Carrier 50BV020-064 specifications

Models: 50BV020-064

1 68
Download 68 pages 11.16 Kb
Page 57
Image 57
LEGEND

 

 

 

 

 

 

LEGEND

Standard Components Legend:

BM

 

Blower Motor

BR

 

Blower Relay

CBR

24-v Circuit Breaker

CC

 

Compressor Contactor

CCH

Crankcase Heater (When Supplied)

CPM

Compressor Protection Module (Except MA480)

HPS

 

High Pressure Switch (380 psig)

LPS

 

Low Pressure Switch (20 psig)

MS

 

Motor Starter

RVR

 

Reversing Valve Relay (Heat Pumps Only)

RVS

 

Reversing Valve Solenoid (Heat Pumps Only)

Optional Components Legend:

BMR

Blower Motor Relay

CMFR

Compressor Malfunction Relay

CMR

Compressor Monitor Relay

EMS

Energy Management System Relay

 

 

 

 

 

 

Factory Wire

 

 

 

 

 

 

 

 

 

 

 

 

Field Wire

NOTES:

 

 

 

 

 

1.

See unit nameplate for electrical rating.

2.

All field wiring must be in accordance with NEC-NFPA #70.

3.

208/230-v units are factory wired for 230-v operation. For 208-v operation, remove ORG

 

 

 

lead and replace it with RED lead. Cap all unused leads.

4.

Check phase rotation on all scroll compressor units. Reverse rotation will damage the

 

 

 

compressor and void unit warranty.

5.

For alternative EMS coil voltages, consult factory.

57

Fig. 40 — 50BVT,U,V044-064 Constant Volume Wiring Schematic

Page 57
Image 57
Carrier 50BV020-064 specifications