Fig. 20 --- Outdoor-Air Damper With
Hood Attached
C06132
Fig. 21 --- Outdoor-Air Damper Position Setting
Premierlink™ Control
The PremierLink controller is compatible with Carrier Comfort NetworkR (CCN) devices. This control is designed to allow users the access and ability to change
The PremierLink controller (see Fig. 22 and 23) requires the use of a Carrier electronic thermostat or a CCN connection for time broadcast to initiate its internal timeclock. This is necessary for broadcast of time of day functions (occupied/unoccupied). No sensors are supplied with the
NOTE: PremierLink controller versions 1.3 and later are shipped in Sensor mode. If used with a thermostat, the PremierLink controller must be configured to Thermostat mode.
Install the Supply Air Temperature (SAT) Sensor
When the unit is supplied with a
The SAT probe is
NOTE: The sensor must be mounted in the discharge airstream downstream of the cooling coil and any heating devices. Be sure the probe tip does not come in contact with any of the unit or heat surfaces.
Outdoor Air Temperature Sensor (OAT)
When the unit is supplied with a
Install the Indoor Air Quality (CO2) Sensor
Mount the optional indoor air quality (CO2) sensor according to manufacturer specifications.
A separate
Wire the CO2 sensor to the COM and IAQI terminals of J5 on the PremierLink controller. Refer to the PremierLink Installation,
Enthalpy Sensors and Control
The enthalpy control (HH57AC077) is supplied as a
NOTE: The enthalpy control must be set to the “D” setting for differential enthalpy control to work properly.
The enthalpy control receives the indoor and return enthalpy from the outdoor and return air enthalpy sensors and provides a dry contact switch input to the PremierLink controller. Locate the controller in place of an existing economizer controller or near the actuator. The mounting plate may not be needed if existing bracket is used.
A closed contact indicates that outside air is preferred to the return air. An open contact indicates that the economizer should remain at minimum position.
Outdoor Air Enthalphy Sensor/Enthalpy Controller (HH57AC077)
To wire the outdoor air enthalpy sensor, perform the following (See Fig. 25 and 26):
NOTE: The outdoor air sensor can be removed from the back of the enthalpy controller and mounted remotely.