LEGEND

55

 

LEGEND

Standard Components Legend:

#1

First Stage

#2

Second Stage

BM

Blower Motor (1 or 2 per Unit)

BR

Blower Relay

CBR

24-vac Circuit Breaker

CCCompressor Contactor

CPM

Compressor Protection Module (15 Ton and Larger Compressors)

HPS

High Pressure Switch

LPS

Low Pressure Switch

RV

Reversing Valve

 

Optional Components Legend:

AUX

Auxiliary Relay (for Pumps, Valves, etc.)

BMR

Blower Motor Relay

CMFR

Compressor Malfunction Relay

CMR

Compressor Monitor Relay

CS

Condensate Sensor (One per Drain Pan)

EMS

Energy Management System Relay

FS

Freeze Sensor

HGL

Hot Gas Limit (Bypass Only)

PM

Phase Monitor

 

 

 

 

 

 

Factory Wire

 

 

 

 

 

 

 

 

 

 

 

 

Field Wire

 

 

 

 

 

 

TRANSFORMER PRIMARY

LEAD COLOR

120White

208Red

240Orange

277Brown

380Purple or Yellow

460Black/Red

575Gray

NOTES:

1.See unit nameplate for electrical rating.

2.All field wiring must be in accordance with NEC-NFPA #70.

3.208/230-v units are factory wired for 208-v operation. For 230-v operation, remove ORG lead and replace with RED lead. Cap all unused leads.

4.Check phase rotation on all scroll compressor units. Reverse rotation will damage the compressor and void unit warranty.

5.For alternative EMS coil voltages, consult factory.

6.UPM board includes built in 30 to 60-second random start, 5-minute delay on break, 90-second low pres- sure bypass, and 5-second second stage delay.

7.Setting the UPM board test mode jumper to yes reduces all time delays to 5 seconds.

8.“Freeze” pins on UPM board must be jumped if freeze sensor is not installed.

Fig. 38 — 50BVC,E,Q020-034 Constant Volume Wiring Schematic

Page 55