Ingersoll-Rand X41 technical manual C02

Page 12

compressor number) with an additional wire. Use a 7- conductor shielded cable in this instance.

Compressors that use electronic pressure detection but are not equipped with a remote pressure control enable feature will not automatically revert to local control if the X4I is stopped or experiences a fault or loss of power.

+VDC

+VDC

VFD/Fixed

 

Load Enable

 

Load/Unload

VFD/Fixed

 

Load Enable

 

Load/Unload

ir-PCB

Load, Sequence, and VFD Connections

Compressor controller inputs common voltage may be 0V or +V.

The local/remote pressure regulation input and/or remote load input logic of some electronic pressure sensor type controllers are reversed. In this instance, the “pressure switch” outputs (terminal C02) can be used to establish alternative logic control connections.

For Example:

If the compressor controller “Local/Remote Pressure Control” input is a normally open type (local when open, remote when closed), but the “Remote Load” input is a normally closed type (load when open), the IR-PCB pressure switch terminal contacts can be used to achieve the correct switching logic.

functions are internally connected and a short circuit condition and/or malfunction may result.

The IR-PCB connection examples shown in this manual are intended to provide a guide for the majority of compressor control systems in use. Some compressors have variations in operation and/or function; consult your compressor supplier/specialist for advice.

SERVICE MAINTENANCE SWITCH

The IR-PCB is equipped with a volt-free input (terminal C05) that can be used to remove the compressor from X4I control, without generating a fault condition, during short-term maintenance or servicing periods.

 

1

C05

2

 

Service Maintenance Switch Circuit

When the “Service Maintenance Switch” input terminal pins are connected together using a volt-free switching contact, the X4I will indicate that the compressor is not available but will not generate a warning, alarm, or shutdown condition. The X4I will also remove the compressor from the sequence strategy and substitute with an alternative available compressor if necessary. When the “Service Maintenance Switch” input circuit is open again, the compressor will automatically be accepted back in to the sequence strategy and will be utilized when next required.

The use of a “key switch” is recommended for this purpose in order to prevent the switch contacts being inadvertently left in the closed circuit condition after service maintenance is complete.

DO NOT connect any external voltage source to the pins of terminal C05.

C02

NO

OUT C

NC

NO

IN C

NC

Local/Remote common

Remote Load common

AUXILIARY INPUT (OPTION)

The X4I is equipped with an auxiliary input at terminals 31 and 32 (X07).

The function of the input is menu selectable and can be adapted for differing application requirements.

X07

Alternate Logic

Examine the “i-PCB” internal output circuit diagram to establish any desired switching logic that may differ from normal practice.

Do not attempt to utilize “Digital Pressure Regulation Control” (terminal C01) and the “Pressure Switch Control” (terminal C02) output connections at the same time for different products. These two output

32

31

Auxiliary Input Circuit

The input is designed to detect a remote “volt-free” switching contact (rated for a minimum 24VDC @ 10mA).

www.air.irco.com

12

X4I System Automation

 

Image 12
Contents More Than Air. Answers Table of Contents Intellisys S3 1of2 Intellisys S3 2of2 Introduction X4I System Automation Installation Power Supply Pressure Sensor Connection Input Functions Alarm Lamp Alarm Run ReadyOutput Functions C02 28 RS485 X06Specifications X4I Overview16 is a representation for After the conversion is completed Unigy Phase Unigy Phase 1 1of2Unigy Phase 1 2of2 Unigy Phase 2/3 Unigy Phase 2/3 1of2Unigy Phase 2/3 2of2 Nirvana 15 30KW 20 40HP Nirvana 15 30KW 20-40HP 1of2Nirvana 15 30KW 20-40HP Nirvana 15 30KW 20-40HP 2of2Page SSR Redeye SSR Redeye 1of3SSR Redeye FV SSR Redeye FV 2of3SSR Redeye SD SSR Redeye SD 3of3Page SE UP 1of2 0VAC 1M 110VACIntellisys SE UP Series SE UP 2of2 SE ESA 1of2 Intellisys SE ESA SeriesSE ESA 2of2 SE DSA 1of2 J5 34 33Intellisys SE DSA Contact Cooled SE DSA 2of2 Page SG SSR 1of2 1SbP2 3 2 Intellisys SGSG SSR 2of2 SG Sierra SG Sierra 1of2SG Sierra 2of2 Page SSR UP5 11-22 SD SSR UP5 11-22 SD 1of2SSR UP5 11-22 SD 2of2 SSR UP5 22-37 SD SSR UP5 22-37 SD 1of2Relay Contact Contact 110VACSSR UP5 22-37 SD 2of2 SSR UP6 15-30 FV SSR UP6 15-30 FV 1of2Restart TD Relay Contact To TR Relay To M ContactSSR UP6 15-30 FV 2of2 SSR UP6 15-30 SD SSR UP6 15-30 SD 1of2Contact To TR Relay To 1M Contact To 2M Contact VAC SSR UP6 15-30 SD 2of2 SSR UP6 40-50 FV SSR UP6 40-50 FV 1of2Relay Relay Contact Contact To TR Relay To 1M ContactSSR UP6 40-50 FV 2of2 C01 VFD/fixed Load Enable To TR Relay SSR UP6 40-50 SDSSR UP6 40-50 SD 1of2 Load/Unload To 1M ContactSSR UP6 40-50 SD 2of2 UP6 5-15 FV 1PH 60Hz UP6 5-15 FV 1PH 60Hz 1of2To CR Relay To HMUP6 5-15 FV 1PH 60Hz 2of2 UP6 5-15 FV 3PH 60Hz UP6 5-15 FV 3PH 60Hz 1of2UP6 5-15 FV 3PH 60Hz 2of2 UP6 5-15 SD 3PH 60Hz UP6 5-15 SD 3PH 60Hz 1of2110VAC To EDV To 1M/1S/2M Contacts To TD Relay VAC 1M UP6 5-15 SD 3PH 60Hz 2of2 UP6 5-15 FV 3PH 50Hz UP6 5-15 FV 3PH 50Hz 1of2To HM 110VAC HATSTo EDV KM1/KM2/KM3 Contacts To KM1 UP6 5-15 FV 3PH 50Hz 2of2 UP6 5-15 SD 3PH 50Hz UP6 5-15 SD 3PH 50Hz 1of2UP6 5-15 SD 3PH 50Hz 2of2 SSR M15-22c 20-30HP XF EP HP HXP 50-60Hz SSR M15-22c 20-30HP XF EP HP HXP 50-60Hz 1of2SSR M15-22c 20-30HP XF EP HP HXP 50-60Hz 2of2 M37-50 M37-50 1of2M37-50 2of2 EP 20-30 ESP FV EP 20-30 ESP FV 1of2EP 20-30 ESP FV 2of2 EP 20-30 ESP SD EP 20-30 ESP SD 1of2Contact To 1TD Relay To 2M Contact VAC EP 20-30 ESP SD 2of2 Page Nirvana SGN/SGNe Nirvana SGN/SGNe 1of3Nirvana SGN/SGNe 2of3 Nirvana SGN/SGNe 3of3 SI1 Interface to Redeye, SE, SG Controllers SI1 Interface to Redeye, SE, SG ControllersRedeye X4I Interconnect To Ingersoll Rand Intellisys S3 X4I Interconnect To Ingersoll Rand Intellisys S3Intellisys S3 Intellisys S3 1of2X04 X02Intellisys S3 2of2 Page UP6RE 7.5-15 175, UP6RX 7.5-15 UP6RE 7.5-15 175, UP6RX 7.5-15 175 1of3110VAC To ETM UP6RE 7.5-15 175, UP6RX 7.5-15 175 2of3 UP6RE 7.5-15 175, UP6RX 7.5-15 175 3of3 Models 2340, 2475, 2545, 7100, 15T Models 2340, 2475, 2545, 7100, 15T & 3000 10f3To Customer Supplied External Neutral External 110VAC Contact L2Models 2340, 2475, 2545, 7100, 15T & 3000 2of3 Models 2340, 2475, 2545, 7100, 15T & 3000 3of3 X4I Compressor #1 X01 Terminal Pressure