4. Service procedures
(J)Change the period of the filter timer
❏If the period of filter timer is not suitable (for example in case of dirty environment), the period can be shortened to half as follows:
aPress the TEST / CHK button for more than 4 seconds.
Section
1
AIR FLOW |
|
|
UNIT | UNIT No. | MODE |
FLAP | R.C. No. |
|
|
| |
| CODE No. | SET TEMP. |
TIMER SET |
|
|
| SETTING | FAN SPEED |
|
| |
| SET DATA |
|
SET CL |
|
|
| ON • |
|
| OFF • |
|
|
| TEST / CHK |
2
3
0213_M_I
bIn case of group control, if you want to change all units in group control collectively, proceed next step remaining “ALL” displayed.
If you want to change a unit individually, select the indoor unit address (UNIT No.) with UNIT button.
cSelect the CODE No. 02 with , (SET TEMP) button.
dChange the No. from 0 to 1 with , ( ) button.
4
AIR FLOW |
|
|
UNIT | UNIT No. | MODE |
FLAP | R.C. No. |
|
|
| |
| CODE No. | SET TEMP. |
TIMER SET |
|
|
| SET TEMP. | FAN SPEED |
| SETTING | |
|
| |
| SET DATA |
|
SET CL |
|
|
| ON • |
|
| OFF • |
|
|
| TEST / CHK |
EX:
UNIT No.
CODE No. 02
K type 150 hr → 75 hr
0214_M_I
ePress the SET button.
CODE No. 06, SET DATA and SETTING change from flashing to ON state.
fIf you made a mistake, press the CL button.
gFinally, press the TEST / CHK button.
SM830076
– 86 –