DETAILED COOLING CAPACITIES* Continued
| EVAPORATOR |
|
|
|
| CONDENSER ENTERING AIR TEMPERATURES °F |
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
| AIR |
| 85 |
|
| 95 |
|
| 105 |
|
| 115 |
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
| Capacity | Total | Capacity | Total | Capacity | Total | Capacity | Total |
| |||||
|
|
|
| MBtuh† | MBtuh† | MBtuh† | MBtuh† |
| |||||||||
|
|
|
|
|
| System |
|
|
| System |
|
| System |
|
| System |
|
| CFM |
| EWB | Total | Sens‡ | Kw** | Total |
| Sens‡ | Kw** | Total | Sens‡ | Kw** | Total | Sens‡ | Kw** |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| ||||||||
|
|
| 72 | 66.2 | 32.7 | 4.89 | 63.3 |
| 31.7 | 5.42 | 60.2 | 30.5 | 6.0 | 57.0 | 29.4 | 6.63 |
|
| 1575 |
| 67 | 61.0 | 41.4 | 4.82 | 58.4 |
| 40.3 | 5.35 | 55.5 | 39.2 | 5.9 | 52.5 | 38.0 | 6.54 |
|
|
| 63†† | 57.2 | 40.5 | 4.77 | 54.6 |
| 39.4 | 5.29 | 52.0 | 38.2 | 5.8 | 49.2 | 37.0 | 6.47 |
| |
|
|
| 62 | 56.2 | 49.9 | 4.76 | 53.7 |
| 48.7 | 5.28 | 51.1 | 47.5 | 5.8 | 48.4 | 46.2 | 6.46 |
|
|
|
| 57 | 54.0 | 54.0 | 4.73 | 52.1 |
| 52.1 | 5.26 | 50.1 | 50.1 | 5.8 | 47.8 | 47.8 | 6.45 |
|
|
|
| 72 | 67.0 | 33.9 | 4.95 | 64.1 |
| 32.9 | 5.49 | 60.8 | 31.7 | 6.0 | 57.5 | 30.5 | 6.69 |
|
| 1750 |
| 67 | 61.8 | 43.4 | 4.89 | 59.0 |
| 42.3 | 5.41 | 56.1 | 41.2 | 5.9 | 53.0 | 39.9 | 6.61 |
|
|
| 63†† | 57.9 | 42.4 | 4.84 | 55.3 |
| 41.2 | 5.36 | 52.6 | 40.0 | 5.9 | 49.7 | 38.8 | 6.54 |
| |
|
|
| 62 | 57.1 | 52.7 | 4.83 | 54.5 |
| 51.5 | 5.35 | 51.9 | 50.1 | 5.9 | 49.2 | 48.7 | 6.53 |
|
|
|
| 57 | 55.7 | 55.7 | 4.81 | 53.6 |
| 53.6 | 5.34 | 51.4 | 51.4 | 5.9 | 49.0 | 49.0 | 6.53 |
|
|
|
| 72 | 67.8 | 35.6 | 5.05 | 64.7 |
| 34.5 | 5.58 | 61.5 | 33.3 | 6.1 | 58.0 | 32.2 | 6.79 |
|
| 2012 |
| 67 | 63.1 | 46.5 | 4.99 | 60.2 |
| 45.4 | 5.52 | 56.8 | 44.0 | 6.0 | 53.6 | 42.8 | 6.70 |
|
|
| 63†† | 58.8 | 45.1 | 4.93 | 56.1 |
| 43.9 | 5.45 | 53.3 | 42.7 | 6.0 | 50.2 | 41.5 | 6.64 |
| |
|
|
| 62 | 58.5 | 56.7 | 4.93 | 55.6 |
| 55.1 | 5.45 | 53.1 | 53.1 | 6.0 | 50.6 | 50.6 | 6.65 |
|
|
|
| 57 | 57.7 | 57.7 | 4.92 | 55.5 |
| 55.5 | 5.45 | 53.2 | 53.2 | 6.0 | 50.7 | 50.7 | 6.65 |
|
Multipliers for Determining the Performance With Other Indoor Sections
| Indoor |
|
| Cooling | Indoor |
|
| Cooling |
| ||
|
|
|
|
|
|
|
|
|
| ||
| Section | Size | Capacity |
| Power | Section | Size | Capacity |
| Power |
|
|
|
|
|
|
|
|
|
|
|
|
|
| F(A,B)4AN(F,B,C) | 060 | 0.97 |
| 1.06 | CD3(A,B)A | 060 | 0.94 |
| 1.01 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| FB4ANB | 070 | 0.99 |
| 1.04 | CE3AA | 060 | 0.97 |
| 1.01 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| FC4BN(F,B) | 060 | 0.97 |
| 1.06 | CJ5A/CK5A/CK5BA | 060 | 0.97 |
| 1.00 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| FC4BNB | 070 | 0.99 |
| 1.04 | CJ5A/CK5A/CK5BX | 060 | 0.99 |
| 0.99 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| FG3AAA | 060 | 0.96 |
| 1.02 | CK3BA | 060 | 0.97 |
| 1.00 |
|
|
|
|
|
|
|
|
|
|
|
| |
| FK4BNB | 006 | 1.00 |
| 1.01 | COILS + 333(B,J)AV060120 |
| ||||
| FK4CNB | 006 | 1.00 |
| 1.00 | CC5A/CD5A/CD5BA | 060 | 0.93 |
| 1.02 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| CC5A/CD5A/CD5BA | 060 | 0.94 |
| 1.02 | CC5A/CD5A/CD5BW | 060 | 0.96 |
| 1.01 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| CC5A/CD5A/CD5BW | 060 | 0.96 |
| 1.02 | CD3(A,B)A | 060 | 0.93 |
| 1.02 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| CD3(A,B)A | 060 | 0.94 |
| 1.02 | CE3AA | 060 | 0.97 |
| 1.02 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| CE3AA | 060 | 0.97 |
| 1.03 | CJ5A/CK5A/CK5BA | 060 | 0.97 |
| 1.01 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| CJ5A/CK5A/CK5BA | 060 | 0.97 |
| 1.02 | CJ5A/CK5A/CK5BX | 060 | 0.98 |
| 1.00 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| CJ5A/CK5A/CK5BN | 060 | 0.97 |
| 1.02 | CK3BA | 060 | 0.97 |
| 1.01 |
|
|
|
|
|
|
|
|
|
|
|
| |
| CJ5A/CK5A/CK5BX | 060 | 0.98 |
| 1.02 | COILS + 355MAV060100 |
| ||||
| CK3BA | 060 | 0.97 |
| 1.02 | CC5A/CD5A/CD5BA | 060 | 0.93 |
| 1.04 |
|
|
|
|
|
|
|
|
|
|
|
| |
| COILS + 333(B,J)AV060100 | CC5A/CD5A/CD5BW | 060 | 0.96 |
| 1.04 |
| ||||
| CC5A/CD5A/CD5BA | 060 | 0.94 |
| 1.01 | CD3(A,B)A | 060 | 0.93 |
| 1.04 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| CC5A/CD5A/CD5BW | 060 | 0.97 |
| 1.00 |
| — | — |
| — |
|
|
|
|
|
|
|
|
|
|
|
|
|
*Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard
†Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
‡Sensible capacities shown are based on 80 °F (27°C) entering air at the indoor coil. For sensible capacities at other than 80°F (27°C), deduct 835 Btuh (245 kw) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80°F (27°C), or add 835 Btuh (245 kw) per 1000 CFM (480 L/S) of indoor coil air per degree above 80°F (27°C).
**System kw is total of indoor and outdoor unit kilowatts.
††At TVA rating indoor condition (75 °F edb/63°F ewb). All other indoor air temperatures are at 80°F edb.