4. Service procedures
Section
1
2
3
4
(3)Meanings of alarm messages
If an error occurred in the air conditioner, the error condition is presented by indicating the error code in the wired remote controller display or by the combination of lamp statuses for operation, timer and heat
Possible causes of troubles |
| Wired remote | Wireless remote | |||
| controller | controller | ||||
|
|
|
|
| display | display |
|
| Remote controller is detecting |
| Error receiving of serial communications signal. | E01 | Operation lamp |
|
| unusual signal from indoor unit. |
|
|
| flashes |
|
|
| Error transmitting of serial communications signal. | E02 | ||
|
|
|
|
| ||
|
| • Indoor unit is detecting unusual signal from the remote controller and group control. | E03 | O: Operation lamp | ||
|
| (No serial communications signal) |
|
| ⬤: Timer lamp | |
|
|
|
|
|
| |
setting- | Improper setting of indoor unit or |
| Indoor unit address setting is duplicated. | E08 | ⬤:Heat | |
remote controller. |
| Remote controller address (RCU.ADR) is duplicated. | E09 | lamp | ||
• Mis |
|
|
|
|
| |
Indoor unit is detecting unusual |
| Error transmitting of serial communications signal | E10 |
| ||
errors | signal from signal option. |
|
|
|
| |
| Error receiving of serial communications signal. | E11 |
| |||
|
|
| ||||
|
|
|
|
| ||
communication | Improper setting of indoor unit or |
| When using flexible combination control, main indoor unit address | E14 |
| |
Outdoor unit is detecting |
| Error receiving of serial communications signal. | E06 |
| ||
|
| remote controller. |
| setting is duplicated. (judged by outdoor unit.) |
|
|
|
| Indoor unit is detecting unusual |
| Error receiving of serial communications signal. | E04 | Heat |
|
| signal from outdoor unit. |
| Error transmitting of serial communications signal | E05 | lamp flashes |
|
|
|
| |||
|
|
|
|
|
| ⬤:Operation lamp |
• Serial | unusual signal from indoor unit. |
|
|
| ||
| (Confirmation error of unit numbers included) |
| ⬤: Timer lamp | |||
|
|
| ||||
|
| Error transmitting of serial communications signal. | E07 | O: Heat | ||
|
|
|
|
|
| lamp |
|
| Auto. address setting is not |
| No. of judged indoor units or total capacity of indoor units is small. | E15 | |
|
|
|
| |||
|
| correct. |
| No. of judged indoor units or total capacity of indoor units is large. | E16 |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| Indoor unit is detecting unusual |
| Error transmitting of serial communications signal | E17 |
|
|
| signal from another indoor unit. |
|
|
|
|
|
|
| Error receiving of serial communications signal. | E18 |
| |
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| Improper setting of indoor unit or |
| Indoor unit group address is not correct. | L01 | Operation lamp and |
|
| remote controller. |
| Model setting of indoor unit is not matching the outdoor unit. | L02 | heat |
|
|
|
| flash at the same time. | ||
|
|
|
|
|
| |
|
|
|
| When using group control, main indoor unit address setting is duplicated. | L03 | |
|
|
|
| O: Operation lamp | ||
setting- |
|
| (judged by indoor unit.) |
| ||
|
|
| O: Heat | |||
|
|
|
| Outdoor unit address is duplicated. | L04 | ⬤: Timer lamp |
|
|
|
|
| ||
• Mis |
|
|
|
|
| |
|
| Improper wiring between indoor units. | L07 | lamp | ||
|
| (There is a group connection wiring in case of individual control.) |
| |||
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
| Indoor unit address (or group address) is not set. | L08 |
|
|
|
|
| Capacity code of indoor unit is not set. | L09 |
|
|
|
|
|
|
|
|
|
|
|
| Improper wiring of group control wiring. | L11 |
|
|
|
|
|
|
|
|
|
|
|
| Indoor unit model setting is improper (capacity) | L13 |
|
|
|
|
|
|
| |
Improper wiring connections of ceiling panel. | P09 | ⬤: Operation lamp | ||||
|
|
|
|
|
| O: Timer lamp |
device | Protective device in indoor unit |
| Thermal protector in indoor fan motor is activated. | P01 | ||
| O: Heat | |||||
|
| is activated. |
| Float switch is activated. | P10 | lamp |
|
|
|
|
| ||
protective | Protective device in outdoor unit |
| • Thermal protector in outdoor fan motor is activated. | P02 | Operation lamp and heat | |
| ||||||
is activated. |
| • Compressor thermal protector is activated. |
| |||
|
|
|
| • Power supply voltage is unusual. (The voltage is more than |
| alternately. |
|
|
|
|
| O: Operation lamp | |
of |
|
| 260 V or less than 160 V.) |
| ||
|
| Discharge gas temperature of comp. is unusual. | P03 | ⬤: Timer lamp | ||
Activation• |
|
| ||||
|
|
|
| O: Heat | ||
|
| High pressure switch is activated. | P04 | |||
|
|
|
| |||
|
|
|
| lamp | ||
|
|
|
|
|
| |
|
|
|
| Voltage drops. | P05 | |
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| Other indooor unit is warning. | P31 |
|
|
|
|
|
|
|
|
SM830076
– 58 –