Carrier 50HE003-006 Rpm Bhp Watts 1800 907 558 1006 708 1092 860, 1900 945 638 1042 796, 2700

Page 50

50HE,HJ

Table 23—Fan Performance 50HJ007 — Vertical Discharge Units; Standard Motor (Belt Drive)*

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

 

0.8

 

 

1.0

 

CFM

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1800

907

0.63

558

1006

0.80

708

1092

0.97

860

 

1169

1.14

1015

1239

1.32

1174

1900

945

0.72

638

1042

0.90

796

1126

1.08

956

 

1201

1.26

1119

1271

1.45

1285

2000

984

0.82

727

1078

1.00

892

1160

1.19

1060

 

1235

1.39

1230

1303

1.58

1403

2100

1024

0.93

823

1115

1.12

997

1195

1.32

1173

 

1268

1.52

1350

1335

1.72

1531

2200

1063

1.05

929

1152

1.25

1111

1230

1.46

1294

 

1302

1.67

1480

1368

1.88

1668

2300

1103

1.18

1044

1189

1.39

1234

1266

1.60

1425

 

1337

1.82

1618

1402

2.04

1814

2400

1143

1.32

1168

1227

1.54

1367

1302

1.76

1566

 

1371

1.99

1767

1435

2.22

1970

2500

1183

1.47

1303

1265

1.70

1510

1339

1.93

1717

 

1406

2.17

1926

2600

1224

1.63

1448

1303

1.87

1663

1375

2.12

1878

 

1442

2.36

2095

2700

1264

1.81

1604

1342

2.06

1828

1412

2.31

2051

 

2800

1305

1.99

1772

1381

2.26

2003

 

2900

1346

2.20

1951

 

3000

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

CFM

 

1.2

 

 

1.4

 

 

1.6

 

 

 

1.8

 

 

2.0

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1800

1304

1.51

1337

1365

1.69

1503

1422

1.88

1674

 

1477

2.08

1848

1528

2.28

2025

1900

1335

1.64

1454

1395

1.83

1627

1452

2.03

1804

 

1506

2.23

1984

2000

1366

1.78

1580

1426

1.98

1760

1482

2.19

1943

 

1535

2.40

2130

2100

1398

1.93

1715

1457

2.14

1901

1512

2.35

2091

 

2200

1430

2.09

1858

1488

2.31

2052

 

2300

1462

2.27

2012

 

2400

 

2500

 

2600

 

2700

 

2800

 

2900

 

3000

 

NOTES:

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

 

1. Bold cells indicate field-supplied drive is required.

 

 

Bhp — Brake Horsepower

 

 

 

 

2. Maximum continuous bhp is 2.40.

 

 

 

 

Watts — Input Watts to Motor

 

 

 

 

3. See general fan performance notes.

 

 

 

 

*Motor drive range: 1120 to 1585 rpm. All other rpms require field-supplied

 

 

 

 

 

 

 

 

drive.

 

 

 

 

 

 

50

Image 50
Contents Installation Instructions Provide Unit Support Roof Curb Alternate Unit SupportRoof Curb Details Positioning Unit Leveling Tolerances50HE 50HJ50HJ004-007 Base Unit Dimensions 50HE003-006 Base Unit Dimensions Field Control Wiring Field Power SupplyHeat Anticipator Settings Make Electrical ConnectionsPhysical Data 50HJ Hi-StaticPhysical Data 50HE Base Unit 50HEPower Wiring Connections Electrical Data-50HE None YES Actual kW PH---HzMin Max B00006 008,009 23.4 30.1 40.8 Electrical Data-50HJ KW†006 11.8 414 508 007 10.6 16.0 008 13.8 20.0 Ton 004+005 19.9 24.3 55.2 76.3 86.9 168 34.9 173 002 13.6 A00 or 007008 Humi 009 18.4 111 518 632 018 17.0 16.4 23.9 012 10 ton18.7 133 518 632 17.0 16.4 24.6 019 34.0 32.7 45.0 12.5 A00 or Actual kW014 Humidi-MizerAdaptive Dehumidification System Disconnect SwitchAssembly Manual Outdoor DamperTypical Humidi-MiZer t Adaptive Dehumidification System Install the Indoor Air Quality CO2 Sensor Install the Supply Air Temperature SAT SensorOutdoor Air Temperature Sensor OAT Enthalpy Sensors and ControlOr Equivalent PremierLinkSensor UsageRequired Not UsedPremierLinktController Installed Return Air Enthalphy Sensor EconoMi$er IV Component LocationsHood Box Removal Outdoor Air Lockout Sensor Supply Air Temperature SAT SensorSupply Air Sensor Temperature Resistance Values Economi$er IV Control ModesEconoMi$er IV Wiring Indoor Air Quality IAQ Sensor Input Exhaust Set Point AdjustmentDifferential Enthalphy Control Damper Movement Minimum Position ControlThermostats + TR Belt Drive Motors Adjust Evaporator-Fan SpeedDehumidification of Fresh Air with DCV Control CO2Sensor Standard Settings Belt Drive Motor MountingEvaporator-Fan Motor Data Standard Motor Evaporator-Fan Motor Data High-Static Motors003,004,005 006 74/84 007 Evaporator-Fan Motor Efficiency600 900 1200 1400 1600 1800 2000 2200 2400 2600 External Static Pressure in. wg957 522 1000 598 173 718 267 Rpm Bhp Watts 900 566 142 690 228879 9031400 737 355 842 481 932 610 Rpm Bhp Watts 1200 666 252 778 361 873 476 956 5941300 701 809 418 902 540 983 665 875 551 962 6891700 866 478 966 608 Rpm Bhp Watts 1500 790 353 897 471 991 6001600 828 412 931 536 1022 670 1800 905 551 1001 6871495 1858 1700 1462 20671472 1761 1600 1463 1766 1520 1964 18002400 1145 1174 1223 1346 1296 1526 2200 1063 929 1147 1089 1224 1256 1295 14312300 1104 1046 1185 1212 1260 1386 2500 1185 1311 1262 14902000 984 727 1078 892 Rpm Bhp Watts 1800 907 558 1006 708 1092 8601900 945 638 1042 796 2100 1024 823 1115 9972300 1103 1044 1189 1234 1266 1425 2100 1024 823 1115 997 1195 1173 1268 13502200 1063 929 1152 1111 1230 1294 2400 1143 1168 1227 13671100 612 195 735 Rpm Bhp Watts 900 554 134 6811000 583 163 707 9191400 706 324 Rpm Bhp Watts 1200 643 233 762 3441300 674 276 1500 738 379719 Rpm Bhp Watts 1500 724 295 837 402 937 524 1028 6601600 757 343 866 455 962 580 1700 790 398 894 514 988 6431490 1873 1800 External Sttic Pressure in. wg1474 1797 1700 1508 1957 1900Rpm Bhp Watts 1500 1188 970 1261 1143 2400 1033 970 1115 1120 1192 1279 1264 14482500 1069 1084 1149 1239 1223 1403 1293 1576 1600 1208 1033 12792600 1097 1169 1181 1356 1257 1546 2400 1026 945 1115 1118 1195 1295 1268 14762500 1061 1053 1148 1233 1226 1416 1297 1604 2700 1132 1294 1214 1487 1289 1684Unit Preparation Internal WiringRefrigerant Service Ports Return-Air FiltersVentilation Continuous Fan Safety ReliefHeating Operating Sequence Cooling Units Without EconomizerDX Cooling Temperature Control Example Routine 3 OATSubcooling Mode Humidi-MiZer Normal Design Cooling OperationCondenser Coil CleaningEvaporator Coil One-Row CoilFan Motor Bearings Evaporator Fan Belt AdjustmentCondenser-Fan Adjustment Condensate DrainCooling Charging Chart Standard 50HJ005 Low Charge CoolingCooling Charging Chart Standard 50HJ007 50HE,HJ C06145 Economi$er IV Troubleshooting Replacement PartsUnit Troubleshooting DCV Demand Controlled Ventilation and Power ExhaustSupply-Air Input Economi$er IV Troubleshooting CompletionDCV Minimum and Maximum Position Cooling Service Analysis Subcooling Mode Liquid Reheat EconoMi$er IV Input/Output LogicEconoMi$er IV Functional View START-UP Checklist