Carrier 50BV020-064 specifications Fan Performance - 50BVT,U,V054 cont

Models: 50BV020-064

1 68
Download 68 pages 11.16 Kb
Page 39
Image 39
Table 19 — Fan Performance — 50BVT,U,V054 (cont)

Table 19 — Fan Performance — 50BVT,U,V054 (cont)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

AIRFLOW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.2

 

 

2.4

 

 

2.6

 

 

2.8

 

 

3.0

 

(cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

15,000

886

4,444

5.27

922

4,741

5.62

958

5,046

5.99

993

5,380

6.38

16,000

893

4,924

5.84

927

5,212

6.18

961

5,539

6.57

994

5,857

6.95

17,000

903

5,495

6.52

935

5,795

6.87

967

6,095

7.23

999

6,341

7.61

1031

6,664

8.00

18,000

912

6,095

7.23

943

6,324

7.59

974

6,629

7.95

1005

6,943

8.33

1035

7,266

8.72

18,500

919

6,359

7.63

950

6,664

8.00

980

6,970

8.36

1010

7,284

8.74

1039

7,606

9.13

19,000

925

6,690

8.03

955

6,996

8.39

984

7,310

8.77

1013

7,624

9.15

1042

7,955

9.54

19,500

932

7,048

8.46

962

7,362

8.83

991

7,676

9.21

1019

7,999

9.60

1047

8,330

9.99

20,000

940

7,423

8.91

969

7,746

9.29

997

8,060

9.67

1025

8,253

10.07

1053

8,578

10.46

20,500

946

7,798

9.36

975

8,121

9.74

1003

8,304

10.13

1030

8,630

10.53

1057

8,955

10.92

21,000

955

8,199

9.84

982

8,390

10.23

1010

8,715

10.63

1037

9,041

11.03

1063

9,375

11.44

22,000

971

8,913

10.87

998

9,238

11.27

1024

9,572

11.68

1050

9,915

12.09

1076

10,257

12.51

23,000

988

9,812

11.97

1014

10,155

12.39

1040

10,506

12.82

1065

10,848

13.23

1090

11,207

13.67

24,000

1006

10,771

13.14

1031

11,130

13.58

1056

11,490

14.02

1080

11,849

14.45

1104

12,217

14.90

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

3.2

 

 

3.4

 

 

3.6

 

 

3.8

 

 

4.0

 

(cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

15,000

16,000

17,000

1062

7,005

8.40

1093

7,353

8.82

18,000

1065

7,606

9.13

1095

7,946

9.53

18,500

1069

7,946

9.53

1098

8,286

9.94

1127

8,501

10.37

1156

8,861

10.81

19,000

1071

8,286

9.94

1100

8,493

10.36

1128

8,835

10.78

1157

9,195

11.22

1185

9,564

11.67

19,500

1076

8,518

10.39

1104

8,861

10.81

1132

9,212

11.24

1159

9,572

11.68

1187

9,932

12.12

20,000

1081

8,904

10.86

1108

9,247

11.28

1136

9,598

11.71

1163

9,958

12.15

1190

10,326

12.60

20,500

1084

9,298

11.34

1112

9,641

11.76

1138

9,992

12.19

1165

10,343

12.62

1191

10,711

13.07

21,000

1090

9,718

11.85

1116

10,060

12.27

1143

10,411

12.70

1169

10,771

13.14

1195

11,139

13.59

22,000

1102

10,608

12.94

1127

10,959

13.37

1153

11,319

13.81

1178

11,678

14.25

1203

12,046

14.69

23,000

1115

11,558

14.10

1139

11,918

14.54

1164

12,286

14.99

1188

12,653

15.43

1212

13,038

15.90

24,000

1128

12,585

15.35

1152

12,953

15.80

1176

13,329

16.26

1200

13,705

16.72

1223

14,090

17.19

LEGEND

Bhp — Brake Horsepower Input to Supply Fan

Watts — Input Power to Supply Fan Motor

NOTES:

1.Unit is available with the following motor and drive combina- tions: 7.5, 10, 15, 20 HP standard drive; 7.5, 10, 15, 20 HP medium-static drive; 7.5, 10, 15, 20 HP high-static drive.

For 7.5 HP standard drives, the drive range is 780 to 960 rpm. For 10, 15, 20 HP standard and 7.5 HP medium-static drives, the drive range is 805 to 991 rpm. For 10, 15, 20 HP medium- static and 7.5 HP high-static drives the drive range is 960 to 1146 rpm. For 10, 15, 20 HP high-static drives the drive range is 1119 to 1335 rpm.

2.Italics indicates field-supplied drive required.

3.Manual backgroundManual background Do not operate in shaded area.

4.Static pressure losses must be applied to external static pres- sure before entering the fan performance table.

5.Interpolation is permitted, extrapolation is not.

6.Fan performance is based on filter, unit casing and wet coil losses.

7.Bhp values are per fan. Watts values are per motor. Unit has 2 supply fans and 2 motors.