Carrier 50HJ004 Install the Supply Air Temperature SAT Sensor, Outdoor Air Temperature Sensor OAT

Page 31

C06131

Fig. 20 ---Outdoor-Air Damper With

Hood Attached

C06132

Fig. 21 ---Outdoor-Air Damper Position Setting

PremierlinkControl

The PremierLink controller is compatible with Carrier Comfort NetworkR (CCN) devices. This control is designed to allow users the access and ability to change factory-defined settings, thus expanding the function of the standard unit control board. Carrier’s diagnostic standard tier display tools such as Navigatort or Scrolling Marquee can be used with the PremierLink controller.

The PremierLink controller (see Fig. 22 and 23) requires the use of a Carrier electronic thermostat or a CCN connection for time broadcast to initiate its internal timeclock. This is necessary for broadcast of time of day functions (occupied/unoccupied). No sensors are supplied with the field-mounted PremierLink control. The factory-installed PremierLink control includes only the supply-air temperature (SAT) sensor and the outdoor air temperature (OAT) sensor as standard. An indoor air quality (CO2) sensor can be added as an option. Refer to Table 5 for sensor usage. Refer to Fig. 24 for PremierLink controller wiring. The PremierLink control may be mounted in the control panel or an area below the control panel.

NOTE: PremierLink controller versions 1.3 and later are shipped in Sensor mode. If used with a thermostat, the PremierLink controller must be configured to Thermostat mode.

Install the Supply Air Temperature (SAT) Sensor

When the unit is supplied with a factory-mounted PremierLink control, the supply-air temperature (SAT) sensor (33ZCSENSAT) is factory-supplied and wired. The wiring is routed from the PremierLink control over the control box, through a grommet, into the fan section, down along the back side of the fan, and along the fan deck over to the supply-air opening.

The SAT probe is wire-tied to the supply-air opening (on the horizontal opening end) in its shipping position. Remove the sensor for installation. Re-position the sensor in the flange of the supply-air opening or in the supply air duct (as required by local codes). Drill or punch a 1/2-in. hole in the flange or duct. Use two field-supplied, self-drilling screws to secure the sensor probe in a horizontal orientation.

NOTE: The sensor must be mounted in the discharge airstream downstream of the cooling coil and any heating devices. Be sure the probe tip does not come in contact with any of the unit or heat surfaces.

Outdoor Air Temperature Sensor (OAT)

When the unit is supplied with a factory-mounted PremierLink control, the outdoor-air temperature sensor (OAT) is factory-supplied and wired.

Install the Indoor Air Quality (CO2) Sensor

Mount the optional indoor air quality (CO2) sensor according to manufacturer specifications.

A separate field-supplied transformer must be used to power the CO2 sensor.

Wire the CO2 sensor to the COM and IAQI terminals of J5 on the PremierLink controller. Refer to the PremierLink Installation, Start-up, and Configuration Instructions for detailed wiring and configuration information.

Enthalpy Sensors and Control

The enthalpy control (HH57AC077) is supplied as a field-installed accessory to be used with the EconoMi$er2 damper control option. The outdoor air enthalpy sensor is part of the enthalpy control. The separate field-installed accessory return air enthalpy sensor (HH57AC078) is required for differential enthalpy control.

NOTE: The enthalpy control must be set to the “D” setting for differential enthalpy control to work properly.

The enthalpy control receives the indoor and return enthalpy from the outdoor and return air enthalpy sensors and provides a dry contact switch input to the PremierLink controller. Locate the controller in place of an existing economizer controller or near the actuator. The mounting plate may not be needed if existing bracket is used.

A closed contact indicates that outside air is preferred to the return air. An open contact indicates that the economizer should remain at minimum position.

Outdoor Air Enthalphy Sensor/Enthalpy Controller (HH57AC077)

To wire the outdoor air enthalpy sensor, perform the following (See Fig. 25 and 26):

NOTE: The outdoor air sensor can be removed from the back of the enthalpy controller and mounted remotely.

50HE,HJ

31

Image 31
Contents Installation Instructions Alternate Unit Support Provide Unit Support Roof CurbRoof Curb Details Unit Leveling Tolerances Positioning50HJ 50HE50HJ004-007 Base Unit Dimensions 50HE003-006 Base Unit Dimensions Make Electrical Connections Field Power SupplyHeat Anticipator Settings Field Control WiringHi-Static Physical Data 50HJBase Unit 50HE Physical Data 50HEPower Wiring Connections Electrical Data-50HE None YES B00 PH---HzMin Max Actual kW006 008,009 23.4 30.1 40.8 KW† Electrical Data-50HJ006 11.8 414 508 007 10.6 16.0 008 13.8 20.0 Ton 004+005 19.9 24.3 55.2 76.3 86.9 168 34.9 173 002 13.6 007 A00 or008 Humi 009 18.4 111 518 632 018 17.0 16.4 23.9 10 ton 01218.7 133 518 632 17.0 16.4 24.6 019 34.0 32.7 45.0 014 A00 or Actual kW12.5 Manual Outdoor Damper Disconnect SwitchAssembly Humidi-MizerAdaptive Dehumidification SystemTypical Humidi-MiZer t Adaptive Dehumidification System Enthalpy Sensors and Control Install the Supply Air Temperature SAT SensorOutdoor Air Temperature Sensor OAT Install the Indoor Air Quality CO2 SensorNot Used PremierLinkSensor UsageRequired Or EquivalentPremierLinktController Installed EconoMi$er IV Component Locations Return Air Enthalphy SensorHood Box Removal Economi$er IV Control Modes Supply Air Temperature SAT SensorSupply Air Sensor Temperature Resistance Values Outdoor Air Lockout SensorEconoMi$er IV Wiring Differential Enthalphy Control Exhaust Set Point AdjustmentIndoor Air Quality IAQ Sensor Input Thermostats Minimum Position ControlDamper Movement + TR Dehumidification of Fresh Air with DCV Control Adjust Evaporator-Fan SpeedBelt Drive Motors Belt Drive Motor Mounting CO2Sensor Standard SettingsEvaporator-Fan Motor Data High-Static Motors Evaporator-Fan Motor Data Standard MotorExternal Static Pressure in. wg Evaporator-Fan Motor Efficiency600 900 1200 1400 1600 1800 2000 2200 2400 2600 003,004,005 006 74/84 007903 Rpm Bhp Watts 900 566 142 690 228879 957 522 1000 598 173 718 267875 551 962 689 Rpm Bhp Watts 1200 666 252 778 361 873 476 956 5941300 701 809 418 902 540 983 665 1400 737 355 842 481 932 6101800 905 551 1001 687 Rpm Bhp Watts 1500 790 353 897 471 991 6001600 828 412 931 536 1022 670 1700 866 478 966 6081463 1766 1520 1964 1800 1462 20671472 1761 1600 1495 1858 17002500 1185 1311 1262 1490 2200 1063 929 1147 1089 1224 1256 1295 14312300 1104 1046 1185 1212 1260 1386 2400 1145 1174 1223 1346 1296 15262100 1024 823 1115 997 Rpm Bhp Watts 1800 907 558 1006 708 1092 8601900 945 638 1042 796 2000 984 727 1078 8922400 1143 1168 1227 1367 2100 1024 823 1115 997 1195 1173 1268 13502200 1063 929 1152 1111 1230 1294 2300 1103 1044 1189 1234 1266 1425919 Rpm Bhp Watts 900 554 134 6811000 583 163 707 1100 612 195 7351500 738 379 Rpm Bhp Watts 1200 643 233 762 3441300 674 276 1400 706 3241700 790 398 894 514 988 643 Rpm Bhp Watts 1500 724 295 837 402 937 524 1028 6601600 757 343 866 455 962 580 7191508 1957 1900 External Sttic Pressure in. wg1474 1797 1700 1490 1873 18001600 1208 1033 1279 2400 1033 970 1115 1120 1192 1279 1264 14482500 1069 1084 1149 1239 1223 1403 1293 1576 Rpm Bhp Watts 1500 1188 970 1261 11432700 1132 1294 1214 1487 1289 1684 2400 1026 945 1115 1118 1195 1295 1268 14762500 1061 1053 1148 1233 1226 1416 1297 1604 2600 1097 1169 1181 1356 1257 1546Return-Air Filters Internal WiringRefrigerant Service Ports Unit PreparationOperating Sequence Cooling Units Without Economizer Safety ReliefHeating Ventilation Continuous FanRoutine 3 OAT DX Cooling Temperature Control ExampleHumidi-MiZer Normal Design Cooling Operation Subcooling ModeOne-Row Coil CleaningEvaporator Coil Condenser CoilCondensate Drain Evaporator Fan Belt AdjustmentCondenser-Fan Adjustment Fan Motor BearingsLow Charge Cooling Cooling Charging Chart Standard 50HJ005Cooling Charging Chart Standard 50HJ007 50HE,HJ C06145 DCV Demand Controlled Ventilation and Power Exhaust Replacement PartsUnit Troubleshooting Economi$er IV TroubleshootingDCV Minimum and Maximum Position Economi$er IV Troubleshooting CompletionSupply-Air Input Cooling Service Analysis EconoMi$er IV Input/Output Logic Subcooling Mode Liquid ReheatEconoMi$er IV Functional View START-UP Checklist