Ingersoll-Rand X41 technical manual Output Functions

Page 11

OUTPUT FUNCTIONS

The X4I will control the IR-PCB load/unload relay outputs based on the active system load and unload pressure setpoints. The IR-PCB load/unload relay contacts can be used for compressor controllers that have electro- mechanical pressure switch load/unload regulation.

+V

LOAD

SOLENOID

0V

NO

C

NC

NO

C

NC

 

OUT

C02

IN

 

 

 

 

 

Two Wire Pressure Switch Connections

LOAD

SOLENOID

+V

0V

IR-PCB Internal Output Circuits

The C01 and C02 terminals of the IR-PCB are intended to control load and unload regulation of the compressor.

PRESSURE SWITCH REGULATION

For air compressors fitted with an electro-mechanical pressure switch, a six-pin terminal C02 has been provided to enable connection to a pressure switch that has a two-wire or three-wire connection.

When connected, the pressure switch can be switched in and out of circuit automatically. If the X4I is stopped or experiences a failure or loss of power, pressure control will automatically revert back to the pressure switch and the compressor will continue to operate in “local” mode.

The local pressure settings of all compressors in the system should be set in a cascaded manner such that the system will operate normally in the event of X4I inoperability.

The NC (normally closed) and NO (normally open) terminal references of the IR-PCB are related to internal connection functions and should not be referenced to the connections of a compressor pressure switch, which will generally be in reverse order.

Lethal voltages may be present on the terminals of the air compressor pressure switch. Isolate the air compressor power supply before starting any work.

www.air.irco.com

11

 

RUN-ON

TIMER

NO

C

NC

NO

C

NC

 

OUT

 

 

IN

 

C02

Three Wire Pressure Switch Connections

DIGITAL REGULATION CONTROL TERMINAL C01

A 4-pin connector, C01, has been provided for air compressor controllers fitted with digital inputs allowing remote pressure regulation control.

This terminal provides volt free contact closure, referenced to a common terminal pin, for:

Remote Load Enable (remote/local pressure regulation control)

Remote Load (remote load/unload)

Remote Variable Speed Regulation Inhibit (remote variable/fixed speed regulation control)

The “remote load enable” function provides the facility to change the compressor load regulation from internal control to a remote switching source (local/remote).

V The “remote variable/fixed” function provides for multiple variable speed compressor regulation control on variable speed compressor(s) equipped with this facility.

When using the “Variable/Fixed” function, the “V” terminal of the IR-PCB must be connected to the appropriate “V” terminal of the X4I (according to

X4I System Automation

Image 11
Contents More Than Air. Answers Table of Contents Intellisys S3 1of2 Intellisys S3 2of2 Introduction X4I System Automation Installation Power Supply Pressure Sensor Connection Input Functions Alarm Run Ready Alarm LampOutput Functions C02 X06 28 RS485X4I Overview Specifications16 is a representation for After the conversion is completed Unigy Phase 1 1of2 Unigy PhaseUnigy Phase 1 2of2 Unigy Phase 2/3 1of2 Unigy Phase 2/3Unigy Phase 2/3 2of2 Nirvana 15 30KW 20-40HP 1of2 Nirvana 15 30KW 20 40HPNirvana 15 30KW 20-40HP 2of2 Nirvana 15 30KW 20-40HPPage SSR Redeye 1of3 SSR RedeyeSSR Redeye FV 2of3 SSR Redeye FVSSR Redeye SD 3of3 SSR Redeye SDPage Intellisys SE UP Series SE UP 1of20VAC 1M 110VAC SE UP 2of2 Intellisys SE ESA Series SE ESA 1of2SE ESA 2of2 Intellisys SE DSA Contact Cooled SE DSA 1of2J5 34 33 SE DSA 2of2 Page Intellisys SG SG SSR 1of21Sb P2 3 2SG SSR 2of2 SG Sierra 1of2 SG SierraSG Sierra 2of2 Page SSR UP5 11-22 SD 1of2 SSR UP5 11-22 SDSSR UP5 11-22 SD 2of2 Contact 110VAC SSR UP5 22-37 SDSSR UP5 22-37 SD 1of2 Relay ContactSSR UP5 22-37 SD 2of2 Contact To TR Relay To M Contact SSR UP6 15-30 FVSSR UP6 15-30 FV 1of2 Restart TD RelaySSR UP6 15-30 FV 2of2 Contact To TR Relay To 1M Contact To 2M Contact VAC SSR UP6 15-30 SDSSR UP6 15-30 SD 1of2 SSR UP6 15-30 SD 2of2 To TR Relay To 1M Contact SSR UP6 40-50 FVSSR UP6 40-50 FV 1of2 Relay Relay Contact ContactSSR UP6 40-50 FV 2of2 Load/Unload To 1M Contact C01 VFD/fixed Load Enable To TR RelaySSR UP6 40-50 SD SSR UP6 40-50 SD 1of2SSR UP6 40-50 SD 2of2 To HM UP6 5-15 FV 1PH 60HzUP6 5-15 FV 1PH 60Hz 1of2 To CR RelayUP6 5-15 FV 1PH 60Hz 2of2 UP6 5-15 FV 3PH 60Hz 1of2 UP6 5-15 FV 3PH 60HzUP6 5-15 FV 3PH 60Hz 2of2 110VAC To EDV To 1M/1S/2M Contacts To TD Relay VAC 1M UP6 5-15 SD 3PH 60HzUP6 5-15 SD 3PH 60Hz 1of2 UP6 5-15 SD 3PH 60Hz 2of2 To HM 110VAC HATSTo EDV KM1/KM2/KM3 Contacts To KM1 UP6 5-15 FV 3PH 50HzUP6 5-15 FV 3PH 50Hz 1of2 UP6 5-15 FV 3PH 50Hz 2of2 UP6 5-15 SD 3PH 50Hz 1of2 UP6 5-15 SD 3PH 50HzUP6 5-15 SD 3PH 50Hz 2of2 SSR M15-22c 20-30HP XF EP HP HXP 50-60Hz 1of2 SSR M15-22c 20-30HP XF EP HP HXP 50-60HzSSR M15-22c 20-30HP XF EP HP HXP 50-60Hz 2of2 M37-50 1of2 M37-50M37-50 2of2 EP 20-30 ESP FV 1of2 EP 20-30 ESP FVEP 20-30 ESP FV 2of2 Contact To 1TD Relay To 2M Contact VAC EP 20-30 ESP SDEP 20-30 ESP SD 1of2 EP 20-30 ESP SD 2of2 Page Nirvana SGN/SGNe 1of3 Nirvana SGN/SGNeNirvana SGN/SGNe 2of3 Nirvana SGN/SGNe 3of3 Redeye SI1 Interface to Redeye, SE, SG ControllersSI1 Interface to Redeye, SE, SG Controllers X4I Interconnect To Ingersoll Rand Intellisys S3 X4I Interconnect To Ingersoll Rand Intellisys S3X02 Intellisys S3Intellisys S3 1of2 X04Intellisys S3 2of2 Page 110VAC To ETM UP6RE 7.5-15 175, UP6RX 7.5-15UP6RE 7.5-15 175, UP6RX 7.5-15 175 1of3 UP6RE 7.5-15 175, UP6RX 7.5-15 175 2of3 UP6RE 7.5-15 175, UP6RX 7.5-15 175 3of3 External 110VAC Contact L2 Models 2340, 2475, 2545, 7100, 15TModels 2340, 2475, 2545, 7100, 15T & 3000 10f3 To Customer Supplied External NeutralModels 2340, 2475, 2545, 7100, 15T & 3000 2of3 Models 2340, 2475, 2545, 7100, 15T & 3000 3of3 X4I Compressor #1 X01 Terminal Pressure