
Compact® NSF and NSJ 150 to 600 A Circuit Breakers
Section
Options for | Equipment | |||
Electronic Trip |
|
|
| |
Type | Residual Current | |||
Unit STR53UP | ||||
|
|
| ||
Tripping threshold | Ig | Adjustable (8 Settings) | ||
| ||||
|
|
| ||
| Accuracy | ± 15% | ||
|
| |||
|
|
|
| |
| Tripping time (ms) | Max. overcurrent time before tripping (Tg) | Adjustable (4 Settings + Constant I2t Function) 60, 140, 230, 350 | |
| Total Breaking Time | |||
|
| |||
|
|
|
|
Ammeter (I)
06153068 |
|
|
|
|
|
| A |
In | I1 | I2 | I3 |
A digital display continuously indicates the current of the phase with the greatest load. By pressing a scroll button, it is also possible to display successively the readings of I1, I2, I3 and I neutral. LEDs indicate the phase for which the current is displayed.
| A number of circuit breakers are interconnected one after another by a pilot wire. In the event of a | |
Interlocking (ZSI) | ||
| • If a given trip unit STR53UP detects the fault, it informs the upstream circuit breaker which applies | |
|
| the set time delay |
| • If the trip unit STR53UP does not detect the fault, the upstream circuit breaker trips after its shortest | |
|
| time delay |
| In this way, the fault is cleared rapidly by the nearest circuit breaker. In addition, thermal stresses on | |
| the circuits are minimized and time discrimination is maintained throughout the installation. | |
| The use of | |
Outputs | circuits wired by the user. | |
Communication | Transmission of the following data to Digipact® distribution monitoring and control modules: | |
(COM) | • | Settings |
| ||
| • Phase and neutral currents (rms values) | |
| • Highest current of the three phases | |
| • | Overload condition alarm |
Possible | • | I |
Combinations | • | T |
| • | I + T |
| • | I + COM |
| • I + T + COM | |
| • | ZSI |
| • | ZSI + I |
| • | ZSI + T |
• ZSI + I + T
• ZSI + I + COM
• ZSI + I + T + COM
© | 15 |