Carrier 39L Display Codes, Force States, Display Description, Operating Modes, Alarms

Page 79

Occupied Cooling (31) Ð Indicates that the unit is in the Cooling mode to satisfy its Occupied Cooling set point.

Occupied Fan Only (32) Ð Indicates that the unit is main- taining set point by using a mixture of outside and return air only. No mechanical heating or cooling is being used.

Nighttime Free Cooling (33) Ð Indicates that the supply fan is on and using outside air to precool the space served by the unit. Unit must be con®gured for nighttime free cool-

ing ( ). (This mode is enabled by .)

Smoke Pressurization (34) Ð Indicates that the unit is in the Pressurization mode. This mode is issued from the ®re system panel. Refer to Table 15 for the state of the items controlled.

Smoke Evacuation (35) Ð Indicates that the unit is in the Smoke Evacuation mode. This mode is issued from the system panel. Refer to Table 15 for the state of the items controlled.

Smoke Purge (36) Ð Indicates that the unit is in the Smoke Purge mode. This mode is issued from the ®re system panel. Refer to Table 15 for the state of the items controlled.

Fire Shutdown (37) Ð Indicates that the unit is in the Fire Shutdown mode. This mode is issued from the ®re system panel or local smoke detector. Refer to Table 15 for the state of the items controlled.

Quick Test (38) Ð Indicates that the unit is in the Quick Test mode. It allows the user to test all inputs and outputs con- nected to the PIC controller. All control routines are deac- tivated when the unit is in this mode. This mode can only be initiated manually when the supply fan status is OFF. (HOA switch is in OFF position.) In order to reactivate all

the con®gured control routines, press and then press .

Timed Override (39) Ð Indicates that the unit operation has been extended by the user. Unit must be con®gured for

Timed Override schedule and timed override hours ( ).

 

Table 14 Ð Display Codes

 

 

 

FORCE STATES

Display

Description

1Fire mode force

2Internal safety force

3Quick Test/Service tool force

4HSIO/Building Supervisor force

5Remote Building Supervisor force

6Loadshed minimum offtime force

7Data transfer force

8BEST (Building Environmental Systems Translator) force

9Temperature override force

10Loadshed force

 

OPERATING MODES

Display

Description

21Temperature Reset in effect

22Demand Limit in effect

23Unoccupied Heating mode

24Unoccupied Cooling mode

26Optimal Start mode

27Unoccupied mode

29Optimal Stop mode

30Occupied Heating mode

31Occupied Cooling mode

32Occupied Fan Only mode

33Nighttime Free Cooling mode

34Pressurization mode

35Evacuation mode

36Smoke Purge mode

37Fire Shutdown mode

38Quick Test mode

39Timed Override mode

 

ALARMS

Display

Description

60Air quality 1 high limit

61Air quality 2 high limit

62Air quality/constant outside air suspended

63(Not used)

64DX cooling shutdown

65Pressurization

66Evacuation

67Smoke purge

68Fire shutdown

69Service/maintenance required

70Linkage failure

71Space temperature low limit

72Space temperature high limit

73Supply-air temperature low limit

74Supply-air temperature high limit

75Return-air temperature low limit

76Return-air temperature high limit

77Mixed-air temperature low limit

78Mixed-air temperature high limit

79Outside-air temperature low limit

80Outside-air temperature high limit

81Static pressure low limit

82Static pressure high limit

83Relative humidity low limit

84Relative humidity high limit

85Fan status

86Freezestat

87Analog temperature control sensor low limit

88Analog temperature control sensor high limit

89Outside-air relative humidity low limit

90Outside-air relative humidity high limit

91Supply velocity pressure low limit

92Supply velocity pressure high limit

93Return velocity pressure low limit

94Return velocity pressure high limit

95Delta CCFM low limit

96Delta CCFM high limit

97Filter status

98Duct high humidity

CCFM Ð Cfm x 100

79

Image 79
Contents Contents Installation, Operation, Start-Up InstructionsInstallation Safety ConsiderationsGeneral Page VAV ABXIGV PICNormally Closed Direct ExpansionFMB Ð Filter Mixing Box MXB Ð Mixing BoxControl Box for Remote Mounting AQ2 AFSAotc AQ1PIC Section Control Box Component Arrangements, 39L PIC Section Control Box Component Arrangement, 39NX Sizes PIC Section Control Box Component Arrangement, 39NX Sizes Page Address Input and Output PointsUnit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Page Page Page Page Page Page Terminal Signal Junction Box Connections for Optional Remote Control BoxValve Assembly Typical Hot Water Valve Wiring Duct Static Pressure Probe Chilled Water Valve WiringNema Ð National Electrical Manufacturers Association Ohms Resistance TemperatureMixed-Air Temperature Sensor HH79NZ021 Installation Supply/Return Air Temperature Sensor HH79NZ019 Enthalpy Control SettingsCOI L Comno Wall-Mounted Relative Humidity Sensor Fig Duct-Mounted Relative Humidity Sensor Locations Air¯ow Switch P/N HK06WC030 CGCDXGAS001A00 CO2 Sensor AccessoriesCGCDXSEN002A00 CGCDXSEN003A00CO2 Concentration PPM Air Quality CO2 Sensor Wall Mount Version ShownOAC Pressure Transducers Sensor Module PIN no Recommended Sensor Device WiringManufacturer Part Number ProcessorField Wiring of Sensors Stroke Recommended ActuatorsField-Supplied Mixing Box Actuator Signal Wiring Fire Shut Down Terminal Block HAND/OFF/AUTO Switch Tran Ð TransformerHigh-Pressure Switch Remove Jumper Evacuation Supply Fan ContactorPres Single-Pole, Double-Throw Spdt Relay Wiring of Device Under Discrete Output Temperature Control Wiring of Two-Stage Humidication Control Relays Duct Mounted Relative Humidity Transmitter Wiring Air Quality and Oavp Sensor Wiring Wiring of Return Fan Volume Control With IGVs Control System Pulse-Type Meter WiringCCN Communication Wiring Outdoor Air Thermostat AHUAir Handling Unit Relay ModuleFunction USE Keys Local Interface Device Key UsageOperative USE Keys Oavp Status History Schedule Service Set Point TestFunctions and Subfunctions SUB Function NumberOperation Keyboard Display Description Entry Control OperationStatus Keyboard DirectoryInputs VAV Direct Expansion Oavp Ð Outside Air Velocity Pressure AIRQUAL1 SET Point Quick Test History Example 2 Ð Reading Current Operating Modes Example 1 Ð Reading Alarm CodesKeyboard Display Comments Entry Response Display Description AlarmsDisplay Codes Force StatesRelay Stages State of Items ControlledExample 3 Ð Forcing An Input Value Example 4 Ð Forcing An Output ValueTo LOG OFF Example 5 Ð Using Quick TestExample 6 Ð Logging On and Logging Off Service Function Keyboard Display Comments Entry Response To LOG onService Conguration Ranges and Defaults Analog Output Temperature Control Example 8 Ð Conguration of Measurements Example 7 Ð Reading and Changing Factory CongurationsExample 9 Ð User Congurations Example 10 Ð Conguration of Heating Coil Example 11 Ð Conguration of Space Temperature ResetExample 12 Ð Conguration of Loadshed Example 15 Ð Conguration of Analog Temperature Control Example 14 Ð Conguration of Alarm LimitsExample 13 Ð Conguration of Fan Tracking Set Point Ranges and Defaults Example 16 Ð Conguration of Discrete Temperature ControlExample 17 Ð Service History Conguration Example 18 Ð Service/Maintenance Alarm CongurationExample 22 Ð Setting Daylight Savings Time Example 21 Ð Setting of Time and DateExample 20 Ð Reading and Changing System Set Points Schedule I Sample Time Schedule Example 23 Ð Setting of HolidaysKeyboard Display Comment Entry Response Programming Period Example 24 Ð Using the Schedule FunctionPeriod 1 Dene schedule period For this example, Period 6 is used for holiday only Control Operating Sequence Constant Volume and Variable Air Volume UnitsPage Page Indoor-Air Quality MAT Ð Mixed-Air TemperatureOAT Ð Outdoor-Air Temperature IAQConstant Volume Units Only RAT Ð Return-Air CCV Ð Cooling Coil ValveDX Submaster Gain Control Operation Variable Air Volume Units Only Page Oavp Ð Outside Air Velocity Pressure Outside AirOAC Constant Outside Air102 Initial Check START-UPKeyboard Display COMMENTS/ACTION Entry Response Test of Input SignalsFollowing Keyboard Display COMMENTS/ACTION Entry Response FSD NRMFor Variable Air Volume Units Test of Output SignalsElectric Heater Test Test of Output Options Using Option ModuleDC Milliamps DC Voltage Control Loop CheckoutDirect Expansion DX Cooling Test Digital DC Volt Meter vs DC Milliamp MeterRecommended Gain Starting Valves Valve TroubleshootingHCV 10/FORCED Typical LinkagesExample 25 Ð Forcing An Output IGV %Example 26 Ð Heating Coil Valve Test Way Normally Open Control Module TroubleshootingExit Test Dsio Problem Possible Cause Corrective Action Unit TroubleshootingHCV, CCV, IGV OAC malfunctioning IAQ featuresMalfunctioning Metric Conversion Chart

39L specifications

The Carrier 39L is a cutting-edge air conditioning unit designed for both residential and commercial applications, providing exceptional cooling and heating performance. Equipped with advanced technologies, this system ensures optimal climate control while maintaining energy efficiency.

One of the standout features of the Carrier 39L is its inverter technology. This innovation allows the system to adjust its compressor speed based on the ambient temperature, which results in a significant reduction in energy consumption. By operating at varying capacities rather than a fixed output, the 39L can maintain a consistent temperature, enhancing comfort while lowering electricity bills.

The Carrier 39L also includes a high-efficiency air filtration system, designed to capture dust, allergens, and other airborne particles. This not only improves indoor air quality but also promotes a healthier living environment. The filtration system is complemented by anti-bacterial treatment, ensuring that the air circulated within your space is both clean and refreshing.

In terms of design, the Carrier 39L boasts a sleek and compact form factor, making it easy to integrate into various settings, from homes to offices. Its quiet operation is another notable feature, as it minimizes noise levels, allowing occupants to enjoy a serene atmosphere without disruptive sound.

Further enhancing convenience, the Carrier 39L comes equipped with smart connectivity options. Users can control the unit remotely via a smartphone app, making it easy to adjust settings, program schedules, and monitor energy usage from anywhere. This feature not only improves user experience but also supports energy-saving practices.

Durability is also a key characteristic of the Carrier 39L. Constructed with high-quality materials and coated with corrosion-resistant treatments, the unit is built to withstand various environmental conditions. This ensures long-lasting performance and reduces the need for frequent maintenance.

Overall, the Carrier 39L is a versatile, efficient, and user-friendly air conditioning solution. Its blend of advanced technologies, energy-saving capabilities, and robust design makes it an ideal choice for those seeking reliable climate control in their spaces. Whether for residential comfort or commercial necessity, the Carrier 39L stands out as a leader in modern air conditioning.