Carrier 50HJ004, 50HE003-006 installation instructions EconoMi$er IV Wiring

Page 37

FOR OCCUPANCY CONTROL

REPLACE JUMPER WITH

FIELD-SUPPLIED TIME CLOCK

50HE,HJ

LEGEND

Potentiometer Defaults Settings:

NOTES:

DCV— Demand Controlled Ventilation

Power Exhaust

Middle

1.

620 ohm, 1 watt 5% resistor should be removed only when using differential

Minimum Pos.

Fully Closed

 

enthalpy or dry bulb.

IAQ — Indoor Air Quality

 

DCV Max.

Middle

2.

If a separate field-supplied 24 v transformer is used for the IAQ sensor power

LA — Low Ambient Lockout Device

OAT — Outdoor-Air Temperature

DCV Set

Middle

 

supply, it cannot have the secondary of the transformer grounded.

POT — Potentiometer

Enthalpy

C Setting

3.

For field-installed remote minimum position POT, remove black wire jumper

RAT — Return-Air Temperature

 

 

 

between P and P1 and set control minimum position POT to the minimum

 

 

 

 

position.

C06028

Fig. 34 ---EconoMi$er IV Wiring

 

 

 

 

BLACK

4

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

5

 

 

 

 

BLUE

2

 

 

 

 

 

 

500 OHM

 

 

 

8

 

RESISTOR

 

 

 

 

 

VIOLET

 

 

6

NOTE 1

 

 

 

 

 

PINK

 

 

 

 

 

 

 

7

 

RUN

 

 

 

 

 

 

 

 

 

-

 

 

RED

1

NOTE 3

 

 

 

 

+

 

 

 

10

50HJ540573

 

 

 

 

SENSOR 4 - 20 mA

 

YELLOW

 

 

ACTUATOR

 

 

11

ASSEMBLY

OPTIONAL CO2

 

 

 

 

 

 

 

 

 

OUTPUT

 

 

 

9

 

DIRECT DRIVE

 

 

WHITE

12

 

ACTUATOR

 

 

 

ECONOMISER2 PLUG

NOTES:

1.Switch on actuator must be in run position for economizer to operate.

2.PremierLink™ control requires that the standard 50HJ540569 outside-air sensor be replaced by either the CROASENR001A00 dry bulb sensor or HH57A077 enthalpy sensor.

3.50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500-ohm resistor.

C06029

Fig. 35 ---EconoMi$er2 with 4 to 20 mA Control Wiring

Outdoor Enthalpy Changeover

For enthalpy control, accessory enthalpy sensor (part number HH57AC078) is required. Replace the standard outdoor dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location. (See Fig. 27.) When the outdoor air enthalpy rises above the outdoor enthalpy changeover set point, the outdoor-air damper moves to its minimum position. The outdoor

enthalpy changeover set point is set with the outdoor enthalpy set point potentiometer on the EconoMi$er IV controller. The set points are A, B, C, and D. (See Fig. 43.) The factory-installed 620-ohm jumper must be in place across terminals SR and SR+ on the EconoMi$er IV controller. (See Fig. 27 and 44.)

37

Image 37
Contents Installation Instructions Alternate Unit Support Provide Unit Support Roof CurbRoof Curb Details Unit Leveling Tolerances Positioning50HJ 50HE50HJ004-007 Base Unit Dimensions 50HE003-006 Base Unit Dimensions Heat Anticipator Settings Field Power SupplyField Control Wiring Make Electrical ConnectionsHi-Static Physical Data 50HJBase Unit 50HE Physical Data 50HEPower Wiring Connections Electrical Data-50HE None YES Min Max PH---HzActual kW B00006 008,009 23.4 30.1 40.8 KW† Electrical Data-50HJ006 11.8 414 508 007 10.6 16.0 008 13.8 20.0 Ton 004+005 19.9 24.3 55.2 76.3 86.9 168 34.9 173 002 13.6 007 A00 or008 Humi 009 18.4 111 518 632 018 17.0 16.4 23.9 10 ton 01218.7 133 518 632 17.0 16.4 24.6 019 34.0 32.7 45.0 014 A00 or Actual kW12.5 Assembly Disconnect SwitchHumidi-MizerAdaptive Dehumidification System Manual Outdoor DamperTypical Humidi-MiZer t Adaptive Dehumidification System Outdoor Air Temperature Sensor OAT Install the Supply Air Temperature SAT SensorInstall the Indoor Air Quality CO2 Sensor Enthalpy Sensors and ControlRequired PremierLinkSensor UsageOr Equivalent Not UsedPremierLinktController Installed EconoMi$er IV Component Locations Return Air Enthalphy SensorHood Box Removal Supply Air Sensor Temperature Resistance Values Supply Air Temperature SAT SensorOutdoor Air Lockout Sensor Economi$er IV Control ModesEconoMi$er IV Wiring Differential Enthalphy Control Exhaust Set Point AdjustmentIndoor Air Quality IAQ Sensor Input Thermostats Minimum Position ControlDamper Movement + TR Dehumidification of Fresh Air with DCV Control Adjust Evaporator-Fan SpeedBelt Drive Motors Belt Drive Motor Mounting CO2Sensor Standard SettingsEvaporator-Fan Motor Data High-Static Motors Evaporator-Fan Motor Data Standard Motor600 900 1200 1400 1600 1800 2000 2200 2400 2600 Evaporator-Fan Motor Efficiency003,004,005 006 74/84 007 External Static Pressure in. wg879 Rpm Bhp Watts 900 566 142 690 228957 522 1000 598 173 718 267 9031300 701 809 418 902 540 983 665 Rpm Bhp Watts 1200 666 252 778 361 873 476 956 5941400 737 355 842 481 932 610 875 551 962 6891600 828 412 931 536 1022 670 Rpm Bhp Watts 1500 790 353 897 471 991 6001700 866 478 966 608 1800 905 551 1001 6871472 1761 1600 1462 20671495 1858 1700 1463 1766 1520 1964 18002300 1104 1046 1185 1212 1260 1386 2200 1063 929 1147 1089 1224 1256 1295 14312400 1145 1174 1223 1346 1296 1526 2500 1185 1311 1262 14901900 945 638 1042 796 Rpm Bhp Watts 1800 907 558 1006 708 1092 8602000 984 727 1078 892 2100 1024 823 1115 9972200 1063 929 1152 1111 1230 1294 2100 1024 823 1115 997 1195 1173 1268 13502300 1103 1044 1189 1234 1266 1425 2400 1143 1168 1227 13671000 583 163 707 Rpm Bhp Watts 900 554 134 6811100 612 195 735 9191300 674 276 Rpm Bhp Watts 1200 643 233 762 3441400 706 324 1500 738 3791600 757 343 866 455 962 580 Rpm Bhp Watts 1500 724 295 837 402 937 524 1028 660719 1700 790 398 894 514 988 6431474 1797 1700 External Sttic Pressure in. wg1490 1873 1800 1508 1957 19002500 1069 1084 1149 1239 1223 1403 1293 1576 2400 1033 970 1115 1120 1192 1279 1264 1448Rpm Bhp Watts 1500 1188 970 1261 1143 1600 1208 1033 12792500 1061 1053 1148 1233 1226 1416 1297 1604 2400 1026 945 1115 1118 1195 1295 1268 14762600 1097 1169 1181 1356 1257 1546 2700 1132 1294 1214 1487 1289 1684Refrigerant Service Ports Internal WiringUnit Preparation Return-Air FiltersHeating Safety ReliefVentilation Continuous Fan Operating Sequence Cooling Units Without EconomizerRoutine 3 OAT DX Cooling Temperature Control ExampleHumidi-MiZer Normal Design Cooling Operation Subcooling ModeEvaporator Coil CleaningCondenser Coil One-Row CoilCondenser-Fan Adjustment Evaporator Fan Belt AdjustmentFan Motor Bearings Condensate DrainLow Charge Cooling Cooling Charging Chart Standard 50HJ005Cooling Charging Chart Standard 50HJ007 50HE,HJ C06145 Unit Troubleshooting Replacement PartsEconomi$er IV Troubleshooting DCV Demand Controlled Ventilation and Power ExhaustDCV Minimum and Maximum Position Economi$er IV Troubleshooting CompletionSupply-Air Input Cooling Service Analysis EconoMi$er IV Input/Output Logic Subcooling Mode Liquid ReheatEconoMi$er IV Functional View START-UP Checklist