Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Section
UL 489 TEST PROCEDURE
Standard Tests For electronic trip circuit breakers and uncompensated
Test |
| Sequence |
| |
|
| X | Y | Z |
200% | Calibration at 25° C (77° F) | ■ | ■ | ■ |
|
|
|
|
|
135% | Calibration at 25° C (77° F) | ■ |
|
|
|
|
|
| |
Calibration of Adjustable Instantaneous Trip | ■ |
|
| |
|
|
|
| |
Overload | ■ |
|
| |
|
|
|
| |
Tungsten Lamp Load | ① |
|
| |
|
|
|
|
|
100% | Calibration at 40° C (104° F) | ② |
|
|
|
|
|
| |
Temperature and 100% Calibration at 25° C (77° F) | ■ |
|
| |
|
|
|
| |
Endurance |
| ■ |
| |
|
|
|
|
|
200% | Calibration at 25° C (77° F) Repeated |
| ■ |
|
|
|
|
|
|
135% | Calibration at 25° C (77° F) Repeated |
| ■ |
|
|
|
|
| |
Interrupting Ability (Y sequence) |
| ■ |
| |
|
|
|
| |
Interrupting Ability (Z sequence) |
|
| ■ | |
|
|
|
|
|
200% | Trip Out at 25° C (77° F) |
| ■ | ■ |
|
|
|
| |
Dielectric Voltage Withstand | ■ | ■ | ■ |
①Applies only to circuit breakers rated 50 A or less, and 125 or 125/250 V or less.
②Applies only to
Standard
Specifications
Temperature | The temperature rise at the circuit breaker and at its terminals does not exceed specified limits when | |||
| connected with specified cables or bus bars (see below) and at its rated current. | |||
| Examples of specified wires and bus: | |||
| • 75° C Copper Wire |
|
| |
|
|
|
|
|
| Rating | Number | Size |
|
| 100 A | 1 | #1 AWG (60° C) |
|
|
|
|
| |
| 1 | #3 AWG | ||
|
| |||
|
|
|
|
|
| 250 A | 1 | 250 kcmil | |
|
|
|
|
|
| 400 A | 2 | 3/0 AWG | |
|
|
|
|
|
| 600 A | 2 | 350 kcmil | |
|
|
|
|
|
| 800 A | 3 | 300 kcmil | |
|
|
|
|
|
| 1000 A | 3 | 400 kcmil | |
|
|
|
|
|
| 1200 A | 4 | 350 kcmil | |
|
|
|
|
|
•Copper Busbar
Rating | Number | Size | |
1600 A | 2 | 1/4 x 3 | |
|
|
| |
2000 A | 2 | 1/4 x 4 | |
|
|
| |
2500 A | 2 | 1/4 x 5 | |
|
| ||
4 | 1/4 x | ||
| |||
|
|
| |
3000 A | 4 | 1/4 x4 | |
|
|
|
| (1200 A or |
Calibration | 200% calibration at 25° |
| from three minutes for 30 A rated circuit breakers to 30 minutes for over 2000 A rated circuit breakers. |
135% calibration at 25°
© | 67 |