Schneider Electric Class 615 dimensions IEC 947-2 Test Procedure

Page 70

Compact® NSF and NSJ 150 to 600 A Circuit Breakers

Section 13—Supplementary Technical Information

IEC 947-2 TEST PROCEDURE

Standard Tests Consisting of seven parts, the IEC 947 Standard applies to all low-voltage equipment designed for industrial application.

Three documents are to be consulted for circuit breakers and switches:

IEC 947-1: general regulations

IEC 947-2: circuit breakers

IEC 947-3: switches

Two Categories of Devices

Breaking Capacity

The IEC 947-1 standard defines two categories of devices:

Category A—devices not specifically designed to carry out chronometric selectivity

Category B—devices specifically designed to carry out chronometric selectivity; these circuit breakers possess a compulsory additional characteristic: short-time withstand (Icw)

Ultimate Breaking

Icu is the value to be taken into account when calculating an installation. The rule remains: Icu > Icc

Capacity: Icu

(maximum fault current of the installation).

Breaking

This characteristic indicates the ability of the device to eliminate short-circuit currents less than Icc and

Performance During

with a greater likelihood of occurring, generally near the application. Ics is expressed in % of Icu (values

Operation: Ics

retained by the standard IEC 25-50-75-100% of Icu). This test sequence designed to check the Ics

 

performance, groups together on the same device, following the breaking test (O-CO-CO, see page

 

72), certain checks such as:

 

Temperature rise under In

 

Calibration at 1.45 In

 

Leakage current (for devices suitable for disconnection)

 

The leakage current should not exceed 2 mA under the application voltage (0.5 mA when new). These

 

checks ensure that the device is able to carry out all its functions after elimination of a fault of Ics value

 

and to be put back in operation; hence the notion of breaking power performance during operation Ics.

70

© 1995–2003 Schneider Electric All Rights Reserved

Image 70
Contents Compact NSF and NSJ Page Table of Contents Compact Compact Circuit Breaker LineRated Current a Interrupting Rating at 480General Characteristics Compliance with StandardsInstallation Class Switchboards Longer Service Life of Electrical InstallationsUL 489 Listed Ratings Circuit BreakersRatings and Interrupting Ratings IEC 947-2 and EN 60947-2 RatingsUltimate Breaking Capacity Icu Compact Circuit Breakers NSJ400 NSJ600 Rated VoltageKA rms Protection Trip UnitsTrip Units for Compact NSF150 and NSF250 Circuit Breakers Against overload 1 with a fixed thermal protectionTrip Units Trip Units for Compact NSJ400 and NSJ600 Circuit BreakersSTR53UP Protection With trip unit STR23SP where Io = 0.5 and Ir = 0.8? Unit or other accessoriesSetting Example IndicationsProtection Overload Indications %Ir Fault IndicationsElectronic Trip Unit STR53UP Self-monitoringOptions for Electronic TripMini Test Kit and Hand-held Test Kit Electronic Trip Unit Test KitsPortable Test Kit Full-function IEC 947-3 Ratings SwitchesUL 1087 Listed Ratings NSF150A NSF250AShort-circuit Withstand Current NSJ400A NSJ600AUL 489 Recognized Component Motor Circuit ProtectorsNSF150HC NSF250HC NSJ400HC NSJ600HC Connections Mounting ConfigurationsFixed Mounting PLUG-IN MountingMounting Parts of a Plug-in ConfigurationDrawout Mounting Horizontally or verticallyAccessories Connection of AuxiliariesConnection to Cables ConnectionsFront Connection Copper or Aluminum CablePlug-in Mounting Drawout Rear ConnectionConnection to Bars Compact Circuit Breake r NSF150/250 NSJ400/600Location AccessoriesPlug-in and Drawout Mounting Automatic Secondary Disconnecting Blocks Auxiliary and Alarm Switches UL 489 and CSA C22.2 No .1 Ratings Electrical RatingsIEC 947 Ratings Shunt trip MX Shunt Trip and Undervoltage TripUndervoltage trip OperationAutomatic Motor OperatorApplications Manual OperationNSJ400/600 Accessories forCharacteristics Keylock for locking in OFF positionRotary Operating Handles Directly MountedDoor Mounted Handle Cable Cable Operating HandleFlange-mounted OperatingLocking Systems Locking In the Off PositionInterlocking of Circuit Breakers Interlocking AccessoriesInterlocking of Circuit Breakers with Toggle Control With Rotary HandlesUse For Fixed or Plug- in Mounting Toggle BootFRONT-PANEL Escutcheons Front-panel Escutcheons for ToggleIdentification Sealing AccessoryFor Drawout Mounting Toggle CollarsFixed Mounted DimensionsDimensions Mounting on BackplateH53 H54 Front-panel Cutouts With Toggle Boot With EscutcheonC20 C21 R12 R13PLUG-IN and Drawout Mounting Dimensions Plug-in On BaseDrawout On Chassis On Rails Plug-in Base or Chassis See Fixed-mounted InstallationMounting Through a Backplate Plug-in Base Front-panel Cutouts Plug-in MountingK11 K12 K13 K20 K21 C11 C17 G10 G11 G12 G13 G20 G21 H16 H17 H18 H19L10 P12 P44 Front-panel Cutouts Dimension TableMotor Operators C22 C23 H20 H21 H22 H23 L11 L12 P32 P33 P45 R14Compact NSF CABLE-OPERATING HandlesCompact NSJ Dimensions ROTARY-OPERATING HandlesFront-panel Cutout Drawout Mounting P35 P36 P37 P38 P40 P42 P43 P44 R14 R15 C11 C17 C22 C23 G36 G37 G38 G39 H10 H20 H23 H24 H25H26 K14 K15 L11 L12 L13 L14 L15 P34 ØT6 ØT7Extended Escutcheons For Toggle Front AccessoriesFront-panel Escutcheons Interlocking Systems L16 L17 R19Connection Dimensions Plug-in or Drawout Mounting G33 G35 P22 P23Manually-operated Circuit Breaker Wiring DiagramsMotor-operated Circuit Breaker OFF Supplementary Technical Information Trip Units for Compact NSF150-NSF250 Circuit BreakersTM50DP TM90DP Example Effect of High Temperatures45 C 50 C 55 C 60 C 65 C 70 C Trip Units for Compact NSJ400-NSJ600 Circuit Breakers STR53UPReflex Tripping KA RMSMaximum Peak Let-through Current Amperes LET-THROUGH Curves AT 480Maximum Let- through I2t Amperes2 Seconds LET-THROUGH Curves AT 600 SecondsCURRENT-LIMITING Curves AT 380/415 Maximum * LetCURRENT-LIMITING Curves AT 690 Temperature UL 489 Test Procedure Standard Specifications CalibrationOverload EnduranceOptional Tests AccessoriesDielectric Tests OnIEC 947-2 Test Procedure Two Categories of Devices Breaking CapacityIsolation FunctionTest Sequences Sequence Category of Devices TestsRoutine and Maintenance Guidelines Insulation Resistance Tests Page Replaces 0615CT9901 dated 03/1999