Bryant warranty 697C060-A Outdoor Section With FK4CNB006 Indoor Section

Page 26

DETAILED COOLING CAPACITIES* Continued

 

EVAPORATOR

 

 

 

 

CONDENSER ENTERING AIR TEMPERATURES °F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIR

 

85

 

 

95

 

 

105

 

 

115

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity

Total

Capacity

Total

Capacity

Total

Capacity

Total

 

 

 

 

 

MBtuh†

MBtuh†

MBtuh†

MBtuh†

 

 

 

 

 

 

 

System

 

 

 

System

 

 

System

 

 

System

 

 

CFM

 

EWB

Total

Sens‡

Kw**

Total

 

Sens‡

Kw**

Total

Sens‡

Kw**

Total

Sens‡

Kw**

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

697C060-A Outdoor Section With FK4CNB006 Indoor Section

 

 

 

 

 

 

 

72

66.2

32.7

4.89

63.3

 

31.7

5.42

60.2

30.5

6.0

57.0

29.4

6.63

 

 

1575

 

67

61.0

41.4

4.82

58.4

 

40.3

5.35

55.5

39.2

5.9

52.5

38.0

6.54

 

 

 

63††

57.2

40.5

4.77

54.6

 

39.4

5.29

52.0

38.2

5.8

49.2

37.0

6.47

 

 

 

 

62

56.2

49.9

4.76

53.7

 

48.7

5.28

51.1

47.5

5.8

48.4

46.2

6.46

 

 

 

 

57

54.0

54.0

4.73

52.1

 

52.1

5.26

50.1

50.1

5.8

47.8

47.8

6.45

 

 

 

 

72

67.0

33.9

4.95

64.1

 

32.9

5.49

60.8

31.7

6.0

57.5

30.5

6.69

 

 

1750

 

67

61.8

43.4

4.89

59.0

 

42.3

5.41

56.1

41.2

5.9

53.0

39.9

6.61

 

 

 

63††

57.9

42.4

4.84

55.3

 

41.2

5.36

52.6

40.0

5.9

49.7

38.8

6.54

 

 

 

 

62

57.1

52.7

4.83

54.5

 

51.5

5.35

51.9

50.1

5.9

49.2

48.7

6.53

 

 

 

 

57

55.7

55.7

4.81

53.6

 

53.6

5.34

51.4

51.4

5.9

49.0

49.0

6.53

 

 

 

 

72

67.8

35.6

5.05

64.7

 

34.5

5.58

61.5

33.3

6.1

58.0

32.2

6.79

 

 

2012

 

67

63.1

46.5

4.99

60.2

 

45.4

5.52

56.8

44.0

6.0

53.6

42.8

6.70

 

 

 

63††

58.8

45.1

4.93

56.1

 

43.9

5.45

53.3

42.7

6.0

50.2

41.5

6.64

 

 

 

 

62

58.5

56.7

4.93

55.6

 

55.1

5.45

53.1

53.1

6.0

50.6

50.6

6.65

 

 

 

 

57

57.7

57.7

4.92

55.5

 

55.5

5.45

53.2

53.2

6.0

50.7

50.7

6.65

 

Multipliers for Determining the Performance With Other Indoor Sections

 

Indoor

 

 

Cooling

Indoor

 

 

Cooling

 

 

 

 

 

 

 

 

 

 

 

 

Section

Size

Capacity

 

Power

Section

Size

Capacity

 

Power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F(A,B)4AN(F,B,C)

060

0.97

 

1.06

CD3(A,B)A

060

0.94

 

1.01

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FB4ANB

070

0.99

 

1.04

CE3AA

060

0.97

 

1.01

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FC4BN(F,B)

060

0.97

 

1.06

CJ5A/CK5A/CK5BA

060

0.97

 

1.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FC4BNB

070

0.99

 

1.04

CJ5A/CK5A/CK5BX

060

0.99

 

0.99

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FG3AAA

060

0.96

 

1.02

CK3BA

060

0.97

 

1.00

 

 

 

 

 

 

 

 

 

 

 

 

 

FK4BNB

006

1.00

 

1.01

COILS + 333(B,J)AV060120 VARIABLE-SPEED FURNACE

 

 

FK4CNB

006

1.00

 

1.00

CC5A/CD5A/CD5BA

060

0.93

 

1.02

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CC5A/CD5A/CD5BA

060

0.94

 

1.02

CC5A/CD5A/CD5BW

060

0.96

 

1.01

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CC5A/CD5A/CD5BW

060

0.96

 

1.02

CD3(A,B)A

060

0.93

 

1.02

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CD3(A,B)A

060

0.94

 

1.02

CE3AA

060

0.97

 

1.02

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CE3AA

060

0.97

 

1.03

CJ5A/CK5A/CK5BA

060

0.97

 

1.01

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CJ5A/CK5A/CK5BA

060

0.97

 

1.02

CJ5A/CK5A/CK5BX

060

0.98

 

1.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CJ5A/CK5A/CK5BN

060

0.97

 

1.02

CK3BA

060

0.97

 

1.01

 

 

 

 

 

 

 

 

 

 

 

 

 

CJ5A/CK5A/CK5BX

060

0.98

 

1.02

COILS + 355MAV060100 VARIABLE-SPEED FURNACE

 

 

CK3BA

060

0.97

 

1.02

CC5A/CD5A/CD5BA

060

0.93

 

1.04

 

 

 

 

 

 

 

 

 

 

 

 

 

COILS + 333(B,J)AV060100 VARIABLE-SPEED FURNACE

CC5A/CD5A/CD5BW

060

0.96

 

1.04

 

 

CC5A/CD5A/CD5BA

060

0.94

 

1.01

CD3(A,B)A

060

0.93

 

1.04

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CC5A/CD5A/CD5BW

060

0.97

 

1.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240-89. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

Total and sensible capacities are net capacities. Blower motor heat has been subtracted.

Sensible capacities shown are based on 80 °F (27°C) entering air at the indoor coil. For sensible capacities at other than 80°F (27°C), deduct 835 Btuh (245 kw) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80°F (27°C), or add 835 Btuh (245 kw) per 1000 CFM (480 L/S) of indoor coil air per degree above 80°F (27°C).

**System kw is total of indoor and outdoor unit kilowatts.

††At TVA rating indoor condition (75 °F edb/63°F ewb). All other indoor air temperatures are at 80°F edb. EWB—Entering Wet Bulb

—26—

Image 26
Contents 697C 60 HZ Dimensions Recommended Tube Diameters Specifications Specifications Accessory Usage Guideline Secondary Outdoor Thermostat Combination Ratings Combination Ratings Accessory‡ Efficiency Coils + 355MAV060120 VARIABLE-SPEED Furnace 41,000 47,500 59,000 11.20 697C Balance Point Worksheet Detailed Cooling Capacities 697C018-B Outdoor Section With FC4BNF024 Indoor SectionDetailed Cooling Capacities 697C024-B Outdoor Section With FC4BNF030 Indoor Section697C030-B Outdoor Section With FC4BNF036 Indoor Section Coils + 355MAV060120 VARIABLE-SPEED Furnace 697C036-B Outdoor Section With FC4BNF,B042 Indoor Section CJ5AS/CK5A/CK5BW 697C042-B Outdoor Section With FK4CNF005 Indoor Section Detailed Cooling Capacities Size Capacity Power 697C048-A Outdoor Section With FK4CNF005 Indoor Section697C060-A Outdoor Section With FK4CNB006 Indoor Section Heat Pump Heating Performance Heat Pump Heating Performance Coils + 355MAV0601020 VARIABLE-SPEED Furnace Coils ± 333B,JAV060120 VARIABLE-SPEED Furnace Heat Pump Heating Performance Indoor Heating Section Size Capacity Power Indoor Heating Section CK5A/CK5A/CK5BX System Design Service Training