Table 3B — Physical Data — 50BVT,U,V,W,X

UNIT 50BVT,U,V,W,X

034

 

044

 

054

 

064

NOMINAL CAPACITY (Tons)

30

 

40

 

50

 

60

OPERATING WEIGHT (lb)

 

 

 

 

 

 

 

50BVT,V…50BVW

2580…2645

 

4334…4404

 

5198…5298

 

5230…5330

50BVU…50BVX

2420…2485

 

4094…4164

 

4938…5038

 

4970…5070

COMPRESSOR

 

 

Copeland Scroll

 

 

Quantity

2

 

4

 

4

 

4

 

 

 

Number of Refrigerant Circuits

2

 

4

 

4

 

4

Oil (oz.)

 

 

 

 

 

 

 

Circuit 1…Circuit 2

140…140

 

110…110

 

140…140

 

140…140

Circuit 3…Circuit 4

 

110…110

 

140…140

 

140…140

REFRIGERANT TYPE

 

 

R-22

 

 

Expansion Device

TXV

 

TXV

 

TXV

 

TXV

 

 

 

Operating Charge (lb)

 

 

 

 

 

 

 

Circuit 1…Circuit 2

18.0…18.0

 

10.0…10.0

 

18.0…18.0

 

18.0…18.0

Circuit 3…Circuit 4

 

10.0…10.0

 

18.0…18.0

 

18.0…18.0

CONDENSER (50BVT,V,W only)

 

 

Tube-in-Tube Coaxial

 

 

Quantity of Manifolded Circuits

2

 

4

 

4

 

4

 

 

 

Nominal Flow Rate (GPM)

90

 

120

 

150

 

180

Water Flow Range (GPM)

60-120

 

80-160

 

100-200

 

120-240

Max. Water Working Pressure (PSIG)

400

 

400

 

400

 

400

Max. Refrig. Working Pressure (PSIG)

450

 

450

 

450

 

450

Min. Entering Water Temp. (°F)

50

 

50

 

50

 

50

Max. Entering Water Temp. (°F)

110

 

110

 

110

 

110

Waterside Volume (gal)

6.0

 

9.0

 

11.3

 

13.5

EVAPORATOR COIL

 

 

 

 

 

 

 

Rows…Fins/in.

4…12

 

3…12

 

4…12

 

4…12

Total Face Area (sq ft)

23.2

 

46.4

 

46.4

 

46.4

EVAPORATOR FAN

 

 

 

 

 

 

 

Quantity…Size

1…18x18

 

2…18x18

 

2…18x18

 

2…18x18

Type Drive

Belt

 

Belt

 

Belt

 

Belt

Nominal CFM

12,000

 

16,000

 

20,000

 

24,000

Motor Option 1 Qty…HP…Frame Size

1…7.5…213T

 

2…7.5…213T

 

2…7.5…213T

 

2…7.5…213T

Motor Option 2 Qty…HP…Frame Size

1…10…215T

 

2…10…215T

 

2…10…215T

 

2…10…215T

Motor Option 3 Qty…HP…Frame Size

1…15…254T

 

2…15…254T

 

2…15…254T

 

2…15…254T

Motor Option 4 Qty…HP…Frame Size

1…20…256T

 

 

2…20…256T

 

2…20…256T

Motor Nominal RPM

1750

 

1750

 

1750

 

1750

Fan Drive RPM Range

 

 

 

 

 

 

 

Standard (7.5 HP)

780-960

 

780-960

 

780-960

 

780-960

Standard (10, 15, 20 HP), Med Static (7.5 HP)

805-991

 

805-991

 

805-991

 

805-991

Med Static (10, 15, 20 HP), High Static (7.5 HP)

960-1146

 

960-1146

 

960-1146

 

960-1146

High Static (10, 15, 20 HP)

1119-1335

 

1119-1335

 

1119-1335

 

1119-1335

Motor Bearing Type

Ball

 

Ball

 

Ball

 

Ball

Maximum Allowable RPM

1450

 

1450

 

1450

 

1450

Motor Pulley Pitch Diameter

 

 

 

 

 

 

 

Std Fan Drive (7.5 HP)

5.2-6.4

 

5.2-6.4

 

5.2-6.4

 

5.2-6.4

Std Fan Drive (10, 15, 20 HP), Med Static (7.5 HP)

4.8-6.0

 

4.8-6.0

 

4.8-6.0

 

4.8-6.0

Med Static Fan Drive (10, 15, 20 HP), High Static (7.5 HP)

5.8-7.0

 

5.8-7.0

 

5.8-7.0

 

5.8-7.0

High Static Fan Drive (10, 15, 20 HP)

5.8-7.0

 

5.8-7.0

 

5.8-7.0

 

5.8-7.0

Motor Shaft Diameter (in.) (7.5, 10 HP)

13/8

 

13/8

 

13/8

 

13/8

Motor Shaft Diameter (in.) (15, 20 HP)

15/8

 

15/8

 

15/8

 

15/8

Belt, Qty…Type…Length (in.)

 

 

 

 

 

 

 

Std Fan Drive (7.5 HP)

2…B…48

 

2...B...48

 

2…B…48

 

2…B…48

Std Fan Drive (10, 15, 20 HP), Med Static (7.5 HP)

2…B…46

 

2…B…46

 

2…B…46

 

2…B…46

Med Static Fan Drive (10, 15, 20 HP), High Static 7.5 HP)

2…B…48

 

2…B…48

 

2…B…48

 

2…B…48

High Static Fan Drive (10, 15, 20 HP)

2…B…45

 

2…B…45

 

2…B…45

 

2…B…45

Pulley Center Line Distance (in.)

10.2-11.4

 

10.2-11.4

 

10.2-11.4

 

10.2-11.4

Speed Change Per Full Turn of Moveable Pulley Flange (RPM)

 

 

 

 

 

 

 

Std Fan Drive (7.5 HP)

36

 

36

 

36

 

36

Std Fan Drive (10, 15, 20 HP), Med Static (7.5 HP)

31

 

31

 

31

 

31

Med Static Fan Drive (10, 15, 20 HP), High Static (7.5 HP)

31

 

31

 

31

 

31

High Static Fan Drive (10, 15, 20 HP)

36

 

36

 

36

 

36

Fan Shaft Diameter (in.)

17/16

 

17/16

 

17/16

 

17/16

HIGH PRESSURE SWITCHES (PSIG)

 

 

 

 

 

 

 

Cutout

380 ± 10

 

380 ± 10

 

380 ± 10

 

380 ± 10

Reset (Auto)

300 ± 15

 

300 ± 15

 

300 ± 15

 

300 ± 15

LOW PRESSURE SWITCHES (PSIG)

 

 

 

 

 

 

 

Cutout

20 ± 3

 

20 ± 3

 

20 ± 3

 

20 ± 3

Reset (Auto)

40 ± 5

 

40 ± 5

 

40 ± 5

 

40 ± 5

REMOTE REFRIGERANT CONNECTIONS (50BVU,X Only)

 

 

 

 

 

 

 

Discharge (Hot Gas) Connection (in.) Qty…Size

2…11/8

 

4…11/8

 

4…11/8

 

4…11/8

Liquid Connection (in.) Qty…Size

2…7/8

 

4…7/8

 

4…7/8

 

4…7/8

RETURN AIR FILTERS

 

 

 

 

 

 

 

Quantity…Size (in.)

8…17x27x4

 

16…17x27x4

 

16…17x27x4

 

16…17x27x4