activation to allow the dampers to open. This delay allows the damper to reach the appropriate position to avoid unnecessary fan overload.
Minimum Position Control
There is a minimum damper position potentiometer on the EconoMi$er IV controller. (See Fig. 40.) The minimum damper position maintains the minimum airflow into the building during the occupied period.
When using demand ventilation, the minimum damper position represents the minimum ventilation position for VOC (volatile organic compound) ventilation requirements. The maximum demand ventilation position is used for fully occupied ventilation.
When demand ventilation control is not being used, the minimum position potentiometer should be used to set the occupied ventilation position. The maximum demand ventilation position should be turned fully clockwise.
Adjust the minimum position potentiometer to allow the minimum amount of outdoor air, as required by local codes, to enter the building. Make minimum position adjustments with at least 10_F temperature difference between the outdoor and
To determine the minimum position setting, perform the following procedure:
1.Calculate the appropriate mixed air temperature using the following formula:
Thermostats
The EconoMi$er IV control works with conventional thermostats that have a Y1 (cool stage 1), Y2 (cool stage 2), W1 (heat stage 1), W2 (heat stage 2), and G (fan). The EconoMi$er IV control does not support space temperature sensors. Connections are made at the thermostat terminal connection board located in the main control box.
19
| 18 | LED ON |
|
|
|
|
|
|
|
|
|
|
| |
|
|
| D |
|
|
|
|
|
|
|
|
|
| |
| 17 |
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| 16 |
| LED OFF | LED ON |
|
|
|
|
|
|
|
| ||
|
|
| C |
|
|
|
|
|
|
|
| |||
| 15 |
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
mA | 14 |
|
|
| LED OFF |
| LED ON |
|
|
|
|
| ||
|
|
|
|
|
| B |
|
|
|
|
| |||
| 13 |
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| 12 |
|
|
|
|
|
| LED OFF | LED ON |
|
| |||
|
|
|
|
|
|
|
|
|
| A |
|
| ||
| 11 |
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| 50HE,HJ | ||
| 10 |
|
|
|
|
|
|
|
|
| LED OFF |
| ||
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| 9 |
|
|
|
|
|
|
|
|
|
|
| 100 |
|
| 40 | 45 | 50 | 55 | 60 | 65 | 70 | 75 | 80 | 85 | 90 | 95 |
| |
|
|
|
|
| DEGREES FAHRENHEIT |
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Fig. 41 |
| C06035 |
| |||||||||
|
|
|
|
| ||||||||||
|
|
|
| Changeover Set Points |
|
|
|
|
|
(TO x 100OA ) + (TR x 100RA ) =TM
TO =
OA = Percent of Outdoor Air
TR =
RA = Percent of Return Air
TM =
ECONOMI$ER IV |
ECONOMI$ER IV CONTROLLER
GROMMET
As an example, if local codes require 10% outdoor air during occupied conditions,
(60 x .10) + (75 x .90) = 73.5_F
2.Disconnect the supply air sensor from terminals T and T1.
3.Ensure that the
4.Connect 24 vac across terminals TR and TR1.
5.Carefully adjust the minimum position potentiometer until the measured supply air temperature matches the calculated value.
6.Reconnect the mixed air sensor to terminals T and T1.
Remote control of the EconoMi$er IV damper is desirable when requiring additional temporary ventilation. If a
To control the minimum damper position remotely, remove the
Damper Movement
Damper movement from full open to full closed (or vice versa) takes 21/2 minutes.
RETURN AIR
SENSOR
RETURN DUCT
C06036
Fig. 42 --- Return Air Temperature or Enthalpy
Sensor Mounting Location
Occupancy Control
The factory default configuration for the EconoMi$er IV control is occupied mode. Occupied mode is provided by the black jumper from terminal TR to terminal N. When unoccupied mode is desired, install a