Carrier 50HJ004 Dehumidification of Fresh Air with DCV Control, Adjust Evaporator-Fan Speed

Page 41

N1

 

EXH

TR

TR1

N

 

Set

 

 

2V

10V

 

 

 

 

 

P1

EXH

 

24

24 Vac

 

 

Vac

COM

P

 

 

 

Min

HOT

_

T1

 

Pos

+

 

 

T

Open

 

 

 

 

 

 

 

 

DCV

1

2

 

 

Max

 

 

 

 

 

2V

10V

 

 

AQ1

DCV

 

 

5

 

 

 

 

 

 

 

AQ

 

DCV

 

4

SO+

 

Set

3

SO

2V

10V

 

 

 

 

 

 

SR+

Free

 

EF

EF1

 

Cool

 

 

 

SR

B

C

 

 

 

A

D

 

 

C06038

Fig. 44 ---EconoMi$er IV Control

CO2 SENSOR MAX RANGE SETTING

 

6000

 

 

 

 

 

 

(ppm)

5000

 

 

 

 

 

 

 

 

 

 

 

 

 

CONFIGURATION

4000

 

 

 

 

 

800 ppm

 

 

 

 

 

 

3000

 

 

 

 

 

900 ppm

 

 

 

 

 

1000 ppm

 

 

 

 

 

 

2000

 

 

 

 

 

1100 ppm

 

 

 

 

 

 

 

 

 

 

 

 

 

RANGE

1000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

2

3

4

5

6

7

8

 

DAMPER VOLTAGE FOR MAX VENTILATION RATE

C06039

Fig. 45 ---CO2 Sensor Maximum Range Setting

CO2 Sensor Configuration

The CO2 sensor has preset standard voltage settings that can be selected anytime after the sensor is powered up. (See Table 8.)

Use setting 1 or 2 for Carrier equipment. (See Table 8.)

1.Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode.

2.Press Mode twice. The STDSET Menu will appear.

3.Use the Up/Down button to select the preset number. (See Table 8.)

4.Press Enter to lock in the selection.

5.Press Mode to exit and resume normal operation.

The custom settings of the CO2 sensor can be changed anytime after the sensor is energized. Follow the steps below to change the non-standard settings:

1.Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode.

2.Press Mode twice. The STDSET Menu will appear.

3.Use the Up/Down button to toggle to the NONSTD menu and press Enter.

4.Use the Up/Down button to toggle through each of the nine variables, starting with Altitude, until the desired setting is reached.

5.Press Mode to move through the variables.

6.Press Enter to lock in the selection, then press Mode to continue to the next variable.

Dehumidification of Fresh Air with DCV Control

Information from ASHRAE indicates that the largest humidity load on any zone is the fresh air introduced. For some applications, a device such as a 62AQ energy recovery unit is added to reduce the moisture content of the fresh air being brought into the building when the enthalpy is high. In most cases, the normal heating and cooling processes are more than adequate to remove the humidity loads for most commercial applications.

If normal rooftop heating and cooling operation is not adequate for the outdoor humidity level, an energy recovery unit and/or a dehumidification option should be considered.

Step 7 Adjust Evaporator-Fan Speed

Adjust evaporator-fan speed to meet jobsite conditions.

Tables 9 and 10 show fan rpm at motor pulley settings for the 50HE003-006 and 50HJ004-007 units. Tables 11 and 14 show maximum amp draw of belt-drive motor. Table 13 shows sound data. Refer to Tables 15-34 for performance data. See Table 35 for accessory static pressure drop. See Fig. 47 for the Humidi-MiZersystem static pressure drops.

For units with electric heating, required minimum cfm is 900 for 50HJ004; 1200 for 50HJ005; 1500 for 50HJ006 and 1800 for 50HJ007.

Belt Drive Motors

Fan motor pulleys are factory set for speed shown in Table 1. Check pulley alignment and belt tension prior to start-up.

To change fan speed:

1.Shut off the unit power supply and tag disconnect.

2.Loosen the belt by loosening the fan motor mounting nuts. (See Fig. 47.)

3.Loosen movable pulley flange setscrew (See Fig. 48).

4.Screw movable flange toward fixed flange to increase speed and away from fixed flange to decrease speed. Increasing fan speed increases load on motor. Do not exceed maximum speed specified in Table 1.

5.Set movable flange at nearest keyway of pulley hub and tighten setscrew. (See Table 1 for speed change for each full turn of pulley flange.)

6.Adjust belt tension and align fan and motor pulleys per guidance below.

NOTE: Once the required flange position is determined for the correct blower rpm, it is recommended (but not required) that the variable pitch pulley be replaced with a corresponding size fixed sheave pulley.

To align fan and motor pulleys:

1.Loosen fan pulley setscrews.

2.Slide fan pulley along fan shaft.

3.Make angular alignment by loosening motor from mount- ing.

To adjust belt tension:

1.Loosen fan motor mounting nuts.

2.Slide motor mounting plate away from fan scroll for

proper belt tension (1/2-in. deflection with 7 to 10 lb of force).

3.Tighten motor mounting nuts.

4.Adjust bolt and tighten nut to secure motor in fixed position.

50HE,HJ

41

Image 41
Contents Installation Instructions Alternate Unit Support Provide Unit Support Roof CurbRoof Curb Details Unit Leveling Tolerances Positioning50HJ 50HE50HJ004-007 Base Unit Dimensions 50HE003-006 Base Unit Dimensions Heat Anticipator Settings Field Power SupplyField Control Wiring Make Electrical ConnectionsHi-Static Physical Data 50HJBase Unit 50HE Physical Data 50HEPower Wiring Connections Electrical Data-50HE None YES Min Max PH---HzActual kW B00006 008,009 23.4 30.1 40.8 KW† Electrical Data-50HJ006 11.8 414 508 007 10.6 16.0 008 13.8 20.0 Ton 004+005 19.9 24.3 55.2 76.3 86.9 168 34.9 173 002 13.6 007 A00 or008 Humi 009 18.4 111 518 632 018 17.0 16.4 23.9 10 ton 01218.7 133 518 632 17.0 16.4 24.6 019 34.0 32.7 45.0 12.5 A00 or Actual kW014 Assembly Disconnect SwitchHumidi-MizerAdaptive Dehumidification System Manual Outdoor DamperTypical Humidi-MiZer t Adaptive Dehumidification System Outdoor Air Temperature Sensor OAT Install the Supply Air Temperature SAT SensorInstall the Indoor Air Quality CO2 Sensor Enthalpy Sensors and ControlRequired PremierLinkSensor UsageOr Equivalent Not UsedPremierLinktController Installed EconoMi$er IV Component Locations Return Air Enthalphy SensorHood Box Removal Supply Air Sensor Temperature Resistance Values Supply Air Temperature SAT SensorOutdoor Air Lockout Sensor Economi$er IV Control ModesEconoMi$er IV Wiring Indoor Air Quality IAQ Sensor Input Exhaust Set Point AdjustmentDifferential Enthalphy Control Damper Movement Minimum Position ControlThermostats + TR Belt Drive Motors Adjust Evaporator-Fan SpeedDehumidification of Fresh Air with DCV Control Belt Drive Motor Mounting CO2Sensor Standard SettingsEvaporator-Fan Motor Data High-Static Motors Evaporator-Fan Motor Data Standard Motor600 900 1200 1400 1600 1800 2000 2200 2400 2600 Evaporator-Fan Motor Efficiency003,004,005 006 74/84 007 External Static Pressure in. wg879 Rpm Bhp Watts 900 566 142 690 228957 522 1000 598 173 718 267 9031300 701 809 418 902 540 983 665 Rpm Bhp Watts 1200 666 252 778 361 873 476 956 5941400 737 355 842 481 932 610 875 551 962 6891600 828 412 931 536 1022 670 Rpm Bhp Watts 1500 790 353 897 471 991 6001700 866 478 966 608 1800 905 551 1001 6871472 1761 1600 1462 20671495 1858 1700 1463 1766 1520 1964 18002300 1104 1046 1185 1212 1260 1386 2200 1063 929 1147 1089 1224 1256 1295 14312400 1145 1174 1223 1346 1296 1526 2500 1185 1311 1262 14901900 945 638 1042 796 Rpm Bhp Watts 1800 907 558 1006 708 1092 8602000 984 727 1078 892 2100 1024 823 1115 9972200 1063 929 1152 1111 1230 1294 2100 1024 823 1115 997 1195 1173 1268 13502300 1103 1044 1189 1234 1266 1425 2400 1143 1168 1227 13671000 583 163 707 Rpm Bhp Watts 900 554 134 6811100 612 195 735 9191300 674 276 Rpm Bhp Watts 1200 643 233 762 3441400 706 324 1500 738 3791600 757 343 866 455 962 580 Rpm Bhp Watts 1500 724 295 837 402 937 524 1028 660719 1700 790 398 894 514 988 6431474 1797 1700 External Sttic Pressure in. wg1490 1873 1800 1508 1957 19002500 1069 1084 1149 1239 1223 1403 1293 1576 2400 1033 970 1115 1120 1192 1279 1264 1448Rpm Bhp Watts 1500 1188 970 1261 1143 1600 1208 1033 12792500 1061 1053 1148 1233 1226 1416 1297 1604 2400 1026 945 1115 1118 1195 1295 1268 14762600 1097 1169 1181 1356 1257 1546 2700 1132 1294 1214 1487 1289 1684Refrigerant Service Ports Internal WiringUnit Preparation Return-Air FiltersHeating Safety ReliefVentilation Continuous Fan Operating Sequence Cooling Units Without EconomizerRoutine 3 OAT DX Cooling Temperature Control ExampleHumidi-MiZer Normal Design Cooling Operation Subcooling ModeEvaporator Coil CleaningCondenser Coil One-Row CoilCondenser-Fan Adjustment Evaporator Fan Belt AdjustmentFan Motor Bearings Condensate DrainLow Charge Cooling Cooling Charging Chart Standard 50HJ005Cooling Charging Chart Standard 50HJ007 50HE,HJ C06145 Unit Troubleshooting Replacement PartsEconomi$er IV Troubleshooting DCV Demand Controlled Ventilation and Power ExhaustSupply-Air Input Economi$er IV Troubleshooting CompletionDCV Minimum and Maximum Position Cooling Service Analysis EconoMi$er IV Input/Output Logic Subcooling Mode Liquid ReheatEconoMi$er IV Functional View START-UP Checklist