Velocity High Alarm Limit (in. wg) | 0 to 3.0 | 3.0 | 
|   |   |   | Return Velocity Low Alarm Limit (in. wg) | 0 to 3.0 | 0.0 | 
|   |   |   | Return Velocity High Alarm Limit (in. wg) | 0 to 3.0 | 3.0 | 
|   |   |   | Delta CFM x 100 (CCFM) Low Alarm Limit | 0 to 250 | 0 | 
|   |   |   | Delta CFM x 100 (CCFM) High Alarm Limit | 0 to 250 | 250 | 
|   |   |   | Air Quality Sensor 1 High Alarm Limit (ppm) | 0 to 2000 | 800 | 
|   |   |   | Air Quality Sensor 2 High Alarm Limit (ppm) | 0 to 2000 | 800 | 
|   |   |   | Preheat Coil/AOTC Master Proportional Gain | 0.0 to 20.0 | 5.0 | 
|   |   |   | Preheat Coil/AOTC Master Integral Gain | 0.0 to 2.0 | 0.3 | 
|   | 23 |   | Preheat Coil/AOTC Master Derivative Gain | 0.0 to 20.0 | 0.0 | 
|   |   | Preheat Coil/AOTC Submaster Gain | −20.0 to 20.0 | −5.0 | 
|   |   |   | Preheat Coil/AOTC Submaster Center Value (%) | 0 to 100 F | 50 | 
|   |   |   | Preheat Coil/AOTC Fan/Off Value (F) | 35 to 65 | 40 | 
|   |   |   | Preheat Coil/AOTC Sensor | 0 to 128 | 0 | 
|   | 24 |   | Discrete Temperature Control Sensor | 0 to 128 | 0 | 
|   |   | Discrete Temperature Control Logic | 0 to 1 | 0 | 
|   |   |   | Discrete Temperature Control Hysteresis (F) | 0 to 20 | 2 | 
|   | 26 |   | Service/Maintenance Limits (hours x 1000) | 0 to 99 | 0 | 
|   |   | Service/Maintenance Elapsed Hours (hours x 1000) | 0 to 99 | 0 | 
|   |   |   | 
|   | LEGEND |   |   |   | 
| AOTC | Ð Analog Output Temperature Control |   |   | 
| OAVP | Ð Outside Air Velocity Pressure |   |   |   |