Carrier 50BV020-064 Unit Troubleshooting, Problem, Possible Cause, Correction Procedure

Models: 50BV020-064

1 68
Download 68 pages 11.16 Kb
Page 53
Image 53

Table 28 — Unit Troubleshooting

PROBLEM

POSSIBLE CAUSE

CORRECTION PROCEDURE

Unit Will Not Start.

Loss of unit power

Check power source.

 

 

Check fuses, circuit breakers, disconnect switch.

 

 

Check electrical contacts.

 

Unit voltage not correct

Check and correct.

 

Open fuse

Check for short circuit in unit.

 

Open protection device

Check relays (phase monitor option), contacts, pressure switches.

 

Unit or motor contactor out of order

Test and replace if necessary.

Fan Does Not Operate.

Contactor or relay overload or out of order

Test and replace if necessary.

 

VFD not running

Perform VFD diagnostic test.

 

Motor defective

Test and replace if necessary.

 

Broken belt

Replace belt.

 

Loose electrical contact

Tighten contact.

Compressor is Noisy, But

Under voltage

Check and correct.

Will Not Start.

 

 

Defect in compressor motor

Replace compressor.

 

 

Missing phase

Check and correct.

 

Compressor seized

Check and replace if necessary.

Compressor Starts,

Compressor or contact defect

Test and replace if necessary.

But Does Not Continue

 

 

Unit is under charged

Check and correct any leaks. Add refrigerant.

to Run.

Unit is too big

Check load calculation.

 

 

Compressor is overloaded

Check protection device and replace.

 

 

Check for missing phase.

 

 

Check TXV.

 

 

Check temperature in suction discharge line.

Unit is Noisy.

Compressor noise

Check TXV and replace if necessary.

 

 

Compressor rotation incorrect; check and correct.

 

 

Check internal noise.

 

Tube vibration or condenser water problem

Check and correct.

 

Unit panel or part vibrating

Check and tighten appropriate part.

Unit Runs Continuously,

Unit is too small

Check load calculation.

But Has Low Capacity.

 

 

Low refrigerant or noncondensing gas present

Check for leaks and add refrigerant or gas as necessary.

 

 

Compressor defect

Check pressure and amps. Replace if necessary.

 

Insufficient flow of refrigerant in evaporator

Check filter drier and replace if necessary.

 

 

Check TXV and adjust or replace if necessary.

 

 

Check position of TXV bulb and equalizer.

 

Oil in evaporator

Drain evaporator.

 

Low airflow

Check filters, and clean or replace as necessary.

 

 

Check coils, and clean as necessary.

 

 

Check for restrictions in ductwork.

 

 

Check fan rotation and adjust.

 

 

Check fan motor.

 

 

Check belts for wear.

High Discharge Pressure.

Low waterflow in condenser

Purge air.

 

Dirty condenser tubes.

Clean condenser.

 

High temperature in condenser water

Check water tower fans and pumps.

 

Overcharged

Check and reclaim excess charge.

 

 

Adjust subcooling.

 

Noncondensing gas present

Verify and correct.

LEGEND

 

 

TXV — Thermostatic Expansion Valve

VFD — Variable Frequency Drive

53

Page 53
Image 53
Carrier 50BV020-064 specifications Unit Troubleshooting, Problem, Possible Cause, Correction Procedure