50HE,HJ
Step 5 —Make Electrical Connections
!WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death,
Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code), ANSI/NFPA (National Fire Protection Association), latest edition, and local electrical codes. Do not use gas piping as an electrical ground.
Field Power Supply
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gauge) insulated wire (35_C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35_C minimum). For over 75 ft, use no. 14 AWG insulated wire (35_C minimum). All wire larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.
1.Connect thermostat wires to screw terminals of lowvoltage terminal board.
2.Pass the control wires through the hole provided in the control box.
3.Some models may be equipped with a raceway built into the corner post on the left side of control box (See Fig. 13.) This raceway provides the required clearance between
Heat Anticipator Settings
Set heat anticipator settings at 0.8 amp for first stage and 0.3 for second stage heating.
All units except
Refer to unit label diagram for additional information. Pigtails are provided for field service. Use
When installing units, provide a disconnect per NEC.
All field wiring must comply with NEC and local requirements.
Install field wiring as follows:
COOL STAGE 1 | Y1/W2 |
FAN | G |
HEAT STAGE 1 | W/W1 |
COOL STAGE 2 | Y/Y2 |
HEAT STAGE 2 | O/W2 |
24 VAC HOT | R |
24 VAC COM | C |
N/A |
|
OUTDOOR AIR | S1 |
SENSOR | S2 |
THERMOSTAT DIPSWITCH SETTINGS
ON
OFF
A B C D
LEGEND
Field Wiring
R |
| |
G |
| |
Y1 | WIRE | |
Y2 | ||
CONNECTIONS | ||
W1 | TO | |
W2 | SECTION | |
| ||
C |
| |
IPD/X |
| |
|
|
1.Install conduit through side panel openings. For units without electric heat, install conduit between disconnect and control box.
2.Install power lines to terminal connections as shown in Fig. 12.
3.For units with electric heat, refer to Accessory Electric Heat Installation Instructions.
During operation, voltage to compressor terminals must bewithin range indicated on unit nameplate (also see Table 3 and 4). On
NOTE: If accessory
Field Control Wiring
Install a
Route thermostat cable or equivalent single leads of colored wire from subbase terminals through connector on unit to
NOTE: Underlined letter indicates active thermostat output when configured for A/C operation.
C06008
Fig. 10 --- Low-Voltage connections With or Without Economizer or Two-Position Damper
| CONTROL | THERMOSTAT CONTROL | |
CONNECTION | CONNECTION | ||
| BOARD |
| BOARD |
R | 24 VAC | R | R |
G | RMTOCC | Y1 | Y1 |
| CMPSAFE | Y2 | Y2 |
Y2 | FSD | W1 | W1 |
W1 | SFS | W2 | W2 |
| NOT USED | G | G |
C | C | C | C |
X | X | X |
|
C06009
Fig. 11 --- Low-Voltage Connections (Units with PremierLinkt Controls)
8