Table 15 — Fan Performance — 50BVC,E,Q028

Table 15 — Fan Performance — 50BVC,E,Q028

AIRFLOW

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

(cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

6,250

624

678

0.79

689

797

0.92

753

917

1.06

815

1045

1.21

7,000

604

751

0.87

666

880

1.02

726

999

1.16

784

1136

1.32

841

1273

1.48

7,500

634

889

1.03

693

1027

1.19

750

1155

1.34

805

1291

1.50

858

1437

1.67

8,000

667

1054

1.22

723

1191

1.38

777

1337

1.55

829

1482

1.72

880

1627

1.89

8,500

700

1237

1.43

753

1382

1.60

804

1528

1.77

853

1682

1.95

902

1836

2.13

9,000

735

1437

1.67

785

1591

1.84

833

1745

2.02

881

1908

2.21

927

2071

2.40

9,500

769

1664

1.93

816

1827

2.12

863

1989

2.31

908

2152

2.50

952

2323

2.69

10,000

802

1908

2.21

848

2080

2.41

892

2251

2.61

936

2422

2.81

978

2624

3.01

10,500

835

2179

2.53

879

2350

2.73

921

2531

2.93

963

2742

3.14

1004

2924

3.35

11,000

870

2467

2.86

912

2688

3.08

952

2870

3.29

992

3060

3.51

1032

3251

3.73

11,500

904

2824

3.24

944

3015

3.46

983

3206

3.67

1022

3405

3.90

1060

3605

4.13

12,000

937

3169

3.63

976

3369

3.86

1014

3569

4.09

1051

3777

4.33

1088

3985

4.57

12,500

972

3550

4.07

1010

3759

4.31

1046

3967

4.55

1082

4184

4.80

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

1.2

 

 

1.4

 

 

1.6

 

 

1.8

 

 

2.0

 

(cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

6,250

877

1173

1.36

7,000

897

1410

1.63

951

1555

1.80

7,500

911

1582

1.83

963

1727

2.00

1014

1881

2.18

8,000

930

1781

2.07

979

1935

2.24

1028

2098

2.43

1076

2260

2.62

1124

2422

2.81

8,500

950

1989

2.31

997

2152

2.50

1043

2323

2.69

1089

2485

2.88

1134

2697

3.09

9,000

973

2233

2.59

1018

2404

2.79

1062

2576

2.99

1106

2779

3.18

1149

2960

3.39

9,500

996

2494

2.89

1039

2697

3.09

1081

2879

3.30

1123

3060

3.51

1165

3251

3.73

10,000

1020

2806

3.22

1061

2988

3.42

1102

3178

3.64

1142

3360

3.85

1182

3559

4.08

10,500

1044

3106

3.56

1084

3296

3.78

1123

3496

4.01

1161

3686

4.23

1200

3886

4.45

11,000

1070

3451

3.95

1109

3641

4.17

1146

3840

4.40

1184

4049

4.64

1220

4248

4.87

11,500

1097

3804

4.36

1134

4012

4.60

1170

4221

4.84

1206

12,000

1124

4193

4.81

12,500

LEGEND

Bhp — Brake Horsepower Input to Supply Fan

Watts — Input Power to Supply Fan Motor

NOTES:

1.Units are available with 3 or 5 HP standard drive or 3 HP medium static drive.

For 3 HP standard drives, the drive range is 753 to 952 rpm. For medium static drives, the drive range is 872 to 1071 rpm. 5 HP standard drives have drive range of 967 to 1290 rpm.

2.Italics indicates field-supplied drive required.

3.Manual backgroundManual background Do not operate in shaded area.

4.Static pressure losses must be applied to external static pres- sure before entering the fan performance table.

5.Interpolation is permitted, extrapolation is not.

6.Fan performance is based on filter, unit casing and wet coil losses.

7.Bhp values are per fan. Watts values are per motor. Unit has 2 supply fans and 2 motors.

33

Page 33
Image 33
Carrier 50BV020-064 specifications Fan Performance - 50BVC,E,Q028