SERVICE

SERVICE

MAINTENANCE CAUTION

Improper phase sequence will cause scroll compressor failure due to reverse rotation.

Signs of miswire are:

Excessive noise

Reverse rotation of 3 phase indoor fan

Rapid temperature rise on suction tube

No pressure differential

Correct immediately. Shut off power at disconnect and switch any 2 power leads at unit terminal block or pigtails.

Compressor Rotation — To determine whether or not the compressor is rotating in the proper direction:

1.Connect service gages to suction and discharge pressure fittings.

2.Energize the compressor.

The suction pressure should drop and the discharge pres- sure should rise, as is normal on any start-up. If the suc- tion pressure does not drop and the discharge pressure does not rise to normal levels:

3.Turn off power to the unit and tag disconnect.

4.Reverse any 2 of the unit power leads.

Reapply power to the unit. The suction and discharge pressure levels should now move to their normal start-up levels.

Also, check that the fan is rotating in the proper direction.

NOTE: When the compressor is rotating in the wrong direc- tion, the unit makes an elevated level of noise and does not provide cooling.

Fan Motor Replacement — If required, replace the fan motor with an equal or better type and efficiency motor with equal horsepower. The motor must be rated for a VFD or inverter application. Do not change the horsepower unless there is a system design requirement change and VFD size analysis.

CHECK/CHANGE VFD OUTPUT CURRENT LIMIT — The VFD provides additional fan motor protection by limiting the output current to a programmed value. This value has been factory set according to the factory-installed motor and VFD sizing options.

If the VFD and/or motor is replaced, the VFD setup mode parameter "tHr1" should be reprogrammed to the following calculated values for optimum motor protection and operating range:

For VFD size about equal to motor:

tHr1 = 100*motor nameplate Amps / VFD rated output Amps

MAINTENANCE

Cleaning Unit Exterior — Unit exterior panels should be wiped down using a damp soft cloth or sponge with a mix- ture of warm water and a mild detergent.

Coil Cleaning — Hot water, steam, and direct expansion coils must be cleaned at least once a year to maintain peak per- formance. Dirty coils can contribute to decreased heating or cooling capacity and efficiency, increased operating costs, and compressor problems on direct expansion systems. Dirt, grease, and other oils can also reduce the wettability of the coil surfaces, which can result in moisture blow-off from cooling coils and resulting water leakage problems. If the grime on the surface of the coils becomes wet, which commonly occurs with

cooling coils, microbial growth (mold) can result, causing foul odors and health related indoor air quality problems.

Coils can become dirty over a period of time, especially if air filter maintenance is neglected. Coils should be in- spected regularly and cleaned when necessary. Clean coils with a vacuum cleaner, fresh water, compressed air, or a bristle brush (not wire). Do not use high-pressure water or air. Damage to fins may result. Backflush coil to remove de- bris. Commercial coil cleaners may also be used to help re- move grease and dirt. Steam cleaning is NOT recommend- ed. After cleaning, use a fin comb of the correct fin spacing when straightening mashed or bent coil fins.

Units installed in corrosive environments should be cleaned as part of a planned maintenance schedule. In this type of application, all accumulations of dirt should be cleaned off the coil.

Inspection — Check coil baffles for tight fit to prevent air from bypassing the coil. Check panels for air leakage, particu- larly those sealing the fan and coil compartments. Check for loose electrical connections, compressor oil levels, proper re- frigerant charge, and refrigerant piping leaks. Before start-up, be sure all optional service valves are open.

Air Filters — The 50BV single-piece units come with 1-in. filters. The standard 1-in. filters provide lower pressure drop and longer filter service intervals. The 50BV modular units come with 4-in. filters.

Inspect air filters every 30 days and replace filters as necessary.

Replacement filters should have a minimum efficiency rat- ing of MERV 6 per ASHRAE rating procedures and be rated for up to 625 fpm velocity. Job requirements or local codes may specify higher minimum ratings.

Condensate Drains — Clean the drain line and unit drain pan at the start of each cooling season. Check flow by pouring water into the drain.

Water-Cooled Condensers — Water-cooled condens- ers may require cleaning of the scale (water deposits) due to improperly maintained closed-loop water systems. Sludge build-up may need to be cleaned in an open tower system due to inducted contaminants.

Local water conditions may cause excessive fouling or pit- ting of tubes. Condenser tubes should be cleaned at least once a year, or more often if the water is contaminated.

Proper water treatment can minimize tube fouling and pitting. If such conditions are anticipated, water treatment analysis is recommended. Refer to the System Design Manual, Part 5, for general water conditioning information.

Manual background CAUTION

Follow all safety codes. Wear safety glasses and rubber gloves when using inhibited hydrochloric acid solution. Observe and follow acid manufacturer’s instructions.

Isolate the supply and return water connections when re- moving piping to the condenser.

Clean condensers with an inhibited hydrochloric acid solu- tion. The acid can stain hands and clothing, attack concrete, and, without inhibitor, can attack steel. Cover surroundings to guard against splashing. Vapors from vent pipe are not harmful, but take care to prevent liquid from being carried over by the gases.

Warm solution acts faster, but cold solution is just as effec- tive if applied for a longer period.

49

Page 49
Image 49
Carrier 50BV020-064 specifications Service, Maintenance