Bryant 697C warranty Coils ± 333B,JAV060120 VARIABLE-SPEED Furnace

Page 30

HEAT PUMP HEATING PERFORMANCE Continued

 

INDOOR

 

 

 

 

 

 

OUTDOOR COIL ENTERING AIR TEMPERATURES °F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIR

 

–3

 

 

7

 

 

17

 

 

27

 

 

37

 

 

47

 

 

57

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity

Total

Capacity

Total

Capacity

Total

Capacity

Total

Capacity

Total

Capacity

Total

Capacity

Total

 

 

 

 

(MBtuh)

Pwr

(MBtuh)

Pwr

(MBtuh)

Pwr

(MBtuh)

Pwr

(MBtuh)

Pwr

(MBtuh)

Pwr

(MBtuh)

Pwr

 

 

EDB

CFM

Total

Int*

Kw†

Total

Int*

Kw†

Total

Int*

Kw†

Total

Int*

Kw†

Total

Int*

Kw†

Total

Int*

Kw†

Total

Int*

Kw†

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

697C036-B Outdoor Section With FC4BN(F,B)042 Indoor Section

 

 

 

 

 

 

 

 

1100

16.0

14.7

2.43

19.3

17.7

2.53

22.8

20.8

2.64

26.7

23.7

2.74

31.2

28.4

2.87

36.1

36.1

3.03

41.8

41.8

3.23

 

 

65

1200

16.2

14.9

2.46

19.4

17.9

2.55

23.0

21.0

2.65

26.9

23.9

2.75

31.4

28.6

2.87

36.4

36.4

3.03

42.1

42.1

3.22

 

 

 

1300

16.4

15.1

2.48

19.7

18.1

2.58

23.2

21.1

2.66

27.1

24.1

2.76

31.6

28.7

2.88

36.6

36.6

3.03

42.4

42.4

3.22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1100

15.7

14.5

2.52

19.1

17.5

2.64

22.6

20.6

2.75

26.5

23.5

2.87

30.9

28.1

3.00

35.7

35.7

3.17

41.3

41.3

3.37

 

 

70

1200

15.9

14.6

2.55

19.2

17.7

2.66

22.8

20.8

2.76

26.7

23.7

2.87

31.1

28.3

3.00

36.0

36.0

3.16

41.6

41.6

3.36

 

 

 

1300

16.1

14.8

2.57

19.4

17.8

2.68

23.0

20.9

2.78

26.9

23.9

2.88

31.3

28.5

3.01

36.2

36.2

3.16

41.9

41.9

3.35

 

 

 

1100

15.4

14.1

2.62

18.9

17.3

2.74

22.4

20.4

2.87

26.2

23.3

2.99

30.6

27.8

3.14

35.4

35.4

3.31

40.9

40.9

3.52

 

 

75

1200

15.6

14.3

2.64

19.0

17.5

2.76

22.6

20.6

2.88

26.4

23.5

3.00

30.8

28.0

3.14

35.6

35.6

3.30

41.2

41.2

3.50

 

 

 

1300

15.7

14.5

2.67

19.2

17.6

2.78

22.7

20.7

2.89

26.6

23.6

3.01

31.0

28.2

3.14

35.9

35.9

3.30

41.5

41.5

3.50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Multipliers for Determining the Performance With Other Indoor Sections

 

Indoor

 

 

Heating

Indoor

 

 

Heating

 

 

 

 

 

 

 

 

 

 

 

 

Section

Size

Capacity

 

Power

Section

Size

Capacity

 

Power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FC4BN(F,B)

042

1.00

 

1.00

CJ5A/CK5A/CK5BW

036

0.98

 

0.95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FC4BNF

033

1.00

 

1.00

CK3BA

036

0.98

 

0.95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036

1.00

 

1.03

 

042

1.00

 

0.96

 

 

 

 

 

 

 

 

 

 

 

 

 

F(A,B)4ANF

036

1.00

 

1.03

COILS + 333(B,J)AV060100 VARIABLE-SPEED FURNACE

 

 

F(A,B)4AN(F,B)

042

1.00

 

1.00

CC5A/CD5A/CD5BA

042

0.98

 

0.95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FG3AAA

036

1.00

 

1.03

CC5A/CD5A/CD5BW

042

0.98

 

0.95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FK4BNF

001

1.00

 

1.00

CD3(A,B)A

042

0.98

 

0.95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

002

1.00

 

0.97

CC5A/CD5A/CD5BC

048

0.97

 

0.97

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

003

0.99

 

0.94

CE3AA

042

0.98

 

0.94

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

004

1.00

 

0.92

CJ5A/CK5A/CK5BA

042

0.99

 

0.94

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FK4CNF

001

0.98

 

0.99

CJ5A/CK5A/CK5BW

036

0.98

 

0.94

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

002

0.99

 

0.97

CK3BA

036

0.98

 

0.94

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

003

0.98

 

0.94

 

042

0.99

 

0.94

 

 

 

 

 

 

 

 

 

 

 

 

 

CD5A/CD5BW

036

1.00

 

1.01

COILS ± 333(B,J)AV060120 VARIABLE-SPEED FURNACE

 

 

CC5A/CD5A/CD5BA

036

1.00

 

1.01

CC5A/CD5A/CD5BA

042

0.98

 

0.96

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

042

1.00

 

1.01

CC5A/CD5A/CD5BW

042

0.98

 

0.96

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

043

1.00

 

1.01

CD3(A,B)A

042

0.98

 

0.96

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CC5A/CD5A/CD5BW

042

1.00

 

1.02

CC5A/CD5A/CD5BC

048

0.97

 

0.98

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

043

1.00

 

1.01

CE3AA

042

0.987

 

0.95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CD3(A,B)A

036

1.00

 

1.01

CJ5A/CK5A/CK5BA

042

0.99

 

0.94

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

042

1.00

 

1.01

CJ5A/CK5A/CK5BW

036

0.98

 

0.95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CE3AA

036

1.00

 

1.02

CK3BA

036

0.98

 

0.95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

042

1.00

 

0.99

 

042

0.99

 

0.94

 

 

 

 

 

 

 

 

 

 

 

 

 

CF5AA

036

1.00

 

1.01

COILS + 355MAV042040 VARIABLE-SPEED FURNACE

 

 

CJ5A/CK5A/CK5BA

036

1.00

 

1.01

CC5A/CD5A/CD5BA

042

1.00

 

0.98

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

042

1.00

 

0.99

CD3(A,B)A

042

1.00

 

0.98

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CJ5A/CK5A/CK5BN

042

1.00

 

0.99

CJ5A/CK5A/CK5BA

042

1.00

 

0.97

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CJ5A/CK5A/CK5BW

036

1.00

 

1.01

CJ5A/CK5A/CK5BW

036

1.00

 

0.98

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CK3BA

036

1.00

 

1.01

CK3BA

036

1.00

 

0.98

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

042

1.00

 

0.99

 

042

1.00

 

0.97

 

 

 

 

 

 

 

 

 

 

 

 

COILS + 333(B,J)AV036060 VARIABLE-SPEED FURNACE

COILS + 355MAV042060 VARIABLE-SPEED FURNACE

 

 

CC5A/CD5A/CD5BA

042

0.98

 

0.98

CC5A/CD5A/CD5BA

042

1.00

 

0.98

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CC5A/CD5A/CD5BW

042

0.98

 

0.98

CD3(A,B)A

042

1.00

 

0.98

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CD3(A,B)A

042

0.98

 

0.98

CJ5A/CK5A/CK5BA

036

1.00

 

0.98

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CC5A/CD5A/CD5BC

048

0.98

 

1.00

CJ5A/CK5A/CK5BN

042

1.00

 

0.97

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CE3AA

042

0.99

 

0.97

CK3BA

036

1.00

 

0.98

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CJ5A/CK5A/CK5BA

036

0.99

 

0.97

 

042

1.00

 

0.97

 

 

 

 

 

 

 

 

 

 

 

 

 

CK3BA

036

0.99

 

0.97

COILS + 355MAV042080 VARIABLE-SPEED FURNACE

 

 

COILS + 333(B,J)AV048080 VARIABLE-SPEED FURNACE

CC5A/CD5A/CD5BA

042

0.99

 

0.97

 

 

CC5A/CD5A/CD5BA

042

0.98

 

0.96

CD3(A,B)A

042

0.99

 

0.97

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CC5A/CD5A/CD5BW

042

0.98

 

0.96

CJ5A/CK5A/CK5BA

042

1.00

 

0.97

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CD3(A,B)A

042

0.98

 

0.96

CJ5A/CK5A/CK5BW

036

1.00

 

0.98

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CC5A/CD5A/CD5BC

048

0.97

 

0.98

CK3BA

036

1.00

 

0.98

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CE3AA

042

0.98

 

0.95

 

042

1.00

 

0.97

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CJ5A/CK5A/CK5BA

042

1.00

 

0.96

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

See notes on page 34.

—30—

Image 30
Contents 697C 60 HZ Dimensions Recommended Tube Diameters Specifications Specifications Accessory Usage Guideline Secondary Outdoor Thermostat Combination Ratings Combination Ratings Accessory‡ Efficiency Coils + 355MAV060120 VARIABLE-SPEED Furnace 41,000 47,500 59,000 11.20 697C Balance Point Worksheet Detailed Cooling Capacities 697C018-B Outdoor Section With FC4BNF024 Indoor SectionDetailed Cooling Capacities 697C024-B Outdoor Section With FC4BNF030 Indoor Section697C030-B Outdoor Section With FC4BNF036 Indoor Section Coils + 355MAV060120 VARIABLE-SPEED Furnace 697C036-B Outdoor Section With FC4BNF,B042 Indoor Section CJ5AS/CK5A/CK5BW 697C042-B Outdoor Section With FK4CNF005 Indoor Section Detailed Cooling Capacities Size Capacity Power 697C048-A Outdoor Section With FK4CNF005 Indoor Section697C060-A Outdoor Section With FK4CNB006 Indoor Section Heat Pump Heating Performance Heat Pump Heating Performance Coils + 355MAV0601020 VARIABLE-SPEED Furnace Coils ± 333B,JAV060120 VARIABLE-SPEED Furnace Heat Pump Heating Performance Indoor Heating Section Size Capacity Power Indoor Heating Section CK5A/CK5A/CK5BX System Design Service Training