Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Section
Indications | Load indication (LED) in front (6): |
•Lights solid at 90% of Ir threshold
•Flashes at >105% or greater of Ir threshold
Test | Test connector in front (7) for connection to test kit to check circuit breaker operation after fitting the trip |
| unit or other accessories. |
Setting Example | Question: What is the overload protection threshold of a Compact NSJ400 circuit breaker equipped |
| with trip unit STR23SP where Io = 0.5 and Ir = 0.8? |
Answer: In x Io x Ir = 400 x 0.5 x 0.8 = 160 A
The same trip unit with the same settings, mounted on an NSJ600 circuit breaker will have the following tripping threshold: In x Io x Ir = 600 x 0.5 x 0.8 = 240 A.
06153066 | Io | .9 |
|
| Ir |
.8 |
| .9 | .93 | ||
|
| ||||
| .7 | 1 | .88 |
| .95 |
| .63 |
| .85 |
| .98 |
| .5 |
| .8 |
| 1 |
| x In |
|
| x Io | |
| 400 x 0.5 x 0.8 = 160 A |
|
|