Bryant 697C warranty System Design

Page 35

System Design

1.Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc.

2.Minimum outdoor operating air temperature for cooling mode without low-ambient operation accessory is 55°F (12.8°C).

3.Maximum outdoor operating air temperature for cooling mode is 125°F (51.7°C).

4.Minimum outdoor operating air temperature for heating mode is –30°F (–34.4°C).

5.Maximum outdoor operating air temperature for heating mode is 66°F (18.9°C).

6.For reliable operation, unit should be level in all horizontal planes.

7.Maximum elevation of indoor coil above or below base of outdoor unit is: indoor coil above = 50 ft, indoor coil below =150 ft. (See items 8 and 9 following).

8.For interconnecting refrigerant tube lengths greater than 50 ft, consult Long-Line Application Guideline available from equipment distributor.

9.Not more than 36 in. of refrigerant tube should be buried in the ground. If necessary to bury tubes under a sidewalk, provide a minimum 6-in. vertical rise to the valve connections at the unit.

10.Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.

11.Mixmatches of indoor coil capacity more than 1 size larger than outdoor unit capacity may result in inadequate indoor comfort.

—35—

Image 35
Contents 697C 60 HZ Dimensions Recommended Tube Diameters Specifications Specifications Accessory Usage Guideline Secondary Outdoor Thermostat Combination Ratings Combination Ratings Accessory‡ Efficiency Coils + 355MAV060120 VARIABLE-SPEED Furnace 41,000 47,500 59,000 11.20 697C Balance Point Worksheet 697C018-B Outdoor Section With FC4BNF024 Indoor Section Detailed Cooling Capacities697C024-B Outdoor Section With FC4BNF030 Indoor Section Detailed Cooling Capacities697C030-B Outdoor Section With FC4BNF036 Indoor Section Coils + 355MAV060120 VARIABLE-SPEED Furnace 697C036-B Outdoor Section With FC4BNF,B042 Indoor Section CJ5AS/CK5A/CK5BW 697C042-B Outdoor Section With FK4CNF005 Indoor Section Detailed Cooling Capacities 697C048-A Outdoor Section With FK4CNF005 Indoor Section Size Capacity Power697C060-A Outdoor Section With FK4CNB006 Indoor Section Heat Pump Heating Performance Heat Pump Heating Performance Coils + 355MAV0601020 VARIABLE-SPEED Furnace Coils ± 333B,JAV060120 VARIABLE-SPEED Furnace Heat Pump Heating Performance Indoor Heating Section Size Capacity Power Indoor Heating Section CK5A/CK5A/CK5BX System Design Service Training