4-5. Electrical Service Guide

NOTICE − INCORRECT INPUT POWER can damage this welding power source. Phase to ground voltage shall not exceed +10% of rated input voltage.

NOTICE − Actual input voltage should not be 10% less than minimum and/or 10% more than maximum input voltages listed in table. If actual input voltage is outside this range, output may not be be available.

Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommenda- tions are for a dedicated branch circuit sized for the rated output and duty cycle of the welding power source.

 

 

 

Single-Phase

 

 

 

 

 

 

 

 

 

 

Input Voltage

208

230

 

400

 

460

575

 

 

 

 

 

 

 

 

Input Amperes At Rated Output

60.8

54.6

 

29.7

 

25.4

19.9

 

 

 

 

 

 

 

 

Max Recommended Standard Fuse Rating In Amperes 1

 

 

 

 

 

 

 

Time-Delay 2

70

60

35

 

30

25

Normal Operating 3

80

80

45

 

40

30

Min Input Conductor Size In AWG/Kcmil 4

8

8

 

10

 

12

12

Max Recommended Input Conductor Length In Feet (Meters)

72

89

 

176

 

140

219

(22)

(27)

 

(54)

 

(43)

(67)

 

 

 

 

 

 

 

 

 

 

 

Min Grounding Conductor Size In AWG/Kcmil 4

8

8

 

10

 

12

12

 

 

 

Three-Phase

 

 

 

 

 

 

 

 

 

 

Input Voltage

208

230

 

400

 

460

575

 

 

 

 

 

 

 

 

Input Amperes At Rated Output

40.4

36.1

 

20.6

 

17.8

14.1

 

 

 

 

 

 

 

 

Max Recommended Standard Fuse Rating In Amperes 1

 

 

 

 

 

 

 

Time-Delay 2

45

40

25

 

20

15

Normal Operating 3

60

50

30

 

25

20

Min Input Conductor Size In AWG/Kcmil 4

8

10

 

12

 

14

14

Max Recommended Input Conductor Length In Feet (Meters)

119

96

 

175

 

150

234

(36)

(29)

 

(53)

 

(46)

(71)

 

 

 

 

 

 

 

 

 

 

 

Min Grounding Conductor Size In AWG/Kcmil 4

10

10

 

12

 

14

14

Reference: 2005 National Electrical Code (NEC) (including article 630)

1Consult factory for circuit breaker applications.

2“Time-Delay” fuses are UL class “RK5” .

3“Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” (65 amp and above).

4Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table 310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.

OM-229 409 Page 16

Image 20
Contents OM-229 409E ProcessesDescription 2007−11Page Table of Contents Page Symbol Usage Arc Welding HazardsElectric Shock can kill HOT Parts can cause severe burnsFumes and Gases can be hazardous ARC Rays can burn eyes and skinWelding can cause fire or explosion Flying Metal or Dirt can injure eyesWelding Wire can cause injury Fire or Explosion hazardFalling Unit can cause injury Moving Parts can cause injuryPrincipal Safety Standards California Proposition 65 WarningsEMF Information About Implanted Medical DevicesSymboles utilisés UNE Décharge Électrique peut entraîner la mortLE Soudage peut provoquer un in cendie ou une explosion DES Pièces Chaudes peuvent provoquer des brûlures gravesLES Fumées ET LES GAZ peuvent être dangereux LE Bruit peut endommager l’ouïe LES Bouteilles peuvent exploser si elles sont endommagéesRisque D’INCENDIE OU D’EXPLO- Sion LA Chute DE L’APPAREIL peut blesserLE Soudage À L’ARC risque de provoquer des interférences Proposition californienne 65 AvertissementsLES Fils DE Soudage peuvent provoquer des blessures En ce qui concerne les implants médicaux Principales normes de sécuritéInformation EMF OM-229 409 Specifications CC ModeCV Mode − IntroductionDuty Cycle And Overheating 60% Duty CycleMinutes Welding Minutes Resting Overheating Selecting a Location − Installation Dimensions And Weight Connecting 1-Phase Input Power =GND/PE Earth GroundConnecting 3-Phase Input Power Electrical Service Guide Single-Phase Input VoltageInput Amperes At Rated Output Min Grounding Conductor Size In AWG/Kcmil350 ft 400 ft Put terminals Weld Output Receptacles And Selecting Cable SizesARC Welding can cause Electromagnetic Interference Remote 14 Receptacle Information Socket InformationGas flow starts with remote contac- tor on Optional Gas Valve Operation And Shielding Gas ConnectionOperation Front Panel Controls Power Switch− Operation Mode Switch Settings Mode Meter Reading At Idle Meter Reading While WeldingMode Switch Setting Process Output On/Off Control Meter FunctionsLow OCV Stick Lift-Arc TIG ProcedureStick Start Procedure Blowing Out Inside Of Unit − Maintenance & TroubleshootingDo not remove case when blowing out inside of unit Troubleshooting Voltmeter/Ammeter Help DisplaysStart Your Professional Welding Career Now − Electrical Diagram Circuit Diagram211 328-F − Parts List Parts AssemblyPLG1 PLG13 174 Knob, Pointer .840 Dia X .250 Id W/Spring Clip−.21 212 Start Your Professional Welding Career Now SOCKET/WRENCH Selection Table Standard Metric Material Thickness Gauge Warranty Owner’s Record