acceptable system static pressure. If the existing duct system is too small, larger ductwork must be installed.
The duct system and diffusers should be sized to handle the design airflow volumes quietly. To maximize sound attenuation of the unit's blower(s), the supply and return air plenums should be insulated for a length of at least 15 ft from the unit. Direct line of sight from return air grilles into the unit's return should be avoided. If return air is to be ducted to an equipment room, an elbow should be installed within the equipment room. Running a return air drop to near the floor of the room will aid in sound attenuation. Avoid transmitting vibrations generated by the movement of air in the ducting to the walls of the building. This is especially important where ductwork penetrates walls. The maximum recommended return air velocity is 1,000 fpm. Lower return air velocities will result in lower sound power levels. The use of round supply duct plenums should be considered, as it will significantly reduce low frequency sound at the equipment room. If rectangular supply plenums are used, the aspect ratio of the duct should be kept as small as possible (i.e., as close to square as possible). The large, flat surface areas associated with large aspect ratio duct systems will transmit sound to the space, and the potential for
Units with two fans should have a properly designed “pair of pants” duct connection. An adequate straight length of ducting from the unit should be allowed before elbows are installed. If connecting an elbow directly to the fan outlet, a minimum straight length of 2 fan diameters from the fan outlet is recommended. Elbows should turn in the direction of fan ro- tation, if possible. Abrupt turns will generate air turbulence and excessive noise. Turning vanes should be used in all short radi- us bends. Ensure that ducting does not obstruct access to the unit for routine servicing.
DUCT STATIC PRESSURE PROBE AND TUBING (VAV Only) — On VAV systems, the duct static pressure sensor and tubing are
Install the
AIRFLOW
PROBE
a50-7138ef
TUBING
Fig. 16 — Duct Static Pressure Probe
(P/N 39EK20462)
Use
50 ft
The static pressure control should be adjusted so that, at full airflow, all of the remote VAV terminal boxes receive the minimum static pressure required plus any downstream resis- tance. Control the system to the lowest static pressure set point that will satisfy airflow requirements. Lower static pressure set points reduce total required brake horsepower and reduce generated sound levels.
DUCT
IMPORTANT: Use tubing that complies with local codes. Improper location or installation of the supply duct pres- sure tubing will result in unsatisfactory unit operation and poor performance.
DUCT STATIC
PRESSURE
PROBE
BULKHEAD
FITTING
| EXPN |
| STAT |
| EDIT |
WARNING | ALARM |
1 2 3
SRVC
TEST
ALRM
LOCAL | SET | SCHD |
OFF |
|
|
REMOTE |
|
|
4 5 6
7 8 9
– 0 .
HIST ALGO
CLEAR
ENTER
WARNINGALARM
a50-7267ef
LOCAL
OFF
REMOTE
Fig. 17 — Display Panel Location on Unit Front Panel
20