Carrier 50BV020-064 specifications Fan Performance - 50BVT,U,V034

Models: 50BV020-064

1 68
Download 68 pages 11.16 Kb
Page 35
Image 35
Table 17 — Fan Performance — 50BVT,U,V034

Table 17 — Fan Performance — 50BVT,U,V034

AIRFLOW

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

(cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

9,000

564

3,167

3.76

605

3,483

4.13

645

3,798

4.51

683

4,112

4.88

718

4,392

5.21

9,500

590

3,666

4.35

629

3,999

4.74

667

4,331

5.14

704

4,671

5.54

738

4,977

5.90

10,000

617

4,226

5.01

655

4,584

5.44

691

4,933

5.85

726

5,282

6.27

761

5,654

6.71

10,500

643

4,820

5.72

678

5,194

6.16

713

5,583

6.62

747

5,963

7.07

780

6,263

7.51

11,000

669

5,503

6.53

704

5,901

7.00

737

6,298

7.47

770

6,612

7.93

802

7,005

8.40

11,500

696

6,236

7.40

729

6,577

7.89

761

6,987

8.38

792

7,388

8.86

823

7,798

9.36

12,000

722

6,952

8.34

754

7,380

8.85

784

7,798

9.36

815

8,225

9.87

845

8,510

10.38

12,500

750

7,816

9.38

780

8,260

9.91

810

8,561

10.44

839

8,990

10.97

868

9,427

11.50

13,000

777

8,595

10.49

806

9,050

11.04

835

9,504

11.59

863

9,949

12.14

891

10,403

12.69

13,500

804

9,572

11.68

832

10,043

12.25

860

10,514

12.83

887

10,985

13.40

914

11,447

13.96

14,000

832

10,634

12.97

859

11,122

13.57

886

11,610

14.16

912

12,097

14.76

938

12,585

15.35

14,500

859

11,747

14.33

885

12,217

14.90

911

12,756

15.56

936

13,260

16.18

962

13,765

16.79

15,000

886

12,953

15.80

911

13,474

16.44

936

13,996

17.07

961

14,517

17.71

986

15,038

18.34

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

1.2

 

 

1.4

 

 

1.6

 

 

1.8

 

 

2.0

 

(cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

9,000

751

4,663

5.53

785

4,933

5.85

817

5,212

6.18

849

5,512

6.54

881

5,804

6.89

9,500

771

5,264

6.25

802

5,574

6.61

834

5,866

6.96

864

6,166

7.31

895

6,394

7.67

10,000

792

5,963

7.07

822

6,272

7.44

852

6,498

7.80

882

6,804

8.16

911

7,118

8.54

10,500

812

6,603

7.92

841

6,926

8.31

870

7,240

8.69

899

7,563

9.07

927

7,885

9.46

11,000

833

7,388

8.86

861

7,720

9.26

889

8,051

9.66

917

8,253

10.07

944

8,578

10.46

11,500

854

8,199

9.84

882

8,441

10.30

909

8,784

10.72

936

9,127

11.13

962

9,469

11.55

12,000

874

8,921

10.88

903

9,332

11.38

930

9,701

11.83

955

10,060

12.27

981

10,420

12.71

12,500

896

9,855

12.02

924

10,283

12.54

951

10,702

13.06

976

11,079

13.51

1001

11,456

13.97

13,000

919

10,857

13.24

945

11,302

13.79

972

11,747

14.33

997

12,166

14.84

1022

12,551

15.31

13,500

941

11,918

14.54

967

12,380

15.10

993

12,850

15.67

1018

13,303

16.23

1042

13,722

16.74

14,000

964

13,064

15.94

990

13,551

16.53

1015

14,030

17.11

1040

14,517

17.71

1064

14,979

18.27

14,500

987

14,269

17.41

1011

14,765

18.01

1036

15,261

18.62

1060

15,765

19.23

1084

16,260

19.83

15,000

1010

15,560

18.98

1034

16,081

19.62

LEGEND

Bhp — Brake Horsepower Input to Supply Fan

Watts — Input Power to Supply Fan Motor

NOTES:

1.Unit is available with the following motor and drive combina- tions: 7.5, 10, 15, 20 HP standard drive; 7.5, 10, 15, 20 HP medium-static drive; 7.5, 10, 15, 20 HP high-static drive.

For 7.5 HP standard drives, the drive range is 780 to 960 rpm. For 10, 15, 20 HP standard and 7.5 HP medium-static drives, the drive range is 805 to 991 rpm. For 10, 15, 20 HP

medium-static and 7.5 HP high-static drives the drive range is 960 to 1146 rpm. For 10, 15, 20 HP high-static drives the drive range is 1119 to 1335 rpm.

2.Italics indicates field-supplied drive required.

3.Manual backgroundManual background Do not operate in shaded area.

4.Static pressure losses must be applied to external static pres- sure before entering the fan performance table.

5.Interpolation is permitted, extrapolation is not.

6.Fan performance is based on filter, unit casing and wet coil losses.

7.This unit has one supply fan and one fan motor.

35

Page 35
Image 35