Carrier 39L specifications Valve Assembly Typical

Page 38

Variable-Frequency Drives Ð The input signal for the inverter must be 4 to 20 mA. Use a 2-conductor 20 AWG (American Wire Gage) cable (single twisted pair, unshielded) to connect the input of the inverter to the output of the PIC control terminals. See Fig. 8.

Wire the inverter so that if it is placed in the manual or bypass mode the low temperature thermostat and the high- pressure switch (if supplied) are still in the motor control circuit to protect the unit.

Adjust the minimum inverter speed to provide at least 10% air¯ow when inlet guide vanes are at 0% (4 mA) and maxi- mum design air¯ow when inlet guide vanes are at 100% (20 mA). Use the local interface device to verify that the

supply fan status ( ) shows the fan is ON and that the

supply fan is operating at the lowest air¯ow adjustment. In- crease inverter minimum speed as required. For additional information, see the Quick Test section on page 103.

Water Valve Assemblies Ð Water valve assemblies (Fig. 13) are shipped inside the fan section for ®eld instal- lation. All valve assemblies have electrically powered ac- tuators. Each actuator has an external junction box for ®eld wiring. The junction box contains 24 vac power wires (WHITE/ BLUE, BLACK) and 4 to 20 mA signal wires (1RED, −GREEN). The actuators operate the valve through a linear stroke; if power is lost, a return spring reverses the stroke and returns the valve stem to the normal position.

To prevent electric shock and equipment damage, dis- connect the power to the control box before installing valve assemblies. Turn power switch located on control box door to OFF.

On installations where valve mounting space is limited, use unions to couple valve assemblies to water lines. If unions do not provide sufficient clearance, refer to the Valve Troubleshooting section, page 109.

On chilled water applications or hot water applications with 11¤2 to 3-in. valves, the valve actuators can be mounted in any position above the centerline of the valve body. For steam applications or hot water applications with 1¤2 to 11¤4-in. valves that have actuators and high-temperature linkage exten- sions, mount the actuator above the centerline of the valve body and 45 degrees from vertical. This position helps to prevent actuator exposure to direct heat convection.

DO NOT install valve assembly where excessive mois- ture, corrosive fumes, and/or vibration are present.

INSTALL all 2-way valve assemblies so that they close against system ¯ow. An arrow on the valve body indi- cates the proper ¯ow direction.

ALWAYS install 3-way mixing valve with 2 inlet ¯ows and one outlet. Normal ¯ow will be from port B to port AB with stem up. See Fig. 14.

VALVE ACTUATOR

ACTUATOR LINKAGE

VALVE BODY

Fig. 13 Ð Valve Assembly (Typical)

Fig. 14 Ð Three-Way Mixing Valve Ð Normal Flow,

Typical Piping

38

Image 38
Contents Installation, Operation, Start-Up Instructions ContentsGeneral Safety ConsiderationsInstallation Page PIC ABXIGV VAVMXB Ð Mixing Box Direct ExpansionFMB Ð Filter Mixing Box Normally ClosedControl Box for Remote Mounting AQ1 AFSAotc AQ2PIC Section Control Box Component Arrangements, 39L PIC Section Control Box Component Arrangement, 39NX Sizes PIC Section Control Box Component Arrangement, 39NX Sizes Page Input and Output Points AddressUnit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Page Page Page Page Page Page Junction Box Connections for Optional Remote Control Box Terminal SignalValve Assembly Typical Hot Water Valve Wiring Chilled Water Valve Wiring Duct Static Pressure ProbeNema Ð National Electrical Manufacturers Association Resistance Temperature OhmsMixed-Air Temperature Sensor HH79NZ021 Installation Enthalpy Control Settings Supply/Return Air Temperature Sensor HH79NZ019COI L Comno Wall-Mounted Relative Humidity Sensor Fig Duct-Mounted Relative Humidity Sensor Locations Air¯ow Switch P/N HK06WC030 CGCDXSEN003A00 CO2 Sensor AccessoriesCGCDXSEN002A00 CGCDXGAS001A00Air Quality CO2 Sensor Wall Mount Version Shown CO2 Concentration PPMOAC Pressure Transducers Processor Recommended Sensor Device WiringManufacturer Part Number Sensor Module PIN noField Wiring of Sensors Recommended Actuators StrokeField-Supplied Mixing Box Actuator Signal Wiring Evacuation Supply Fan Contactor HAND/OFF/AUTO Switch Tran Ð TransformerHigh-Pressure Switch Remove Jumper Fire Shut Down Terminal BlockPres Single-Pole, Double-Throw Spdt Relay Wiring of Device Under Discrete Output Temperature Control Wiring of Two-Stage Humidication Control Relays Duct Mounted Relative Humidity Transmitter Wiring Air Quality and Oavp Sensor Wiring Wiring of Return Fan Volume Control With IGVs Pulse-Type Meter Wiring Control SystemCCN Communication Wiring Relay Module AHUAir Handling Unit Outdoor Air ThermostatOperative USE Keys Local Interface Device Key UsageFunction USE Keys SUB Function Number Status History Schedule Service Set Point TestFunctions and Subfunctions OavpControl Operation Operation Keyboard Display Description EntryKeyboard Directory StatusInputs VAV Direct Expansion Oavp Ð Outside Air Velocity Pressure AIRQUAL1 SET Point Quick Test History Keyboard Display Comments Entry Response Example 1 Ð Reading Alarm CodesExample 2 Ð Reading Current Operating Modes Force States AlarmsDisplay Codes Display DescriptionExample 4 Ð Forcing An Output Value State of Items ControlledExample 3 Ð Forcing An Input Value Relay StagesKeyboard Display Comments Entry Response To LOG on Example 5 Ð Using Quick TestExample 6 Ð Logging On and Logging Off Service Function To LOG OFFService Conguration Ranges and Defaults Analog Output Temperature Control Example 9 Ð User Congurations Example 7 Ð Reading and Changing Factory CongurationsExample 8 Ð Conguration of Measurements Example 12 Ð Conguration of Loadshed Example 11 Ð Conguration of Space Temperature ResetExample 10 Ð Conguration of Heating Coil Example 13 Ð Conguration of Fan Tracking Example 14 Ð Conguration of Alarm LimitsExample 15 Ð Conguration of Analog Temperature Control Example 18 Ð Service/Maintenance Alarm Conguration Example 16 Ð Conguration of Discrete Temperature ControlExample 17 Ð Service History Conguration Set Point Ranges and DefaultsExample 20 Ð Reading and Changing System Set Points Example 21 Ð Setting of Time and DateExample 22 Ð Setting Daylight Savings Time Example 23 Ð Setting of Holidays Schedule I Sample Time SchedulePeriod 1 Dene schedule period Example 24 Ð Using the Schedule FunctionKeyboard Display Comment Entry Response Programming Period For this example, Period 6 is used for holiday only Constant Volume and Variable Air Volume Units Control Operating SequencePage Page IAQ MAT Ð Mixed-Air TemperatureOAT Ð Outdoor-Air Temperature Indoor-Air QualityConstant Volume Units Only CCV Ð Cooling Coil Valve RAT Ð Return-AirDX Submaster Gain Control Operation Variable Air Volume Units Only Page Constant Outside Air Outside AirOAC Oavp Ð Outside Air Velocity Pressure102 START-UP Initial CheckTest of Input Signals Keyboard Display COMMENTS/ACTION Entry ResponseKeyboard Display COMMENTS/ACTION Entry Response FSD NRM FollowingTest of Output Signals For Variable Air Volume UnitsTest of Output Options Using Option Module Electric Heater TestDigital DC Volt Meter vs DC Milliamp Meter Control Loop CheckoutDirect Expansion DX Cooling Test DC Milliamps DC VoltageValve Troubleshooting Recommended Gain Starting ValvesIGV % Typical LinkagesExample 25 Ð Forcing An Output HCV 10/FORCEDExit Test Control Module TroubleshootingExample 26 Ð Heating Coil Valve Test Way Normally Open Dsio Unit Troubleshooting Problem Possible Cause Corrective ActionHCV, CCV, IGV Malfunctioning IAQ featuresOAC malfunctioning Metric Conversion Chart

39L specifications

The Carrier 39L is a cutting-edge air conditioning unit designed for both residential and commercial applications, providing exceptional cooling and heating performance. Equipped with advanced technologies, this system ensures optimal climate control while maintaining energy efficiency.

One of the standout features of the Carrier 39L is its inverter technology. This innovation allows the system to adjust its compressor speed based on the ambient temperature, which results in a significant reduction in energy consumption. By operating at varying capacities rather than a fixed output, the 39L can maintain a consistent temperature, enhancing comfort while lowering electricity bills.

The Carrier 39L also includes a high-efficiency air filtration system, designed to capture dust, allergens, and other airborne particles. This not only improves indoor air quality but also promotes a healthier living environment. The filtration system is complemented by anti-bacterial treatment, ensuring that the air circulated within your space is both clean and refreshing.

In terms of design, the Carrier 39L boasts a sleek and compact form factor, making it easy to integrate into various settings, from homes to offices. Its quiet operation is another notable feature, as it minimizes noise levels, allowing occupants to enjoy a serene atmosphere without disruptive sound.

Further enhancing convenience, the Carrier 39L comes equipped with smart connectivity options. Users can control the unit remotely via a smartphone app, making it easy to adjust settings, program schedules, and monitor energy usage from anywhere. This feature not only improves user experience but also supports energy-saving practices.

Durability is also a key characteristic of the Carrier 39L. Constructed with high-quality materials and coated with corrosion-resistant treatments, the unit is built to withstand various environmental conditions. This ensures long-lasting performance and reduces the need for frequent maintenance.

Overall, the Carrier 39L is a versatile, efficient, and user-friendly air conditioning solution. Its blend of advanced technologies, energy-saving capabilities, and robust design makes it an ideal choice for those seeking reliable climate control in their spaces. Whether for residential comfort or commercial necessity, the Carrier 39L stands out as a leader in modern air conditioning.