Schneider Electric Class 615 Trip Units for Compact NSJ400 and NSJ600 Circuit Breakers, STR53UP

Page 11

Compact® NSF and NSJ 150 to 600 A Circuit Breakers

Section 4—Trip Units

TRIP UNITS FOR COMPACT® NSJ400 AND NSJ600 CIRCUIT BREAKERS

Compact NSJ400 and NSJ600 circuit breakers are equipped with current sensors and electronic trip units.

Current Sensors Four different sizes are available and can be mounted with all trip units:

NSJ400—150, 250 and 400 A

NSJ600—600 A

Trip Units

Protection for loads, from 60 to 600 A

STR23SP,

— STR23SP and STR53UP for standard protection

STR53UP and

STR23SP-OSN for oversized neutral protection (factory-installed only)

STR23SP-OSN

STR53UP for generator supplied network protection and long cable runs

 

Trip units STR23SP and STR53UP can be mounted on all Compact NSJ400 and NSJ600 circuit

 

breaker types N, H and L

 

Trip unit STR53UP offers a greater number of optional indication and measurement functions,

 

protection settings and ground-fault protection

 

STR23SP and STR53UP available on four-pole circuit breakers with sealable, 3-position neutral

 

protection setting:

 

4P 3D (neutral unprotected)

— 4P 3D + N/2 (neutral protection at 0.5 x Ir) where Ir is trip unit current setting

— 4P 4D (neutral protection at Ir) where Ir is trip unit current setting

Trip Units for Compact® NSJ400 and NSJ600

STR23SP

STR53UP

 

 

 

 

STR23SP OSN

 

Circuit Breakers

 

 

 

 

 

(Oversized Neutral)

 

 

 

 

 

 

 

 

Overload Protection (Long Time)

 

 

 

 

 

 

 

 

 

 

 

Tripping

Ir

20–70° C

Adjustable (48 Settings) 0.4–1 x In

 

 

 

 

 

 

 

Threshold (A)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fixed

Adjustable

 

 

 

 

Fixed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Tripping Time (s)

At 1.5 x Ir

120–180

17–25

 

34–50

69–100

138–200

277–400

120–180

 

(Min–Max)

 

 

At 6 x Ir

5–7.5

0.8–1

 

1.6–2

3.2–4

6.4–8

12.8–16

5–7.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

At 7.2 x Ir

3.2–5.0

0.5–0.7

 

1.1–1.4

2.2–2.8

4.4–5.5

8.8–11

3.2–5.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Short-circuit Protection (Short Time)

 

 

 

 

 

 

 

 

 

 

 

 

 

Im / Isd

 

Adjustable (7 Settings)

Adjustable (7 Settings) 1.5–7 x Ir

 

 

Adjustable (7 Settings) 2–9 x Ir

Tripping

 

2–9 x Ir

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Accuracy

 

± 15%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max. Overcurrent Time Before Tripping

Fixed 40

Adjustable (4 Settings + Constant I2t Function)

 

Fixed 40

 

Time Delay

15

60

140

230

 

 

 

 

 

 

 

 

 

 

(ms)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total Breaking Time

 

60

60

140

230

350

 

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Short-circuit Protection (Instantaneous)

 

 

 

 

 

 

 

 

 

 

Tripping Threshold (A)

 

Fixed 9 x In

Adjustable (7 Settings) 1.5–9 x In

 

 

Fixed 9 x In

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Adjustable Neutral Protection (Three Position Switch)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NSJ250/400N

 

NSJ400/600N

 

 

 

Switch

Settings

Protection Level

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Position 1

4P 3D

No Protection

No Protection

 

 

 

No Protection

 

No Protection

 

 

 

Position 2

4P 3D + N/2

0.5 x Ir

0.5 x Ir

 

 

 

 

0.8 x Ir

 

0.75 x Ir

 

 

 

Position 3

4P 4D

1.0 x Ir

1.0 x Ir

 

 

 

 

1.6 x Ir

 

1.5 x Ir

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Other Functions

 

 

 

 

 

 

 

 

 

 

 

Indication of Fault Type

 

 

(Standard)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Equipment Ground-fault Protection (T)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Built-in Ammeter (I)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Zone-selective Interlocking (ZSI)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Communication (COM)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

© 1995–2003 Schneider Electric All Rights Reserved

11

Image 11
Contents Compact NSF and NSJ Page Table of Contents Interrupting Rating at 480 Compact Circuit Breaker LineRated Current a CompactCompliance with Standards General CharacteristicsInstallation Class Switchboards Life of Electrical Installations Longer Service IEC 947-2 and EN 60947-2 Ratings Circuit Breakers Ratings and Interrupting Ratings UL 489 Listed RatingsKA rms Compact Circuit Breakers NSJ400 NSJ600 Rated VoltageUltimate Breaking Capacity Icu Against overload 1 with a fixed thermal protection Trip UnitsTrip Units for Compact NSF150 and NSF250 Circuit Breakers ProtectionSTR53UP Trip Units for Compact NSJ400 and NSJ600 Circuit BreakersTrip Units Protection Indications Unit or other accessoriesSetting Example With trip unit STR23SP where Io = 0.5 and Ir = 0.8?Self-monitoring Overload Indications %Ir Fault IndicationsElectronic Trip Unit STR53UP ProtectionElectronic Trip Options forPortable Test Kit Full-function Electronic Trip Unit Test KitsMini Test Kit and Hand-held Test Kit NSF150A NSF250A SwitchesUL 1087 Listed Ratings IEC 947-3 RatingsNSJ400A NSJ600A Short-circuit Withstand CurrentNSF150HC NSF250HC Motor Circuit ProtectorsUL 489 Recognized Component NSJ400HC NSJ600HC PLUG-IN Mounting Mounting ConfigurationsFixed Mounting ConnectionsHorizontally or vertically Parts of a Plug-in ConfigurationDrawout Mounting MountingConnection of Auxiliaries AccessoriesCopper or Aluminum Cable ConnectionsFront Connection Connection to CablesCompact Circuit Breake r NSF150/250 NSJ400/600 Rear ConnectionConnection to Bars Plug-in Mounting DrawoutPlug-in and Drawout Mounting AccessoriesLocation Automatic Secondary Disconnecting Blocks Auxiliary and Alarm Switches IEC 947 Ratings Electrical RatingsUL 489 and CSA C22.2 No .1 Ratings Operation Shunt Trip and Undervoltage TripUndervoltage trip Shunt trip MXManual Operation Motor OperatorApplications AutomaticKeylock for locking in OFF position Accessories forCharacteristics NSJ400/600Directly Mounted Rotary Operating HandlesDoor Mounted Operating Cable Operating HandleFlange-mounted Handle CableLocking In the Off Position Locking SystemsWith Rotary Handles Interlocking AccessoriesInterlocking of Circuit Breakers with Toggle Control Interlocking of Circuit BreakersUse Front-panel Escutcheons for Toggle Toggle BootFRONT-PANEL Escutcheons For Fixed or Plug- in MountingToggle Collars Sealing AccessoryFor Drawout Mounting IdentificationMounting on Backplate DimensionsDimensions Fixed MountedR12 R13 Front-panel Cutouts With Toggle Boot With EscutcheonC20 C21 H53 H54Drawout On Chassis Dimensions Plug-in On BasePLUG-IN and Drawout Mounting Front-panel Cutouts Plug-in Mounting See Fixed-mounted InstallationMounting Through a Backplate Plug-in Base On Rails Plug-in Base or ChassisL10 P12 P44 C11 C17 G10 G11 G12 G13 G20 G21 H16 H17 H18 H19K11 K12 K13 K20 K21 C22 C23 H20 H21 H22 H23 L11 L12 P32 P33 P45 R14 Dimension TableMotor Operators Front-panel CutoutsCompact NSJ CABLE-OPERATING HandlesCompact NSF ROTARY-OPERATING Handles DimensionsFront-panel Cutout Drawout Mounting ØT6 ØT7 C11 C17 C22 C23 G36 G37 G38 G39 H10 H20 H23 H24 H25H26 K14 K15 L11 L12 L13 L14 L15 P34 P35 P36 P37 P38 P40 P42 P43 P44 R14 R15Front-panel Escutcheons Front AccessoriesExtended Escutcheons For Toggle L16 L17 R19 Interlocking SystemsConnection Dimensions G33 G35 P22 P23 Plug-in or Drawout MountingMotor-operated Circuit Breaker Wiring DiagramsManually-operated Circuit Breaker OFF Trip Units for Compact NSF150-NSF250 Circuit Breakers Supplementary Technical InformationTM50DP TM90DP 45 C 50 C 55 C 60 C 65 C 70 C Effect of High TemperaturesExample STR53UP Trip Units for Compact NSJ400-NSJ600 Circuit BreakersKA RMS Reflex TrippingMaximum Let- through I2t Amperes2 Seconds LET-THROUGH Curves AT 480Maximum Peak Let-through Current Amperes Seconds LET-THROUGH Curves AT 600Maximum * Let CURRENT-LIMITING Curves AT 380/415CURRENT-LIMITING Curves AT 690 Calibration UL 489 Test ProcedureStandard Specifications TemperatureEndurance OverloadTests On AccessoriesDielectric Optional TestsTwo Categories of Devices Breaking Capacity IEC 947-2 Test ProcedureFunction IsolationSequence Category of Devices Tests Test SequencesRoutine and Maintenance Guidelines Insulation Resistance Tests Page Replaces 0615CT9901 dated 03/1999