Carrier 39L specifications Dsio

Page 112

DSIO

COMMUNICATIONS

LEDs

STATUS LED

ADDRESS

SELECTOR

PSIO

Fig. 83 Ð Module Address Selector Switch

and LED Locations

If only the PSIO slave or DSIO module indicate commu- nication failure, check the affected module for proper seat- ing. If the condition persists even though connections are correct, replace the module as described in the following section.

Module Replacement (PSIO, DSIO) Ð The PSIO master module controls the standard unit functions, the PSIO slave module controls many optional functions, and the DSIO module controls electric heat and/or DX cooling. If the mod- ule LEDs are not blinking and the unit or features associated with the module do not work, the module may need to be replaced. Before replacing an inoperative module, check to ensure that:

·The PIC control box power is on

·Power at the processor module is between 18 and 24 vac

·No fuses are blown

·All connections are ®rmly in place

If all of the preceding conditions exist, and the module LEDs are not blinking, the module needs to be replaced.

Before replacing a processor (PSIO) module, store the con- ®guration data from the old module on hard copy. The new processor module can be precon®gured or con®gured in the ®eld.

After obtaining a new module, ®eld-replace the inopera- tive module as follows:

1.Turn off all power to the fan motor starter and PIC con- trol box.

To avoid electrical shock and equipment damage, always disconnect all power to the control box be- fore replacing PIC modules.

2.Open the control box door.

3.Refer to Fig. 5-7 for control box component arrange- ments. Disengage all connectors from the module.

4.Use a screwdriver to remove the mounting screw securing the module to the control box. Remove the module.

5.Install the replacement module and replace the mount- ing screw.

6.Reinstall all connectors. Verify that each connector is in the correct location.

7.Turn on the power to the PIC control box and motor starter.

8.If you are replacing a PSIO master module that is not precon®gured, use the local interface device (HSIO) or Building Supervisor to reset the date and time and change the module's default settings. The original PSIO master module was factory con®gured to match the unit in which it was shipped. A replacement PSIO master mod-

ule must have the Factory Con®guration ( ) de- faults changed in the ®eld to match the con®guration of the unit in which it is being installed. Other settings may also need to be recon®gured to match the unit con- ®guration and/or the original module's settings.

9.Perform the Initial Check, run the Quick Test, and verify that the unit is operating correctly as described in the Start-Up section on page 103.

10.Close the PIC control box door.

112

Image 112
Contents Installation, Operation, Start-Up Instructions ContentsInstallation Safety ConsiderationsGeneral Page ABX IGVPIC VAVDirect Expansion FMB Ð Filter Mixing BoxMXB Ð Mixing Box Normally ClosedControl Box for Remote Mounting AFS AotcAQ1 AQ2PIC Section Control Box Component Arrangements, 39L PIC Section Control Box Component Arrangement, 39NX Sizes PIC Section Control Box Component Arrangement, 39NX Sizes Page Input and Output Points AddressUnit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39L Sizes 03-35 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 07-21 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Unit Wiring Schematic, 39NX Sizes 26-92 115 v, Typical Page Page Page Page Page Page Junction Box Connections for Optional Remote Control Box Terminal SignalValve Assembly Typical Hot Water Valve Wiring Chilled Water Valve Wiring Duct Static Pressure ProbeNema Ð National Electrical Manufacturers Association Resistance Temperature OhmsMixed-Air Temperature Sensor HH79NZ021 Installation Enthalpy Control Settings Supply/Return Air Temperature Sensor HH79NZ019COI L Comno Wall-Mounted Relative Humidity Sensor Fig Duct-Mounted Relative Humidity Sensor Locations Air¯ow Switch P/N HK06WC030 CO2 Sensor Accessories CGCDXSEN002A00CGCDXSEN003A00 CGCDXGAS001A00Air Quality CO2 Sensor Wall Mount Version Shown CO2 Concentration PPMOAC Pressure Transducers Recommended Sensor Device Wiring Manufacturer Part NumberProcessor Sensor Module PIN noField Wiring of Sensors Recommended Actuators StrokeField-Supplied Mixing Box Actuator Signal Wiring HAND/OFF/AUTO Switch Tran Ð Transformer High-Pressure Switch Remove JumperEvacuation Supply Fan Contactor Fire Shut Down Terminal BlockPres Single-Pole, Double-Throw Spdt Relay Wiring of Device Under Discrete Output Temperature Control Wiring of Two-Stage Humidication Control Relays Duct Mounted Relative Humidity Transmitter Wiring Air Quality and Oavp Sensor Wiring Wiring of Return Fan Volume Control With IGVs Pulse-Type Meter Wiring Control SystemCCN Communication Wiring AHU Air Handling UnitRelay Module Outdoor Air ThermostatFunction USE Keys Local Interface Device Key UsageOperative USE Keys Status History Schedule Service Set Point Test Functions and SubfunctionsSUB Function Number OavpControl Operation Operation Keyboard Display Description EntryKeyboard Directory StatusInputs VAV Direct Expansion Oavp Ð Outside Air Velocity Pressure AIRQUAL1 SET Point Quick Test History Example 2 Ð Reading Current Operating Modes Example 1 Ð Reading Alarm CodesKeyboard Display Comments Entry Response Alarms Display CodesForce States Display DescriptionState of Items Controlled Example 3 Ð Forcing An Input ValueExample 4 Ð Forcing An Output Value Relay StagesExample 5 Ð Using Quick Test Example 6 Ð Logging On and Logging Off Service FunctionKeyboard Display Comments Entry Response To LOG on To LOG OFFService Conguration Ranges and Defaults Analog Output Temperature Control Example 8 Ð Conguration of Measurements Example 7 Ð Reading and Changing Factory CongurationsExample 9 Ð User Congurations Example 10 Ð Conguration of Heating Coil Example 11 Ð Conguration of Space Temperature ResetExample 12 Ð Conguration of Loadshed Example 15 Ð Conguration of Analog Temperature Control Example 14 Ð Conguration of Alarm LimitsExample 13 Ð Conguration of Fan Tracking Example 16 Ð Conguration of Discrete Temperature Control Example 17 Ð Service History CongurationExample 18 Ð Service/Maintenance Alarm Conguration Set Point Ranges and DefaultsExample 22 Ð Setting Daylight Savings Time Example 21 Ð Setting of Time and DateExample 20 Ð Reading and Changing System Set Points Example 23 Ð Setting of Holidays Schedule I Sample Time ScheduleKeyboard Display Comment Entry Response Programming Period Example 24 Ð Using the Schedule FunctionPeriod 1 Dene schedule period For this example, Period 6 is used for holiday only Constant Volume and Variable Air Volume Units Control Operating SequencePage Page MAT Ð Mixed-Air Temperature OAT Ð Outdoor-Air TemperatureIAQ Indoor-Air QualityConstant Volume Units Only CCV Ð Cooling Coil Valve RAT Ð Return-AirDX Submaster Gain Control Operation Variable Air Volume Units Only Page Outside Air OACConstant Outside Air Oavp Ð Outside Air Velocity Pressure102 START-UP Initial CheckTest of Input Signals Keyboard Display COMMENTS/ACTION Entry ResponseKeyboard Display COMMENTS/ACTION Entry Response FSD NRM FollowingTest of Output Signals For Variable Air Volume UnitsTest of Output Options Using Option Module Electric Heater TestControl Loop Checkout Direct Expansion DX Cooling TestDigital DC Volt Meter vs DC Milliamp Meter DC Milliamps DC VoltageValve Troubleshooting Recommended Gain Starting ValvesTypical Linkages Example 25 Ð Forcing An OutputIGV % HCV 10/FORCEDExample 26 Ð Heating Coil Valve Test Way Normally Open Control Module TroubleshootingExit Test Dsio Unit Troubleshooting Problem Possible Cause Corrective ActionHCV, CCV, IGV OAC malfunctioning IAQ featuresMalfunctioning Metric Conversion Chart

39L specifications

The Carrier 39L is a cutting-edge air conditioning unit designed for both residential and commercial applications, providing exceptional cooling and heating performance. Equipped with advanced technologies, this system ensures optimal climate control while maintaining energy efficiency.

One of the standout features of the Carrier 39L is its inverter technology. This innovation allows the system to adjust its compressor speed based on the ambient temperature, which results in a significant reduction in energy consumption. By operating at varying capacities rather than a fixed output, the 39L can maintain a consistent temperature, enhancing comfort while lowering electricity bills.

The Carrier 39L also includes a high-efficiency air filtration system, designed to capture dust, allergens, and other airborne particles. This not only improves indoor air quality but also promotes a healthier living environment. The filtration system is complemented by anti-bacterial treatment, ensuring that the air circulated within your space is both clean and refreshing.

In terms of design, the Carrier 39L boasts a sleek and compact form factor, making it easy to integrate into various settings, from homes to offices. Its quiet operation is another notable feature, as it minimizes noise levels, allowing occupants to enjoy a serene atmosphere without disruptive sound.

Further enhancing convenience, the Carrier 39L comes equipped with smart connectivity options. Users can control the unit remotely via a smartphone app, making it easy to adjust settings, program schedules, and monitor energy usage from anywhere. This feature not only improves user experience but also supports energy-saving practices.

Durability is also a key characteristic of the Carrier 39L. Constructed with high-quality materials and coated with corrosion-resistant treatments, the unit is built to withstand various environmental conditions. This ensures long-lasting performance and reduces the need for frequent maintenance.

Overall, the Carrier 39L is a versatile, efficient, and user-friendly air conditioning solution. Its blend of advanced technologies, energy-saving capabilities, and robust design makes it an ideal choice for those seeking reliable climate control in their spaces. Whether for residential comfort or commercial necessity, the Carrier 39L stands out as a leader in modern air conditioning.