Miller Electric EXTREME 360 manual Connecting 1-Phase Input Power, =GND/PE Earth Ground

Page 18

4-3. Connecting 1-Phase Input Power

! Installation must meet all Na- tional and Local Codes − have only qualified persons make this installation.

1

8

!

!

=GND/PE Earth Ground

Disconnect and lockout/tag- out input power before con- necting input conductors from unit.

Always connect green or green/yellow conductor to supply grounding terminal first, and never to a line termi- nal.

10

7

9

.The Auto-Line circuitry in this unit

automatically adapts the power source to the primary voltage be- ing applied. Check input voltage available at site. This unit can be connected to any input power be- tween 208 and 575 VAC without removing cover to relink the pow- er source.

L1

L2

3

6

Tools Needed:

1

1

2 3

6

4

5

1Black And White Input Conductor (L1 And L2)

2Red Input Conductor

3Green Or Green/Yellow Grounding Conductor

4Insulation Sleeving

5Electrical Tape

Insulate and isolate red conductor as shown.

6Input Power Cord.

7Disconnect Device (switch shown in the OFF position)

8Disconnect Device Grounding Terminal

9Disconnect Device Line Terminals

Connect green or green/yellow grounding conductor to disconnect device grounding terminal first.

Connect input conductors L1 and L2 to disconnect device line terminals.

10 Overcurrent Protection

Select type and size of overcurrent protection using Section 4-5(fused disconnect switch shown).

Close and secure door on disconnect device. Remove lockout/tagout de- vice, and place switch in the On posi- tion.

804 531-A

OM-229 409 Page 14

Image 18
Contents Description OM-229 409EProcesses 2007−11Page Table of Contents Page Electric Shock can kill Symbol UsageArc Welding Hazards HOT Parts can cause severe burnsWelding can cause fire or explosion Fumes and Gases can be hazardousARC Rays can burn eyes and skin Flying Metal or Dirt can injure eyesFalling Unit can cause injury Welding Wire can cause injuryFire or Explosion hazard Moving Parts can cause injuryEMF Information Principal Safety StandardsCalifornia Proposition 65 Warnings About Implanted Medical DevicesSymboles utilisés UNE Décharge Électrique peut entraîner la mortDES Pièces Chaudes peuvent provoquer des brûlures graves LES Fumées ET LES GAZ peuvent être dangereuxLE Soudage peut provoquer un in cendie ou une explosion Risque D’INCENDIE OU D’EXPLO- Sion LE Bruit peut endommager l’ouïeLES Bouteilles peuvent exploser si elles sont endommagées LA Chute DE L’APPAREIL peut blesserProposition californienne 65 Avertissements LES Fils DE Soudage peuvent provoquer des blessuresLE Soudage À L’ARC risque de provoquer des interférences Principales normes de sécurité Information EMFEn ce qui concerne les implants médicaux OM-229 409 CV Mode SpecificationsCC Mode − IntroductionMinutes Welding Minutes Resting Duty Cycle And Overheating60% Duty Cycle Overheating− Installation Dimensions And WeightSelecting a Location Connecting 1-Phase Input Power =GND/PE Earth GroundConnecting 3-Phase Input Power Input Amperes At Rated Output Electrical Service GuideSingle-Phase Input Voltage Min Grounding Conductor Size In AWG/KcmilWeld Output Receptacles And Selecting Cable Sizes ARC Welding can cause Electromagnetic Interference350 ft 400 ft Put terminals Remote 14 Receptacle Information Socket InformationOptional Gas Valve Operation And Shielding Gas Connection OperationGas flow starts with remote contac- tor on Power Switch − OperationFront Panel Controls Mode Switch Setting Process Output On/Off Control Mode Switch SettingsMode Meter Reading At Idle Meter Reading While Welding Meter FunctionsLift-Arc TIG Procedure Stick Start ProcedureLow OCV Stick − Maintenance & Troubleshooting Do not remove case when blowing out inside of unitBlowing Out Inside Of Unit Troubleshooting Voltmeter/Ammeter Help DisplaysStart Your Professional Welding Career Now − Electrical Diagram Circuit Diagram211 328-F − Parts List Parts AssemblyPLG1 PLG13 174 Knob, Pointer .840 Dia X .250 Id W/Spring Clip−.21 212 Start Your Professional Welding Career Now SOCKET/WRENCH Selection Table Standard Metric Material Thickness Gauge Warranty Owner’s Record