Carrier 50HE003-006, 50HJ004 Differential Enthalphy Control, Indoor Air Quality IAQ Sensor Input

Page 38

50HE,HJ

Differential Enthalphy Control

For differential enthalpy control, the EconoMi$er IV controller uses two enthalpy sensors (HH57AC078 and CRENTDIF004A00), one in the outside air and one in the return air duct. The EconoMi$er IV controller compares the outdoor air enthalpy to the return air enthalpy to determine EconoMi$er IV use. The controller selects the lower enthalpy air (return or outdoor) for cooling. For example, when the outdoor air has a lower enthalpy than the return air, the EconoMi$er IV opens to bring in outdoor air for free cooling.

(cfm)

2500

 

 

 

 

 

 

 

 

 

 

 

MINUTE

2000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PER

1500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FEET

1000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IN CUBIC

500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

FLOW

 

 

0.05

 

 

0.15

 

 

0.25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 36 ---Barometric Flow Capacity

C06030

 

 

 

 

 

 

 

(cfm)

30

 

 

 

 

 

 

 

 

 

 

 

 

 

MINUTE

 

 

 

 

 

 

 

 

 

 

 

 

 

25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PER

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

 

 

 

 

 

 

 

 

 

 

 

 

 

FEET

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CUBICIN

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

FLOW

0.13

0.20

0.22

0.25

0.30

0.35

0.40

0.45

0.50

 

 

 

 

 

 

 

STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C06031

 

 

 

Fig. 37 Outdoor-Air Damper Leakage---

 

 

(cfm)

6000

 

 

 

 

 

 

 

 

MINUTE

5000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PER

4000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3000

 

 

 

 

 

 

 

 

FEET

 

 

 

 

 

 

 

 

2000

 

 

 

 

 

 

 

 

CUBIC

 

 

 

 

 

 

 

 

1000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IN

 

 

 

 

 

 

 

 

 

FLOW

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.05

0.10

0.15

0.20

0.25

0.30

0.35

 

STATIC PRESSURE (in. wg)

C06032

Fig. 38 ---Return-Air Pressure Drop

SUPPLY AIR

TEMPERATURE

SENSOR

MOUNTING

LOCATION

SUPPLY AIR

TEMPERATURE

SENSOR

C06033

Fig. 39 ---Supply Air Sensor Location

C06034

Fig. 40 ---EconoMi$er IV Controller Potentiometer

and LED Locations

Replace the standard outside air dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location. (See Fig. 27.) Mount the return air enthalpy sensor in the return air duct. (See Fig. 42.) Wiring is provided in the EconoMi$er IV wiring harness. (See Fig. 34.) The outdoor enthalpy changeover set point is set with the outdoor enthalpy set point potentiometer on the EconoMi$er IV controller. When using this mode of changeover control, turn the enthalpy setpoint potentiometer fully clockwise to the D setting.

Indoor Air Quality (IAQ) Sensor Input

The IAQ input can be used for demand control ventilation control based on the level of CO2 measured in the space or return air duct.

Mount the accessory IAQ sensor according to manufacturer specifications. The IAQ sensor should be wired to the AQ and AQ1 terminals of the controller. Adjust the DCV potentiometers to correspond to the DCV voltage output of the indoor air quality sensor at the user-determined set point. (See Fig. 45.)

If a separate field-supplied transformer is used to power the IAQ sensor, the sensor must not be grounded or the EconoMi$er IV control board will be damaged.

Exhaust Set Point Adjustment

The exhaust set point will determine when the exhaust fan runs based on damper position (if accessory power exhaust is installed). The set point is modified with the Exhaust Fan Set Point (EXH SET) potentiometer. (See Fig. 40.) The set point represents the damper position above which the exhaust fans will be turned on. When there is a call for exhaust, the EconoMi$er IV controller provides a 45 ± 15 second delay before exhaust fan

38

Image 38
Contents Installation Instructions Provide Unit Support Roof Curb Alternate Unit SupportRoof Curb Details Positioning Unit Leveling Tolerances50HE 50HJ50HJ004-007 Base Unit Dimensions 50HE003-006 Base Unit Dimensions Field Control Wiring Field Power SupplyHeat Anticipator Settings Make Electrical ConnectionsPhysical Data 50HJ Hi-StaticPhysical Data 50HE Base Unit 50HEPower Wiring Connections Electrical Data-50HE None YES Actual kW PH---HzMin Max B00006 008,009 23.4 30.1 40.8 Electrical Data-50HJ KW†006 11.8 414 508 007 10.6 16.0 008 13.8 20.0 Ton 004+005 19.9 24.3 55.2 76.3 86.9 168 34.9 173 002 13.6 A00 or 007008 Humi 009 18.4 111 518 632 018 17.0 16.4 23.9 012 10 ton18.7 133 518 632 17.0 16.4 24.6 019 34.0 32.7 45.0 12.5 A00 or Actual kW014 Humidi-MizerAdaptive Dehumidification System Disconnect SwitchAssembly Manual Outdoor DamperTypical Humidi-MiZer t Adaptive Dehumidification System Install the Indoor Air Quality CO2 Sensor Install the Supply Air Temperature SAT SensorOutdoor Air Temperature Sensor OAT Enthalpy Sensors and ControlOr Equivalent PremierLinkSensor UsageRequired Not UsedPremierLinktController Installed Return Air Enthalphy Sensor EconoMi$er IV Component LocationsHood Box Removal Outdoor Air Lockout Sensor Supply Air Temperature SAT SensorSupply Air Sensor Temperature Resistance Values Economi$er IV Control ModesEconoMi$er IV Wiring Indoor Air Quality IAQ Sensor Input Exhaust Set Point AdjustmentDifferential Enthalphy Control Damper Movement Minimum Position ControlThermostats + TR Belt Drive Motors Adjust Evaporator-Fan SpeedDehumidification of Fresh Air with DCV Control CO2Sensor Standard Settings Belt Drive Motor MountingEvaporator-Fan Motor Data Standard Motor Evaporator-Fan Motor Data High-Static Motors003,004,005 006 74/84 007 Evaporator-Fan Motor Efficiency600 900 1200 1400 1600 1800 2000 2200 2400 2600 External Static Pressure in. wg957 522 1000 598 173 718 267 Rpm Bhp Watts 900 566 142 690 228879 9031400 737 355 842 481 932 610 Rpm Bhp Watts 1200 666 252 778 361 873 476 956 5941300 701 809 418 902 540 983 665 875 551 962 6891700 866 478 966 608 Rpm Bhp Watts 1500 790 353 897 471 991 6001600 828 412 931 536 1022 670 1800 905 551 1001 6871495 1858 1700 1462 20671472 1761 1600 1463 1766 1520 1964 18002400 1145 1174 1223 1346 1296 1526 2200 1063 929 1147 1089 1224 1256 1295 14312300 1104 1046 1185 1212 1260 1386 2500 1185 1311 1262 14902000 984 727 1078 892 Rpm Bhp Watts 1800 907 558 1006 708 1092 8601900 945 638 1042 796 2100 1024 823 1115 9972300 1103 1044 1189 1234 1266 1425 2100 1024 823 1115 997 1195 1173 1268 13502200 1063 929 1152 1111 1230 1294 2400 1143 1168 1227 13671100 612 195 735 Rpm Bhp Watts 900 554 134 6811000 583 163 707 9191400 706 324 Rpm Bhp Watts 1200 643 233 762 3441300 674 276 1500 738 379719 Rpm Bhp Watts 1500 724 295 837 402 937 524 1028 6601600 757 343 866 455 962 580 1700 790 398 894 514 988 6431490 1873 1800 External Sttic Pressure in. wg1474 1797 1700 1508 1957 1900Rpm Bhp Watts 1500 1188 970 1261 1143 2400 1033 970 1115 1120 1192 1279 1264 14482500 1069 1084 1149 1239 1223 1403 1293 1576 1600 1208 1033 12792600 1097 1169 1181 1356 1257 1546 2400 1026 945 1115 1118 1195 1295 1268 14762500 1061 1053 1148 1233 1226 1416 1297 1604 2700 1132 1294 1214 1487 1289 1684Unit Preparation Internal WiringRefrigerant Service Ports Return-Air FiltersVentilation Continuous Fan Safety ReliefHeating Operating Sequence Cooling Units Without EconomizerDX Cooling Temperature Control Example Routine 3 OATSubcooling Mode Humidi-MiZer Normal Design Cooling OperationCondenser Coil CleaningEvaporator Coil One-Row CoilFan Motor Bearings Evaporator Fan Belt AdjustmentCondenser-Fan Adjustment Condensate DrainCooling Charging Chart Standard 50HJ005 Low Charge CoolingCooling Charging Chart Standard 50HJ007 50HE,HJ C06145 Economi$er IV Troubleshooting Replacement PartsUnit Troubleshooting DCV Demand Controlled Ventilation and Power ExhaustSupply-Air Input Economi$er IV Troubleshooting CompletionDCV Minimum and Maximum Position Cooling Service Analysis Subcooling Mode Liquid Reheat EconoMi$er IV Input/Output LogicEconoMi$er IV Functional View START-UP Checklist