Carrier 50HE003-006 Make Electrical Connections, Field Power Supply, Heat Anticipator Settings

Page 8

50HE,HJ

Step 5 Make Electrical Connections

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death,

Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code), ANSI/NFPA (National Fire Protection Association), latest edition, and local electrical codes. Do not use gas piping as an electrical ground.

Field Power Supply

NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gauge) insulated wire (35_C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35_C minimum). For over 75 ft, use no. 14 AWG insulated wire (35_C minimum). All wire larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.

1.Connect thermostat wires to screw terminals of lowvoltage terminal board.

2.Pass the control wires through the hole provided in the control box.

3.Some models may be equipped with a raceway built into the corner post on the left side of control box (See Fig. 13.) This raceway provides the required clearance between high-voltage and low voltage wiring. For models without a raceway, ensure to provide the NEC required clearance between high-voltage and low-voltage wiring.

Heat Anticipator Settings

Set heat anticipator settings at 0.8 amp for first stage and 0.3 for second stage heating.

All units except 208/230-v units are factory wired for the voltage shown on the nameplate. If the 208/230-v unit is to be connected to a 208-v power supply, the transformer must be rewired by disconnecting the black wire from the 230-v 1/4-in. terminal on the transformer and connecting it to the 200-v 1/4-in. terminal from the transformer.

Refer to unit label diagram for additional information. Pigtails are provided for field service. Use factory-supplied splices or UL (Underwriters’ Laboratories) approved copper connector.

When installing units, provide a disconnect per NEC.

All field wiring must comply with NEC and local requirements.

Install field wiring as follows:

COOL STAGE 1

Y1/W2

FAN

G

HEAT STAGE 1

W/W1

COOL STAGE 2

Y/Y2

HEAT STAGE 2

O/W2

24 VAC HOT

R

24 VAC COM

C

N/A

 

OUTDOOR AIR

S1

SENSOR

S2

THERMOSTAT DIPSWITCH SETTINGS

ON

OFF

A B C D

LEGEND

Field Wiring

R

 

G

 

Y1

WIRE

Y2

CONNECTIONS

W1

TO

LOW-VOLTAGE

W2

SECTION

 

C

 

IPD/X

 

 

 

1.Install conduit through side panel openings. For units without electric heat, install conduit between disconnect and control box.

2.Install power lines to terminal connections as shown in Fig. 12.

3.For units with electric heat, refer to Accessory Electric Heat Installation Instructions.

During operation, voltage to compressor terminals must bewithin range indicated on unit nameplate (also see Table 3 and 4). On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in Table 3 and 4, Note 2, to determine the percentage of voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation invalidates any applicable Carrier warranty.

NOTE: If accessory thru-the-bottom connections and roof curb are used, refer to the Thru-the-Bottom Accessory Installation Instructions for information on wiring the unit.

Field Control Wiring

Install a Carrier-approved accessory thermostat assembly according to installation instructions included with the accessory. Locate thermostat assembly on a solid wall in the conditioned space to sense average temperature in accordance with thermostat installation instructions.

Route thermostat cable or equivalent single leads of colored wire from subbase terminals through connector on unit to low-voltage connections (shown in Fig. 10 and 11).

NOTE: Underlined letter indicates active thermostat output when configured for A/C operation.

C06008

Fig. 10 ---Low-Voltage connections With or Without Economizer or Two-Position Damper

 

CONTROL

THERMOSTAT CONTROL

CONNECTION

CONNECTION

 

BOARD

 

BOARD

R

24 VAC

R

R

G

RMTOCC

Y1

Y1

 

CMPSAFE

Y2

Y2

Y2

FSD

W1

W1

W1

SFS

W2

W2

 

NOT USED

G

G

C

C

C

C

X

X

X

 

C06009

Fig. 11 ---Low-Voltage Connections (Units with PremierLinkt Controls)

8

Image 8
Contents Installation Instructions Provide Unit Support Roof Curb Alternate Unit SupportRoof Curb Details Positioning Unit Leveling Tolerances50HE 50HJ50HJ004-007 Base Unit Dimensions 50HE003-006 Base Unit Dimensions Field Power Supply Heat Anticipator SettingsField Control Wiring Make Electrical ConnectionsPhysical Data 50HJ Hi-StaticPhysical Data 50HE Base Unit 50HEPower Wiring Connections Electrical Data-50HE None YES PH---Hz Min MaxActual kW B00006 008,009 23.4 30.1 40.8 Electrical Data-50HJ KW†006 11.8 414 508 007 10.6 16.0 008 13.8 20.0 Ton 004+005 19.9 24.3 55.2 76.3 86.9 168 34.9 173 002 13.6 A00 or 007008 Humi 009 18.4 111 518 632 018 17.0 16.4 23.9 012 10 ton18.7 133 518 632 17.0 16.4 24.6 019 34.0 32.7 45.0 12.5 A00 or Actual kW014 Disconnect Switch AssemblyHumidi-MizerAdaptive Dehumidification System Manual Outdoor DamperTypical Humidi-MiZer t Adaptive Dehumidification System Install the Supply Air Temperature SAT Sensor Outdoor Air Temperature Sensor OATInstall the Indoor Air Quality CO2 Sensor Enthalpy Sensors and ControlPremierLinkSensor Usage RequiredOr Equivalent Not UsedPremierLinktController Installed Return Air Enthalphy Sensor EconoMi$er IV Component LocationsHood Box Removal Supply Air Temperature SAT Sensor Supply Air Sensor Temperature Resistance ValuesOutdoor Air Lockout Sensor Economi$er IV Control ModesEconoMi$er IV Wiring Indoor Air Quality IAQ Sensor Input Exhaust Set Point AdjustmentDifferential Enthalphy Control Damper Movement Minimum Position ControlThermostats + TR Belt Drive Motors Adjust Evaporator-Fan SpeedDehumidification of Fresh Air with DCV Control CO2Sensor Standard Settings Belt Drive Motor MountingEvaporator-Fan Motor Data Standard Motor Evaporator-Fan Motor Data High-Static MotorsEvaporator-Fan Motor Efficiency 600 900 1200 1400 1600 1800 2000 2200 2400 2600003,004,005 006 74/84 007 External Static Pressure in. wgRpm Bhp Watts 900 566 142 690 228 879957 522 1000 598 173 718 267 903Rpm Bhp Watts 1200 666 252 778 361 873 476 956 594 1300 701 809 418 902 540 983 6651400 737 355 842 481 932 610 875 551 962 689Rpm Bhp Watts 1500 790 353 897 471 991 600 1600 828 412 931 536 1022 6701700 866 478 966 608 1800 905 551 1001 6871462 2067 1472 1761 16001495 1858 1700 1463 1766 1520 1964 18002200 1063 929 1147 1089 1224 1256 1295 1431 2300 1104 1046 1185 1212 1260 13862400 1145 1174 1223 1346 1296 1526 2500 1185 1311 1262 1490Rpm Bhp Watts 1800 907 558 1006 708 1092 860 1900 945 638 1042 7962000 984 727 1078 892 2100 1024 823 1115 9972100 1024 823 1115 997 1195 1173 1268 1350 2200 1063 929 1152 1111 1230 12942300 1103 1044 1189 1234 1266 1425 2400 1143 1168 1227 1367Rpm Bhp Watts 900 554 134 681 1000 583 163 7071100 612 195 735 919Rpm Bhp Watts 1200 643 233 762 344 1300 674 2761400 706 324 1500 738 379Rpm Bhp Watts 1500 724 295 837 402 937 524 1028 660 1600 757 343 866 455 962 580719 1700 790 398 894 514 988 643External Sttic Pressure in. wg 1474 1797 17001490 1873 1800 1508 1957 19002400 1033 970 1115 1120 1192 1279 1264 1448 2500 1069 1084 1149 1239 1223 1403 1293 1576Rpm Bhp Watts 1500 1188 970 1261 1143 1600 1208 1033 12792400 1026 945 1115 1118 1195 1295 1268 1476 2500 1061 1053 1148 1233 1226 1416 1297 16042600 1097 1169 1181 1356 1257 1546 2700 1132 1294 1214 1487 1289 1684Internal Wiring Refrigerant Service PortsUnit Preparation Return-Air FiltersSafety Relief HeatingVentilation Continuous Fan Operating Sequence Cooling Units Without EconomizerDX Cooling Temperature Control Example Routine 3 OATSubcooling Mode Humidi-MiZer Normal Design Cooling OperationCleaning Evaporator CoilCondenser Coil One-Row CoilEvaporator Fan Belt Adjustment Condenser-Fan AdjustmentFan Motor Bearings Condensate DrainCooling Charging Chart Standard 50HJ005 Low Charge CoolingCooling Charging Chart Standard 50HJ007 50HE,HJ C06145 Replacement Parts Unit TroubleshootingEconomi$er IV Troubleshooting DCV Demand Controlled Ventilation and Power ExhaustSupply-Air Input Economi$er IV Troubleshooting CompletionDCV Minimum and Maximum Position Cooling Service Analysis Subcooling Mode Liquid Reheat EconoMi$er IV Input/Output LogicEconoMi$er IV Functional View START-UP Checklist