Table 21 — Controller Set Points

Table 21 — Controller Set Points

DESCRIPTION

 

VALUE

 

UNITS

STATUS

FORCE

 

NAME

DISPLAY SCREENS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OMNIZONE:SETPT01:

 

 

 

 

 

 

 

 

 

 

 

 

Supply fan Status

 

 

 

 

 

 

 

 

 

 

 

 

Occupied Lo Setpoint

 

0.3

 

in. H2O

 

 

 

 

 

OccLow

Occupied Hi Setpoint

 

0.4

 

in. H2O

 

 

 

 

 

OccHgh

Unoccupied Lo Setpoint

 

0.3

 

in. H2O

 

 

 

 

 

UnOccLow

Unoccupied Hi Setpoint

 

0.4

 

in. H2O

 

 

 

 

 

UnOccHgh

OMNIZONE:SETPT02:

 

 

 

 

 

 

 

 

 

 

 

 

VAVRESETbaseline

 

 

 

 

 

 

 

 

 

 

 

 

Occupied Lo Setpoint

 

0

 

 

dF

 

 

 

 

 

OccLow

Occupied Hi Setpoint

 

0

 

 

dF

 

 

 

 

 

OccHgh

Unoccupied Lo Setpoint

 

0

 

 

dF

 

 

 

 

 

UnOccLow

Unoccupied Hi Setpoint

 

0

 

 

dF

 

 

 

 

 

UnOccHgh

OMNIZONE:SETPT03:

 

 

 

 

 

 

 

 

 

 

 

 

Heat/Cool Mode & Reset

 

 

 

 

 

 

 

 

 

 

 

 

Occupied Lo Setpoint

 

70

 

 

dF

 

 

 

 

 

OccLow

Occupied Hi Setpoint

 

74

 

 

dF

 

 

 

 

 

OccHgh

Unoccupied Lo Setpoint

 

55

 

 

dF

 

 

 

 

 

UnOccLow

Unoccupied Hi Setpoint

 

85

 

 

dF

 

 

 

 

 

UnOccHgh

OMNIZONE:SETPT04:

 

 

 

 

 

 

 

 

 

 

 

 

Head Pressure Control

 

 

 

 

 

 

 

 

 

 

 

 

Occupied Lo Setpoint

 

225

 

PSIG

 

 

 

 

 

OccLow

Occupied Hi Setpoint

 

225

 

PSIG

 

 

 

 

 

OccHgh

Unoccupied Lo Setpoint

 

225

 

PSIG

 

 

 

 

 

UnOccLow

Unoccupied Hi Setpoint

 

225

 

PSIG

 

 

 

 

 

UnOccHgh

OMNIZONE:SETPT05:

 

 

 

 

 

 

 

 

 

 

 

 

Supply Static Pressure

 

 

 

 

 

 

 

 

 

 

 

 

Occupied Lo Setpoint

 

1.5

 

in. H2O

 

 

 

 

 

OccLow

Occupied Hi Setpoint

 

1.5

 

in. H2O

 

 

 

 

 

OccHgh

Unoccupied Lo Setpoint

 

1.5

 

in. H2O

 

 

 

 

 

UnOccLow

Unoccupied Hi Setpoint

 

1.5

 

in. H2O

 

 

 

 

 

UnOccHgh

OMNIZONE:SETPT06:

 

 

 

 

 

 

 

 

 

 

 

 

Supply Air Temperature

 

 

 

 

 

 

 

 

 

 

 

 

Occupied Lo Setpoint

 

55

 

 

dF

 

 

 

 

 

OccLow

Occupied Hi Setpoint

 

55

 

 

dF

 

 

 

 

 

OccHgh

Unoccupied Lo Setpoint

 

55

 

 

dF

 

 

 

 

 

UnOccLow

Unoccupied Hi Setpoint

 

55

 

 

dF

 

 

 

 

 

UnOccHgh

OMNIZONE:SETPT07:

 

 

 

 

 

 

 

 

 

 

 

 

Building Static Pressure

 

 

 

 

 

 

 

 

 

 

 

 

Occupied Lo Setpoint

 

0.02

 

in. H2O

 

 

 

 

 

OccLow

Occupied Hi Setpoint

 

0.02

 

in. H2O

 

 

 

 

 

OccHgh

Unoccupied Lo Setpoint

 

0.02

 

in. H2O

 

 

 

 

 

UnOccLow

Unoccupied Hi Setpoint

 

0.02

 

in. H2O

 

 

 

 

 

UnOccHgh

OMNIZONE:SETPT08:

 

 

 

 

 

 

 

 

 

 

 

 

BSP raw control

 

 

 

 

 

 

 

 

 

 

 

 

Occupied Lo Setpoint

 

12.32

 

ma

 

 

 

 

 

OccLow

Occupied Hi Setpoint

 

12.32

 

ma

 

 

 

 

 

OccHgh

Unoccupied Lo Setpoint

 

12.32

 

ma

 

 

 

 

 

UnOccLow

Unoccupied Hi Setpoint

 

12.32

 

ma

 

 

 

 

 

UnOccHgh

OMNIZONE:SETPT09:

 

 

 

 

 

 

 

 

 

 

 

 

Humidity Control

 

 

 

 

 

 

 

 

 

 

 

 

Occupied Lo Setpoint

 

0

 

%RH

 

 

 

 

 

OccLow

Occupied Hi Setpoint

 

99

 

%RH

 

 

 

 

 

OccHgh

Unoccupied Lo Setpoint

 

0

 

%RH

 

 

 

 

 

UnOccLow

Unoccupied Hi Setpoint

 

99

 

%RH

 

 

 

 

 

UnOccHgh

CHECK SYSTEM PARAMETERS — To

 

check

system

parameters, press the

 

 

button. The LID display will

 

STAT

show: “Hardware Points”. Press

 

 

to view the hard-

ENTER

ware points. The user can navigate up and down through the

points with the

and

keys.

Press 2 and STAT to display the software points. The user

can navigate up and down through the points with the Table 22 — Controller Hardware Points and

Table 23 — Software PointsManual backgroundManual background keys.

Refer to Tables 22 and 23 for hardware and software points.

Table 22 — Controller Hardware Points

DESCRIPTION

VALUE

UNITS

STATUS

FORCE

NAME

DISPLAY SCREENS

 

 

 

 

 

OMNIZONE:HWP01-32:

 

 

 

 

 

Hardware points Table 1

 

 

 

 

 

Supply Air Temperature

67

dF

 

 

SAT

Duct Static Pressure

0.2

in. H2O

 

 

DSP

Comp. Status MUX

1.86

Volts

 

 

CSMUX

Fire Alarm/ShutDown

Enable

 

 

 

FSD

Cond. Water Flow Switch

Yes

 

 

 

CDWF

Remote Occupancy

Disable

 

 

 

ROCC

Duct High Press. Switch

Normal

 

 

 

DHS

Entering Water Temp.

69.9

dF

 

 

EWT

Compressor 1 Relay

Stop

 

 

 

CMP1

Compressor 2 Relay

Stop

 

 

 

CMP2

Compressor 3 Relay

Stop

 

 

 

CMP3

Compressor 4 Relay

Stop

 

 

 

CMP4

Supply Fan/VFD

Stop

 

 

 

SF

VFD Speed Signal

0

%

 

 

SPEED

Non Critical Fault

Off

 

 

 

WARN

Critical Fault

Off

 

 

 

ALARM

Mixed/Return Air Temp

77.2

dF

 

 

MA_RA

Dirty Filter Status

Clean

 

 

 

FLTS

Phase Loss Protection

Normal

 

 

 

PHASE

Ext. Supply Air Reset

0

dF

 

 

RESET

Water Econ. FreezeStat

Normal

 

 

 

FREEZ

Space_Reset Sensor

79.2

dF

 

 

SPT

VFD Bypass Enable

Disable

 

 

 

BYPAS

Head Pressure(Comp1)

118.76

PSIG

 

 

PRES

Ventilation Request

Close

 

 

 

VENTR

VAV Terminals Control

No

 

 

 

TRMCT

2-position/Econo Valve

0

%

 

 

ECONO

Reverse/Head Press Ctrl

100

%

 

Control

MVLV

Hot Water Valve

0

%

 

 

HWV

Heat Interlock Relay

Off

 

 

 

HIR

Bypass Start_Stop

Stop

 

 

 

BPS_S

VAV Terminals Open MAX

Close

 

 

 

TRMOP

OMNIZONE:HWP33-64:

 

 

 

 

 

Hardware points table 2

 

 

 

 

 

Cooling Tower Sump

57.5

dF

 

 

TWR

Temp.

 

 

 

 

 

 

 

Building Static Milliamp

12.51

ma

 

 

BSP

Condenser Leaving Water

70.3

dF

 

 

LWT

Indoor Air Quality

587.21

 

 

 

IAQ

Indoor Relative Humidity

49.7

%

 

 

IRH

Outdoor Air Temp.

76.1

dF

 

 

OAT

Heat Stage 1

Off

 

 

 

HEAT1

Heat Stage 2

Off

 

 

 

HEAT2

Heat Stage 3

Off

 

 

 

HEAT3

Heat Stage 4

Off

 

 

 

HEAT4

Pump Request

Off

 

 

 

PUMP

Cooling Tower Request

Off

 

 

 

TOWER

Exhaust Fan

0

%

 

 

EXH

Ext. Dehumidification

Stop

 

 

 

DEHUM

Table 23 — Software Points

DESCRIPTION

VALUE

UNITS

STATUS

FORCE

NAME

DISPLAY SCREENS

 

 

 

 

 

OMNIZONE:SWP65-96:

 

 

 

 

 

Software Points

 

 

 

 

 

Compressor 1 Status

Off

 

 

 

CLO1

Compressor 2 Status

Off

 

 

 

CLO2

Compressor 3 Status

Off

 

 

 

CLO3

Compressor 4 Status

Off

 

 

 

CLO4

Bypass Acc Panel Secure

No

 

 

 

BP_SAFE

DX VAVRESET control

0

dF

 

 

VAVRESET

Factory/Field Test

Stop

 

 

 

FLDTST

Building Static Pressure

0.03

in. H2O

 

 

BSP_IN

Time Clock

Off

 

 

 

TIMCLOCK

Cooling

Disable

 

 

 

COOLOK

Supply Fan Status

Off

 

 

Control

SFS

Ok to run Fan

No

 

 

 

OKFAN

OK Fan + Sup. Fan Stat

FALSE

 

 

 

SF_SFS

Fan + Cond. Water Flow

FALSE

 

 

 

FAN_CDWF

Equipment Mode

Cool

 

 

Control

MODE

Activate Evacuation

Disable

 

 

 

EVAC

Mode

 

 

 

Space Control Point

74

dF

 

 

CTRLPT

Mod. Econ Enabled

No

 

 

Control

ECON_OK

Head Pressure Control

Disable

 

 

Control

HEAD

Economizer Control

77.22

dF

 

 

ECONPT

Temp.

 

 

 

 

 

 

 

Compressor Cooling

Disable

 

 

 

COMPRES

Duct Static Failure

Normal

 

 

 

DSP_ALM

Compressor 1 Alarm

Normal

 

 

 

C1_ALM

Compressor 2 Alarm

Normal

 

 

 

C2_ALM

Compressor 3 Alarm

Normal

 

 

 

C3_ALM

Compressor 4 Alarm

Normal

 

 

 

C4_ALM

Cond. Flow Alarm Status

Disable

 

 

Control

CDWF_ST

46

Page 46
Image 46
Carrier 50BV020-064 specifications Controller Set Points, Controller Hardware Points, Software Points