Carrier 50BV020-064 specifications 50BVU,X034 Low-BoyDimensions

Models: 50BV020-064

1 68
Download 68 pages 11.16 Kb
Page 11
Image 11
Fig. 9 — 50BVU,X034 (Low-Boy) Dimensions

CONNECTIONS

A

LIQUID LINE CIRCUIT 1

7/8 in. OD

B

LIQUID LINE CIRCUIT 2

7/8 in. OD

C

DISCHARGE LINE CIRCUIT 1

1-1/8 in. OD

D

DISCHARGE LINE CIRCUIT 2

1-1/8 in. OD

E

CONDENSATE DRAIN

1-1/4 in. FPT

F

ECONOMIZER DRAIN

1-1/4 in. FPT

REPLACEMENT FILTERS : EIGHT (8) AT 17 x 27 x 4 INCHES.

NOTES:

1.Dimensions in inches.

2.All units are rear return airflow configuration.

3.Recommended condenser match is ONE (1) 09DK034 (50/50 split).

4.Use proper piping practice for remote refrigerant connections. Refer to Carrier System Design Manual Part 3.

5.Recommended minimum service clearances are as follows:

a.Front and rear — 30 in. (762 mm)

b.Left or right side — 65 in. (1651 mm) for coil removal

c.Side opposite coil removal — 20 in. (508 mm)

Fig. 9 — 50BVU,X034 (Low-Boy) Dimensions

11

Page 11
Image 11
Carrier 50BV020-064 specifications 50BVU,X034 Low-BoyDimensions