Installing the Flux Shifter Assembly
The installation procedure for the flux shifter assembly, illustrated in Figure 3, varies depending on the type of breaker and existing trip device. In some cases, mounting holes must be added, termi- nal blocks relocated, or breaker side rails removed.
Breakers with EC or Power Sensor Trip Systems
1.Drill the flux shifter mounting holes in the left side of the breaker frame. The mounting hole pattern is illustrated in Figure 4. A
2.Mount the new flux shifter to the inside of the side frame with the three screws, lock washers, flat washers, and nuts supplied, as shown in Figure 5. Insert the screws from the outside of the side frame.
Figure 4. Pattern for flux shifter mounting holes in the side frame.
Mounting |
|
| |
Screws |
|
| |
Flux Shifter | |||
|
| ||
|
| ||
|
| Assembly | |
|
|
|
Figure 5. Flux shifter assembly mounted to the side frame.
Figure 3. Flux shifter assembly.